Plan Review Details - Permit 07060548
Plan Review Stops For Permit 07060548
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-17 Cont ID  
Sent By jwitmer Date 2007-10-17 Time 07:44 Rev Time 1.00
Received By jwitmer Date 2007-10-17 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-20 Cont ID  
Sent By jwitmer Date 2007-07-20 Time 11:18 Rev Time 1.22
Received By jwitmer Date 2007-07-20 Time 11:18 Sent To  
Notes
2007-07-20 11:21:03BUILDING PLAN REVIEW
 PERMIT: 07060548
 ADD: 828 SOUTHERN BLVD
 CONT: POWER SECURE INC
 TEL: (919)818-8700
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.)
 GENERATOR SLAB & ANCHOR REQUIREMENT
  
 3) PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-04-29 Cont ID  
Sent By dpalmer Date 2008-04-29 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2008-04-29 Time 17:05 Sent To P
Notes
2008-04-29 17:05:56** DENIEDREVIEW **
  
 1) NOTE: PLEASE KNOW THE EVALUATION REPORT SUBMITTED BY
 POWER SECURE BY CSA INTERNATIONAL IS NOT ACCEPTABLE.
 AS STATED ON PREVIOUS REVIEW THE ENTIRE
 GENERATOR/SYSTEM NEEDS TO BE RE-LISTED. THE REPORT
 SUBMITTED SPECIFICALLY STATES THE GAS TRAIN UNIT IS THE
 ONLY ITEM WHICH WAS EVALUATED. THE REPORTS STATES THE
 GENERATOR IS UL LISTED AND HAS BEEN MODIFIED FROM THE
 ORIGINAL LISTING FROM CATERPILLAR AND NEEDS TO BE
 LISTED. THIS REVIEWER HAS CONTACTED CSA INTERNATIONAL.
 CONTACT WILL ALSO BE MADE TO PUBLIX DIRECTLY TO EXPRESS
 CONCERNS OVER LISTING.
 THE REPORT WILL BE RETAINED BY THIS OFFICE WAS REVIEWED
 BY ALL RELEVANT TRADES.
 110.3, 90.7
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-02-16 Cont ID  
Sent By dpalmer Date 2008-02-16 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2008-02-16 Time 18:51 Sent To P
Notes
2008-02-16 18:52:07** DENIEDREVIEW **
  
 1) NOTE: PLEASE SUBMIT THE COMPLETE CSA REPORT AND
 CERTIFICATION. THE DOCUMENTS SUBMITTED ARE NOT COMPLETE
 WITH REPORT, SIGNATURES, CERTIFICATION ETC.
 ONLY SOME BILLING SHEET AND REQUEST FOR CERTIFICATION
 WAS SUBMITTED.
  
 UNIT AND ALL EQUIPMENT SHALL BE IN FULL COMPLIANCE AS
 MODIFIED.
 110.3, 90.7.
 PLEASE ALSO SEE NOTES FROM PLUMBING REVIEWER WHICH ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NOTES FROM THIS
 REVIEW OF THESE DOCUMENTS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2007-10-31 Time 08:59 Sent To  
Notes
2007-10-31 10:23:25** PROVISO**
  
 1) NOTE: MAIN SWITCHGEAR EQUIPMENT SHALL BE VIF BY
 INSPECTOR FOR 230.76 AND 230.79. ENGINEER STATES MAIN
 CAN BE TURNED OFF BY PUSHBUTTON WITHOUT POWER.
  
