Plan Review Details - Permit 07060560
Plan Review Stops For Permit 07060560
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-23 Cont ID  
Sent By jwitmer Date 2007-08-23 Time 14:03 Rev Time 1.22
Received By jwitmer Date 2007-08-23 Time 13:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By jwitmer Date 2007-07-19 Time 20:00 Rev Time 1.11
Received By jwitmer Date 2007-07-19 Time 20:00 Sent To  
Notes
2007-07-19 20:28:53BUILDING PLAN REVIEW
 PERMIT: 07060560
 ADD: 2300 PRESIDENTAL WAY
 CONT: PURDY CONSTRUCTION & DEVELOPMENT
 TEL: (561)718-8080
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE SEE NOTES FROM ADDRESSING FOR ADDRESS TO BE
 USED FOR THIS STRUCTURE.
  
 4) FBC 1802.2.1 QUESTIONABLE SOILS,WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 5) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) OVERHEAD DOOR
 B) ROOFING ASSEMBLIES
  
 6)) THIS ROOF IS MISSING OR NOT INCOMPLIANCE
 WITH THE FOLLOW ITEMS:
 _XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XXX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR
 ZONE _2&3__ .
  
 _XXX__POSSIBILITY SUBSYTEM NOT MARKED,THE SYSTEM
 PROVIDED STATESLIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
  
 _XXX__POSSIBLY SUBSYSTTEM NOT MARKEDTHE SYSTEM
 PROVIDED INDICATES LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. 2004FBC BUILDING W/ 2006 REVISIONS
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-20 Cont ID  
Sent By dpalmer Date 2007-08-20 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2007-08-20 Time 16:23 Sent To B
Notes
2007-08-20 16:23:392ND SET OF PLANS BROUGHT IN BY CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By dpalmer Date 2007-08-20 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2007-08-20 Time 12:06 Sent To  
Notes
2007-08-20 12:27:47PLANS REMOVED FROM INCOMING PER NEIL MELICK.
  
 ELECTRICAL OK, HOWEVER ONLY ONE SET OF PLANS ARE
 COMPLETE.
 MISSING SURVEY SHEET WHICH WAS STAMPED BY ZONING.
 MISSING MAPS PLACE ON ONE SET.
 MISSING 2ND SET OF ELECTRICAL SPECS.
 MISSING 2ND SET OF ELECTRICAL RISER.
  
 ** CALLED MIKE PURDY AND SPOKE TO HIM AND HE ASKED FOR
 PLANS TO BE HELD WAITNG FOR 2ND SET.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 07:16 Rev Time 0.00
Received By dpalmer Date 2007-06-28 Time 16:37 Sent To I
Notes
2007-06-29 07:16:57 
  
 *** UNSAT ***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS AND
 ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 ** PLEASE SEE COMMENTS FROM FIRE AND OTHER TRADES FOR
 OTHER CODES REFERENCED.
  
 2) NOTE: PLEASE PROVIDE THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE MOTOR CONTROL EQUIPMENT . 110.3, 90.7
 FBC 106.1.2
  
 3) NOTE: PLEASE BE SURE THE ADDRESS IS STATED ON PLANS.
 PLEASE KNOW THIS WILL BE ROUTED TO ADDRESSING FOR
 POSSIBLE ADDRESS EXTENSION TO SITE ADDRESS. THERE ARE
 MORE THAN ONEBUILDING LOCATED IN THE COMMON AREA AND
 EACH SHOULD HAVE AN EXTENSION WHICH IS SPECIFIC TO THAT
 BUILDING OR STRUCTURE. FAC 61G1-16.004
  
 4) NOTE: PLEASE BE SURE ALL ELECTRICAL WHICH IS ON THE
 SEPARATE ELECTRICAL RISER IS ON PLANS AND IDENTIFIED AT
 EACH LOCATION. (SOME MISSING).
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE NOTES FROM OTHER TRADES FOR SURVEY
 WHICH IS REQUIRED TO HAVE AN ORIGINAL SIGNATURE PER FS
 472.025
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-28 16:38:40PLANS REMOVED FROM INCOMING AND WILL BE SENT BACK TO
 INCOMING ONCE ELECTRICAL REVIEW IS DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-23 Cont ID  
Sent By mawillia Date 2007-08-23 Time 13:02 Rev Time 0.00
Received By mawillia Date 2007-08-23 Time 12:44 Sent To  
Notes
2007-08-23 12:57:12*****APPROVED*****
  
 EACH ITEM FROM PREVIOUS REVIEW WAS ADDRESSED;
 SURVEY/SITE SHEETS STAMPED, INITIALED, AND DATED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 10:51 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 10:29 Sent To AD
Notes
2007-07-26 10:51:25******DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.PLEASE SHOW THE LOCATION OF THE PROPOSED STRUCTURE
 IN RELATION TO STREET(S) AND SURROUNDING BUILDING(S).
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OR
 VICINITY THEREOF ( ROADS, ALLEYS, FIRE LANES, ETC).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-08 Cont ID  
Sent By mmiller Date 2007-08-08 Time 18:49 Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:48 Sent To  
Notes
2007-08-08 18:49:09WAITING FOR COMMERCIAL BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 10:31 Rev Time 0.00
Received By mawillia Date 2007-06-19 Time 16:24 Sent To  
Notes
2007-06-29 11:11:53TO "COMM" BD#60
2007-06-19 16:24:38WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-22 Cont ID  
Sent By jroach Date 2007-07-22 Time 20:47 Rev Time 0.00
Received By jroach Date 2007-07-22 Time 20:47 Sent To  
Notes
***NONE***