| Plan Review Stops For Permit 07060569 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-18 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-18 |
Time |
17:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-10 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-10 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2007-09-10 08:02:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10' | | | ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE | | | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED | | | FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE | | | H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER | | | OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE | | | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED. | | | | | | 5TH REVIEW - CONTRACTOR HAS SENT A NOTE STATING THAT | | | THE SHUTTER SPAN IS 96", NOT 10FEET.PLEASE SEE THE | | | INSTALLATION SCHEDULE WHICH YOU HAVE COMPLETED.FOR | | | SPAN, YOU STATE THAT IT IS 111" FOR OPENING 1.THE | | | SPAN SHOULD BE THE BLADE LENGTH.ALL DIMENSIONS SHOULD | | | ALWAYS BE WIDTH X HEIGHT, AS STATED ON THE INSTALLATION | | | SCHEDULE AND AS IS INDUSTRY STANDARD FOR WINDOW AND | | | DOOR OPENINGS.IT APPEARS THAT YOU ARE USING THE WIDTH | | | TO STATE THE SPANS.AS SPAN IS BLADE LENGTH, THIS | | | SHOULD ALWAYS CORRELATE WITH THE HEIGHT DIMENSION. | | | PLEASE REVISE THE INSTALLATION SCHEDULE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-28 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-28 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2007-08-28 09:47:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)SEE PREVIOUS LISTS.TWO COMPLETE SETS OF PERMIT | | | DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS | | | SUBMITTED.DUE TO WORKLOAD, I AM UNABLE TO MAKE | | | COPIES.A PHOTOCOPY MACHINE HAS BEEN PROVIDED IN THE | | | LOBBY FOR THIS PURPOSE. | | | | | | 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10' | | | ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE | | | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED | | | FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE | | | H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER | | | OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE | | | PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-03 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-03 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2007-08-03 16:16:25 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)3" EDGE DISTANCE REQUIRES A FACTOR OF .83, SEE | | | SHEET 14 OF THE PRODUCT APPROVAL. | | | | | | 2.)PRESSURES DO NOT MATCH ENGINEERING. | | | | | | 3.)ANCHOR TYPE SHOULD BE ONE FROM THE PRODUCT | | | APPROVAL ANCHOR CHART, NOT "316 AISI".SEE PAGE 14. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-26 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-26 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2007-07-26 12:52:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)SHUTTER CONNECTION MOUNTING TYPES G AND H ARE FOR | | | POURED CONCRETE SUBSTRATE ONLY. | | | | | | 2.)I WAS UNABLE TO FIND W12 AND W14 AS CONNECTION | | | TYPES ON THE ANCHOR SCHEDULES IN THE PRODUCT APPROVAL. | | | | | | | | | 3.)INSTALLATION SCHEDULE SPECIFIES 1" DISTANCE FROM | | | GLASS; SEE SHEET 12 OF THE PRODUCT APPROVAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-06 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-06 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2007-07-06 14:43:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY | | | | | | _XX_1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN | | | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE | | | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A | | | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED | | | ORIGINALS FAC61G15-23.002. | | | | | | _XX_2.PROVIDE A COPY OF THE CONDO ASSOCIATION | | | APPROVAL. | | | | | | _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE | | | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT. | | | | | | ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. | | | | | | ____5.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS | | | APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A | | | HIGHLIGHTER. | | | | | | ____6.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC | | | R310. | | | | | | ____7.PROVIDE A FLOOR PLAN SHOWING WHERE THE | | | SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH | | | CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3 | | | ABOVE. | | | | | | _XX_8.PROVIDE INFORMATION IN REGARDS TO THE | | | SURROUNDING TERRAIN, FBC1609.6.2.1(2), FBC R301.2.1.4. | | | NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED | | | EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-14 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-14 |
Time |
10:13 |
Sent To |
B |
|
| Notes |
| 2007-09-14 10:13:40 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-05 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-05 |
Time |
13:11 |
Sent To |
B |
|
| Notes |
| 2007-09-05 13:12:11 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-13 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-13 |
Time |
11:45 |
Sent To |
B |
|
| Notes |
| 2007-08-13 11:45:49 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-02 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-02 |
Time |
14:26 |
Sent To |
B |
|
| Notes |
| 2007-08-02 14:27:18 | TO "SHLL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-13 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-13 |
Time |
16:10 |
Sent To |
B |
|
| Notes |
| 2007-07-13 16:11:06 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-06 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-22 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2007-06-22 09:27:23 | TO "MISC" BOX#1 |
|
|