 2) NOTE: GENERATOR IS TO BE RE-LISTED FROM A NATIONAL
 RECOGNIZED TESTING LABORATORY (NRTL) AS THE AFTER
 MARKET NATURAL GAS UNIT IS NOT PART OF THE LISTED
 GENERATOR FROM MANUFACTURE. THE ENGINEER'S RESPONSE IS
 THAT CSA WILL RE-LIST THE GENERATOR. THIS DOCUMENTATION
 IS TO BE SUBMITTED TO THE CITY FOR REVIEW.
 110.3, 90.7
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-06 Cont ID  
Sent By dpalmer Date 2007-10-06 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2007-10-06 Time 14:02 Sent To  
Notes
2007-10-06 14:43:41 
 *** DENIED2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
 ** PLEASE SEE COMMENTS FROM ORIGINAL PERMIT *PROVISO*
 ARE STILL PART OF THESE NOTES.
 ** PLEASE SEE COMMENT WITH RESPECT TO THE GENERATOR NOW
 BEING BI-FUEL WHICH WAS NOT PART OF THE ORIGINAL
 GENERATOR PERMIT APPLICATION PACKAGE.
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. CODES
 HAVE NOT CHANGED ON PLANS FOR NEW CODES AS APPLIED. (
 THIS SHOULD NOT AFFECT INSTALLATION OF ELECTRICAL).
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW #4 AND ALSO THE
 ORIGINAL PERMIT NOTES AS PERMIT WAS ISSUED WITH A
 *PROVISO*. THIS CONDITION OF ISSUANCE OF PERMIT WAS AT
 CONTRACTORS OWN RISK AS THE INFORMATION SUBMITTED FOR
 EQUIPMENT DID MEET THE CODES ARE REFLECT ON REDLINED
 PLANS.
 PLEASE SEE THE INFORMATION STILL SUBMITTED FOR THIS
 PARALLEL SWITCHGEAR HAS NOT PROVED TO MEET 230.76 AND
 230.79.
 230.70, 230.71, 110.3, 90.7 ETC.
 IT IS CLEAR THIS IS *PARALLEL SWITCH GEAR* HOWEVER THE
 BREAKER(S) DOES NOT SHOW HOW IT MEETS THESE CODES WHEN
 THE BREAKERS DO NOT SHOW ANY MANUAL MEANS OF DISCONNECT
 REQUIRED FOR SERVICE MEANS OF DISCONNECT.
 THIS IS CLEARLY THE NEW SERVICE MAIN FOR BUILDING.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 ALSO AS THE
 ORIGINAL GENERATOR UNIT WAS DIESEL ONLY AND IS NOW A
 BI-FUEL UNIT.
 THE RESPONSE FROM THE ENGINEER MENTIONS TO SEE THE
 ATTACHED LISTING FOR THE GTI FUEL SYSTEM. THE PREVIOUS
 COMMENT WAS NOT FOR THE GTI FUEL SYSTEM.
 THE NOTE APPLIED TO HOW THE AFTERMARKET INSTALLATION OF
 THIS FUEL SYSTEM VOIDS THE EXISTING
 CERTIFICATION/LISTING FROM THE GENERATOR MANUFACTURE.
 THIS FUEL SYSTEM AND GAS CONNECTION WAS DONE WITHOUT
 ANY PERMIT FOR INSTALLATION OF ANY OF THE GAS SYSTEMS.
 PLEASE KNOW AS THE PERMIT WAS NEVER ISSUED FOR THE GAS
 INSTALLATION AND THIS WORK WAS ALREADY DONE, A 4X
 PERMIT FEE MAY STILL BE APPLIED TO THEGAS PERMIT AS
 APPLIED FOR SUB-PERMIT.
 ONLY ONE SUCH UNIT THIS OFFICE IS AWARE OF HAS BEEN
 RE-LISTED BEFORE LEAVING THE FACTORY WITH THE FUEL
 SYSTEM INSTALLED AT THE FACTORY. ALL DOCUMENTS FOR
 RE-LISTING UNIT WOULD BE REQUIRED FOR ANY SUCH
 PROCESS.
 ANY AFTERMARKET PRODUCTS INSTALLED ON ANY LISTING
 EQUIPMENT WILL REQUIRE THESE TO BE RE-LISTED/TESTED,
 FIELD EVALUATED ETC.110.3, 90.7 ETC. (THIS WOULD ALSO
 INCLUDE LISTING FOR POSSIBLE MECH/PLUMBING ETC). PLEASE
 PROVIDE DOCUMENTATION FOR LISTING OF THIS LISTED
 ASSEMBLY AS INSTALLED.
 PLEASE HAVE THE LISTING AGENCY CONTACT THIS OFFICE IF
 THERE ARE ANY QUESTIONS.
 ALL WORK MUST BE DONE BY A NRTL.
  
