Plan Review Details - Permit 07060569
Plan Review Stops For Permit 07060569
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-18 Cont ID  
Sent By shill Date 2007-09-18 Time 17:10 Rev Time 0.00
Received By shill Date 2007-09-18 Time 17:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-09-10 Cont ID  
Sent By shill Date 2007-09-10 Time 07:58 Rev Time 0.00
Received By shill Date 2007-09-10 Time 07:58 Sent To  
Notes
2007-09-10 08:02:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10'
 ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED
 FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE
 H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER
 OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.
  
 5TH REVIEW - CONTRACTOR HAS SENT A NOTE STATING THAT
 THE SHUTTER SPAN IS 96", NOT 10FEET.PLEASE SEE THE
 INSTALLATION SCHEDULE WHICH YOU HAVE COMPLETED.FOR
 SPAN, YOU STATE THAT IT IS 111" FOR OPENING 1.THE
 SPAN SHOULD BE THE BLADE LENGTH.ALL DIMENSIONS SHOULD
 ALWAYS BE WIDTH X HEIGHT, AS STATED ON THE INSTALLATION
 SCHEDULE AND AS IS INDUSTRY STANDARD FOR WINDOW AND
 DOOR OPENINGS.IT APPEARS THAT YOU ARE USING THE WIDTH
 TO STATE THE SPANS.AS SPAN IS BLADE LENGTH, THIS
 SHOULD ALWAYS CORRELATE WITH THE HEIGHT DIMENSION.
 PLEASE REVISE THE INSTALLATION SCHEDULE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-28 Cont ID  
Sent By shill Date 2007-08-28 Time 09:44 Rev Time 0.00
Received By shill Date 2007-08-28 Time 09:44 Sent To  
Notes
2007-08-28 09:47:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE PREVIOUS LISTS.TWO COMPLETE SETS OF PERMIT
 DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS
 SUBMITTED.DUE TO WORKLOAD, I AM UNABLE TO MAKE
 COPIES.A PHOTOCOPY MACHINE HAS BEEN PROVIDED IN THE
 LOBBY FOR THIS PURPOSE.
  
 2.)SEE OPENING 1.SPAN OF 111 REQUIERS USE OF 10'
 ROW, -52.7 REQUIES USE OF -60PSF COLUMN.SEE THE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.9" REQUIRED
 FOR CONNECTION TYPE G, 7" REQUIRED FOR CONNECTION TYPE
 H.PLEASE SEE PRODUCT APPROVAL AND REVISE.OTHER
 OPENING ANCHOR SPACINGS ARE ALSO INCORRECT; PLEASE SEE
 PRODUCT APPROVAL WHICH I HAVE HIGHLIGHTED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-03 Cont ID  
Sent By shill Date 2007-08-03 Time 16:08 Rev Time 0.00
Received By shill Date 2007-08-03 Time 16:08 Sent To  
Notes
2007-08-03 16:16:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)3" EDGE DISTANCE REQUIRES A FACTOR OF .83, SEE
 SHEET 14 OF THE PRODUCT APPROVAL.
  
 2.)PRESSURES DO NOT MATCH ENGINEERING.
  
 3.)ANCHOR TYPE SHOULD BE ONE FROM THE PRODUCT
 APPROVAL ANCHOR CHART, NOT "316 AISI".SEE PAGE 14.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 12:50 Rev Time 0.00
Received By shill Date 2007-07-26 Time 12:50 Sent To  
Notes
2007-07-26 12:52:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SHUTTER CONNECTION MOUNTING TYPES G AND H ARE FOR
 POURED CONCRETE SUBSTRATE ONLY.
  
 2.)I WAS UNABLE TO FIND W12 AND W14 AS CONNECTION
 TYPES ON THE ANCHOR SCHEDULES IN THE PRODUCT APPROVAL.
  
  
 3.)INSTALLATION SCHEDULE SPECIFIES 1" DISTANCE FROM
 GLASS; SEE SHEET 12 OF THE PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 14:39 Rev Time 0.00
Received By shill Date 2007-07-06 Time 14:39 Sent To  
Notes
2007-07-06 14:43:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 _XX_1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 _XX_2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____6.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____7.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 _XX_8.PROVIDE INFORMATION IN REGARDS TO THE
 SURROUNDING TERRAIN, FBC1609.6.2.1(2), FBC R301.2.1.4.
 NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 10:13 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 10:13 Sent To B
Notes
2007-09-14 10:13:40TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 13:11 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 13:11 Sent To B
Notes
2007-09-05 13:12:11TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 11:45 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 11:45 Sent To B
Notes
2007-08-13 11:45:49TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 14:26 Sent To B
Notes
2007-08-02 14:27:18TO "SHLL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 16:10 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 16:10 Sent To B
Notes
2007-07-13 16:11:06TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 14:43 Rev Time 0.00
Received By shill Date 2007-06-22 Time 09:26 Sent To  
Notes
2007-06-22 09:27:23TO "MISC" BOX#1