 47) NOTE:*** PLEASE KNOW THE VALUE FOR THE COMPLETE
 SCOPE OF WORK WILL BE REQUIRED TO BE ADJUSTED AS THE
 SCOPE OF WORK FROM ORIGINAL APPLICATION HAS GREATLY
 INCREASED AND THE VALUE FOR ALL WORK AS SHOWN IS LOW.
 PLEASE SEE FBC 108.3.
 ALL LABOR, ALL MATERIALS, ALL EQUIPMENT, INSTALLAITON,
 DESIGN COST ETC SHALL BE INCLUDED WHETHER OR NOT ANY OF
 THESE ITEMS ARE OWNER SUPPLIED. THIS INCLUDE EQUIPMENT,
 GENERATOR ETC.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By dpalmer Date 2007-07-02 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2007-07-02 Time 10:20 Sent To I
Notes
2007-07-02 10:21:22 
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE KNOW THIS PERMIT IS FOR COMPLETE ION OF
 WORK STARTED UNDER PERVIOUS PERMIT THEREFORE THE NEW
 ADOPTED CODES AS OF DECEMBER 8TH, 2006 DO NOT APPLY AT
 THIS TIME.
 PLEASE SEE PLANS NEED TO CONTAIN NOTES ACCORDINGLY.
 PLEASE SUBMIT TWO COMPLETE PACKAGES OF PLANS AND SPECS.
 PLEASE SEE NO SITE PLANS/SURVEYS SHOWING ALL EQUIPMENT
 SET-BACKS ETC WERE SUBMITTED.
 FBC 106.1
  
 2) NOTE: PLEASE BE SURE ALL PLANS AND SHEETS SIGNED,
 DATED AND SEALED BY THE ENGINEER CONTAINS TITLE BLOCKS
 AS REQUIRED PER FAC 61G15-23.002.
  
 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE SPECIFIC TO
 INSTALL OF ELECTRICAL. PLANS INDICATE *AS-BUILT*
 HOWEVER STILL INDICATE EITHER/OR FOR CONDUCTORS ETC.
 PLEASE ADJUST PLANS FOR WHAT WAS INSTALLED. 310.16,
 215.5, 240.4 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE KNOW THE ORIGINAL PERMIT WAS ISSUED
 WITH CONDITIONS THAT THE EQUIPMENT INSTALLED MEETS THE
 NEC FOR SEVERAL SECTIONS. 230.70, 230.71, 230.76,
 230.79 ETC.
 THIS WAS GIVEN AS NOTES AND REDLINED ON PLANS FOR
 INSPECTOR HOWEVER THIS HAS NOT YET BEEN VERIFIED TO
 THIS DATE.
 PLEASE SEE THIS EQUIPMENT IS THE FIRST MEANS OF
 DISCONNECT AS WELL AS THE SERVICE MEANS OF DISCONNECT.
 PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT SHEETS
 FOR ALL EQUIPMENT, GENERATOR, SUB BASE FUEL TANK ETC.
 PLEASE KNOW THIS PERMIT RECORD SET OF PLANS WILL NEED
 TO BE COMPLETE WITH ALL NEW INFORMATION.
 PLEASE SUBMIT INFORMATION AS THE GENERATOR IS NOW A
 BI-FUELED UNITS. PLEASE KNOW ANY LISTINGS FOR EQUIPMENT
 WILL STILL NEED TO BE MAINTAINED FOR MANUFACTURING
 STANDARDS. ANY MODIFICATION WHICH CHANGES THE LISTING
 FOR THE MANUFACTURING OF THE GENERATOR MAY REQUIRE A
 NEW ON-SITE LISTING FORM UL OR NRTL AS RECORD. PLEASE
 KNOW AS THE EQUIPMENT FOR THE SERVICE HAS NOT BEEN
 VERIFIED WITH THIS OFFICE NO COMMENTS CAN BE MADE AT
 THIS TIME.
 90.7, 110.3
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE NOTES AT THE EXISTING MDP1 AND
 MDP2 STATE THAT SIGNAGE WILL READ * OPTIONAL STAND-BY
 SYSTEM MAY BE PRESENT* OR WORDS TO THAT AFFECT. THIS
 WORDING WILL BE REQUIRED TO CHANGE AS THERE ARE MORE
 THAN ONE STAND-BY SYSTEMS AND SIGNS AND MAPPING OF
 THESE OTHER SYSTEMS MUST BE DETAILED AND NOTED AS BEING
 PRESENT, NOT *MAY*.
 230.2, 702.8 700.8, 701.8 ETC.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2007-07-02 10:21:15 
 PLANS REMOVED FROM INCOMING, PLANS RETURNED TO INCOMING
 WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 10:46 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-11 Cont ID  
Sent By mwennerg Date 2007-10-11 Time 14:55 Rev Time 0.00
Received By mwennerg Date 2007-10-11 Time 14:55 Sent To  
Notes
2007-10-11 15:06:10***DENIED***
  
 THE RESPONSE LETTER IS DATED TWO (2) DAYS BEFORE THE
 FIRST FIRE PLAN REVIEW WAS COMPLETED. IT DOES NOT
 APPEAR THAT THE FIRE COMMENTS WERE CONSIDERED FOR THIS
 SUBMITTAL. PLEASE SEE THE FOLLOWING COMMENTS TAKEN
 DIRECTLY FROM THE FIRST FIRE REVIEW:
  
 1) STATIONARY GENERATORS FOR EMERGENCY USE OR STAND BY
 POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA
 110.
  
 2) ABOVE GROUND FUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30. NFPA
 704 LABELS WILL BE REQUIRED.
  
 3) SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4) PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT
 LEAST 10' DISTANCE TO BUILDING OPENINGS.
  
 5) PROVIDE MANUFACTURE SPEC SHEETS FOR THE
 EQUIPMENT.-OK
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-25 Cont ID  
Sent By mawillia Date 2007-07-25 Time 16:09 Rev Time 0.00
Received By mawillia Date 2007-07-25 Time 15:13 Sent To  
Notes
2007-07-25 16:09:11*****DENIED*****
  
  
 1.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA
 110.
  
 2.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA
 704 LABELS WILL BE REQUIRED.
  
 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4.PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT
 LEAST 10' DISTANCE TO BUILDING OPENINGS.
  
 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE EQUIPMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 4 Status P Date 2007-12-13 Cont ID  
Sent By rregueir Date 2007-12-13 Time 18:04 Rev Time 0.00
Received By rregueir Date 2007-12-13 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status F Date 2007-11-03 Cont ID  
Sent By rregueir Date 2007-11-03 Time 15:29 Rev Time 0.00
Received By rregueir Date 2007-11-03 Time 15:21 Sent To  
Notes
2007-11-03 15:29:22REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THERE IS NO PLAN WITHIN THIS SUBMITTAL WHICH SHOWS
 APPROVAL BY PALM BEACH COUNTY DERM. THIS IS THE 3RD
 TIME THIS HAS BEEN REQUESTED. PBC DERM MAY BE CONTACTED
 AT 561-233-2400 OR
 HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP
  
 2. OK
  
 3. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By rregueir Date 2007-10-16 Time 15:05 Rev Time 0.00
Received By rregueir Date 2007-10-16 Time 11:31 Sent To  
Notes
2007-10-16 15:06:25REVIEW #: 2
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NO PBC DERM APPROVAL COULD BE FOUND IN SUBMITTED
 PAPERWORK. PLEASE PROVIDE 2 COPIES OF PLANS WITTH PBC
 DERM APPROVAL AFFIXED TO EACH.
  
 2. SITE PLAN DOES NOT PROVIDE DISTANCE TO ADJACENT
 BUILDINGS. SHOW COMPLIANCE WITH NFPA 30 SEC 2.3.2.1.
  
 3. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By rregueir Date 2007-07-18 Time 16:11 Rev Time 0.00
Received By rregueir Date 2007-07-18 Time 16:02 Sent To  
Notes
2007-07-18 16:09:01-------------DENIED---------------
  
 1. ABOVE GROUND FUEL STORAGE TANKS IN EXCESS OF 550
 GALLONS REQUIRE APPROVAL OF THE PALM BEACH COUNTY
 DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT. PLEASE
 SUBMIT 2 COPIES OF PLANS APPROVED BY PBC DERM PRIOR TO
 PERMIT ISSUANCE. FOR ADDITIONAL INFORMATION PLEASE CALL
 561-233-2400 OR VISIT WWW.PBCGOV.COM/ERM
  
 2. PLEASE PROVIDE SITE PLANS SHOWING THE LOCATION AND
 DISTANCE OF THE FUEL STORAGE TANK FROM PROPERTY LINES
 AND ADJACENT BUILDINGS.
  
 3. PLAN SHOWS A DETAIL FOR INSTALLATION OF BOLLARDS,
 BUT THE PLAN DOES NOT INDICATE THE LOCATION OF THE
 BOLLARDS. PLEASE SHOW PROTECTION FROM VEHICLE DAMAGE
 PER FBC,M 303.4
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 7 Status F Date 2008-05-02 Cont ID  
Sent By mperson Date 2008-05-02 Time 16:02 Rev Time 0.00
Received By mperson Date 2008-05-02 Time 16:02 Sent To PC
Notes
2008-05-02 16:18:34**SUBMITTAL DENIED**
  
 1. THE CSA EVALUATION WAS FOR THE GAS TRAIN ONLY NOT
 THE ENTIRE GENERATOR. THE CATERPILLAR GENERATOR HAS
 BEEN MODIFIED FROM THE ORIGINAL UL LISTING.
 NOTE: THE ENTIRE GENERATOR NEEDS RECERTIFICATION DUE
 TO THE FACT THE ADDED BI-FUEL SYSTEM WAS RETROFITTED.
 PLEASE PROVIDE THIS REQUIRED CERTIFICATION OF THE
 ENTIRE GENERATOR SYSTEM WITH THE ADDED RETROFITTED
 BI-FUEL SYSTEM.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 16:04 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 16:04 Sent To  
Notes
2008-02-23 16:06:48SUBMITTAL DENIED
  
 1. SEE COMMENTS FROM ELECTRICAL REVIEW OF SUBMITTAL.
  
 2. FROM PREVIOUS GAS REVIEW:
 THE LETTER CONCERNING THE CSA LISTING WILL BE RETURNED
 AT THIS TIME. PLEASE RESUBMIT WITH THE FIELD EVALUATION
 REPORT FOR THE AFTER MARKET ADAPTION LISTING FOR THE
 BI-FUEL FROM CSA.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2008-02-06 Cont ID  
Sent By kstevens Date 2008-02-06 Time 11:41 Rev Time 0.00
Received By kstevens Date 2008-02-06 Time 11:41 Sent To  
Notes
2008-02-06 11:56:10REVISION DENIED
 REFERENCE: FBC-2004 BUILDING
 NFPA-110
  
 1. LETTER DATED JANUARY 18, 2008 INDICATING THAT A
 VIBRATION HOSE CONNECTION IS NOT REQUIRED IS NOT
 APPROVED. PER NFPA 110 SECTION 7.9.3.2 APPROVED
 FLEXIBLE FUEL LINES SHALL BE USED BETWEEN THE PRIME
 MOVER AND THE FUEL PIPING. (ALSO SEE FBC-2004 SECTION
 2702.1 REQUIREMENTS FOR EMERGENCY AND STANDBY
 GERERATORS).
  
 2. THE LETTER CONCERNING THE CSA LISTING WILL BE
 RETURNED AT THIS TIME. PLEASE RESUBMIT WITH THE FIELD
 EVALUATION REPORT FOR THE AFTER MARKET ADAPTION LISTING
 FOR THE BI-FUEL FROM CSA.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-12-19 Cont ID  
Sent By kstevens Date 2007-12-19 Time 12:31 Rev Time 0.00
Received By kstevens Date 2007-12-19 Time 12:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-11-01 Cont ID  
Sent By kstevens Date 2007-11-01 Time 17:08 Rev Time 0.00
Received By kstevens Date 2007-11-01 Time 17:08 Sent To  
Notes
2007-11-01 17:18:34DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
 ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS ARE
 NOT INDICATED ON THE ISOMETRIC FOR ALL CUT SECTIONS AS
 REQUESTED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE
 PLAN REVIEW.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING
 EXISTING.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
 ******RESPONSE NOTED, BUT THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD OF THE SYSTEM HAVE NOT
 BEEN INDICATED AS REQUESTED. ALL INFORMATION IS
 REQUIRED TO DO A COMPLETE PLAN REVIEW.
  
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
 ******RESPONSE NOTED, BUT THE DISTANCE FROM THE METER
 TO THE MOST REMOTE OUTLET AS REQUESTED HAS NOT BEEN
 INDICATED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE
 PLAN REVIEW.
  
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL
 INDICATE MAXIMUM BTU LOAD AT 100%.
 ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE
 COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE
 ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE
 GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR
 RELISTING THE GENERATOR AS WELL AS THE MANUF.
 INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES.
 ******RESPONSE NOTED AND THIS CAN BE A PROVISO AS
 INDICATED IN THE ELECTRICAL PLAN REVIEW, BUT SINCE THE
 GENERATOR HAS BEEN INSTALLED ALREADY, THIS SHALL BE
 DONE AS SOON AS POSSIBLE AS TO NOT DELAY ANY
 INSPECTIONS.
  
 B. OK
  
 C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE
 REGULATORS WERE NOT SUBMITTED.
 ******NO RESPONSE, NOT ADDRESSED. WHEN SUBMITTING THE
 REGULATOR INFORMATION, INDICATE THE MODEL NUMBER AND
 THE TOTAL BTU LOAD ON EACH LOW PRESSURE SYSTEM
 DOWNSTREAM OF THE REGULATOR.
  
 D. OK
 E. OK
  
 ********NEW COMMENT********
  
 1B. OK
 2B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-10-18 Cont ID  
Sent By kstevens Date 2007-10-18 Time 14:31 Rev Time 0.00
Received By kstevens Date 2007-10-18 Time 14:31 Sent To  
Notes
2007-10-18 14:55:53DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW::
  
 A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING
 EXISTING.
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN
 SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL
 INDICATE MAXIMUM BTU LOAD AT 100%.
 ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE
 COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE
 ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE
 GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR
 RELISTING THE GENERATOR AS WELL AS THE MANUF.
 INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES.
  
 B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS
 NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHT P2 WAS NOT SUBMITTED.
  
 C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE
 REGULATORS WERE NOT SUBMITTED.
  
 D. OK
  
 E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025 ****RESPONSE
 NOTED, BUT SHTS P1, P2 & P3 HAVE NOT BEEN SUBMITTED.
  
 ********NEW COMMENT********
  
 1B. SHT SD1 IS NOT SHOWN IN THE ELECTRICAL SHEET INDEX,
 BUT SUBMITTED WITH THE ELECTRICAL SHEETS. PLEASE
 CLARIFY.
  
 2B.SHTS P1, P2 & P3 ARE INDICATED ON THE ELECTRICAL
 SHEET INDEX, BUT NOT SUBMITTED. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By kstevens Date 2007-07-16 Time 18:26 Rev Time 0.00
Received By kstevens Date 2007-07-16 Time 18:25 Sent To  
Notes
2007-07-16 18:51:52DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING
 EXISTING.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL
 INDICATE MAXIMUM BTU LOAD AT 100%.
  
 B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS
 NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1.
  
 C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. SECTION 106.1.2.
  
 D. NO SITE PLANSOR SURVEYSHAS BEEN SUBMITTED
 SHOWING SET BACKS.
  
 E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 08:31 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 08:31 Sent To E
Notes
2008-05-16 08:31:38TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 14:33 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 14:33 Sent To E
Notes
2008-04-22 14:34:02TO "DPALMER"DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 14:59 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 14:59 Sent To E
Notes
2008-02-14 14:59:44TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 11:57 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 11:57 Sent To P
Notes
2008-01-18 11:57:27TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 14:47 Sent To  
Notes
2007-12-12 14:52:59TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-29 Cont ID  
Sent By adarroug Date 2007-10-29 Time 16:32 Rev Time 0.00
Received By adarroug Date 2007-10-29 Time 16:32 Sent To  
Notes
2007-10-29 16:38:59TO "COMM" BD#9--EXPEDITED-- NEW SHEETS FOR "MECH"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 15:45 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 15:45 Sent To  
Notes
2007-09-28 15:53:24TO "COMM" BD#25
2007-09-06 15:45:39WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-25 Cont ID  
Sent By mawillia Date 2007-07-25 Time 15:13 Rev Time 0.00
Received By mawillia Date 2007-06-19 Time 16:52 Sent To  
Notes
2007-07-03 10:56:15TO "COMM" BD#6
2007-06-19 16:53:06WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-16 Cont ID  
Sent By rregueir Date 2007-10-16 Time 15:24 Rev Time 0.00
Received By rregueir Date 2007-10-16 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By rregueir Date 2007-07-18 Time 16:17 Rev Time 0.00
Received By rregueir Date 2007-07-18 Time 16:11 Sent To  
Notes
2007-07-18 16:17:22--------------DENIED----------------
  
 1. PLEASE SEE FUEL REVIEW FOR ADDITIONAL COMMENTS.
  
 2. PLEASE SHOW GENERATOR EXHAUST TERMINATION LOCATION
 TO BE MINIMUM 10' FROM ANY OPENINGS INTO ADJACENT
 BUILDINGS SUCH AS DOORS, WINDOWS, SOFFIT VENTS OR AIR
 INAKES PER FBC,M 401.5.1.
  
 3. PLEASE SUBMIT FULL DOCUMENTATION FOR THIS PERMIT
 APPLICATION PER FBC 106.1 INCLUDING GENERATOR SUBMITTAL
 DATA.
  
 4. PERMIT APPLICATION STATES A DIESEL GENERATOR IS
 BEING INSTALLED, HOWEVER THE PLANS SHOW NATURAL GAS. IS
 THIS GENERATOR BEING MODIFIED?
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By kdfreema Date 2007-10-30 Time 09:21 Rev Time 0.00
Received By kdfreema Date 2007-10-30 Time 09:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-12 Cont ID  
Sent By kdfreema Date 2007-09-12 Time 15:38 Rev Time 0.00
Received By kdfreema Date 2007-09-12 Time 15:38 Sent To  
Notes
2007-09-12 15:40:50***FAILED***
  
 *REPEAT COMMENT*
  
 THE UNIT IS REQUIRED TO BE SCREENED BY MEANS OF A WALL
 AND LANDSCAPING INDEPENDENT OF THE SOUND/WEATHER
 PROOFING ENCLOSURE. PLEASE REFER TO SEC. 94-444(B) FOR
 THE REQUIREMENTS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-06 Cont ID  
Sent By kdfreema Date 2007-07-06 Time 16:37 Rev Time 0.00
Received By kdfreema Date 2007-07-06 Time 16:37 Sent To  
Notes
2007-07-06 16:40:44** FAILED**
  
 RESPONSE NOTED, HOWEVER THE UNIT IS REQUIRED TO BE
 SCREENED BY MEANS OF A WALL AND LANDSCAPING INDEPENDENT
 OF THE SOUND/WEATHER PROOFING ENCLOSURE. PLEASE REFER
 TO SEC. 94-444(B) FOR THE REQUIREMENTS. AS PART OF YOUR
 RESUBMITTAL, PLEASE INCLUDE LANDSCAPE PLANS AND
 ELEVATIONS FOR THE ENCLOSURE.
  
 REGARDING THE SURVEY YOUR RESPONSE IS NOTED, HOWEVER,
 WHAT WAS INCLUDED IS NOT A SURVEY. PLEASE INCLUDE A
 SURVEY SHOWING THE LOCATION OF THE GENERATOR AND ALL
 EASEMENTS ON THE PROPERTY.
  
 ADDITIONALLY, THE ADDITION OF THE GENERATOR WILL
 REQUIRE A MINOR PLANNED DEVELOPMENT AMENDMENT. PLEASE
 VISIT WWW.WPB.ORG/PLAN AND DOWNLOAD THE 2006-2007
 DEVELOPMENT APPLICATION. THE REQUIREMENTS FOR THE
 AMENDMENT ARE CONTAINED WITHIN THE APPLICATION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH ANY QUESTIONS YOU
 MAY HAVE.