| Plan Review Stops For Permit 07060548 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-17 |
Time |
07:44 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2007-10-17 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-20 |
Time |
11:18 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-07-20 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2007-07-20 11:21:03 | BUILDING PLAN REVIEW | | | PERMIT: 07060548 | | | ADD: 828 SOUTHERN BLVD | | | CONT: POWER SECURE INC | | | TEL: (919)818-8700 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.) | | | GENERATOR SLAB & ANCHOR REQUIREMENT | | | | | | 3) PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | | PLUS PROVIDE PLANS WITH THE INFORMATION | | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | SECOND, PROVIDE INFORMATION ON THE | | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | | WILL BEUSED. | | | THE NEW SLAB AND HOLD DOWN DETAILS: | | | 104.2.1* ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 4)2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-29 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-29 |
Time |
17:05 |
Sent To |
P |
|
| Notes |
| 2008-04-29 17:05:56 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE KNOW THE EVALUATION REPORT SUBMITTED BY | | | POWER SECURE BY CSA INTERNATIONAL IS NOT ACCEPTABLE. | | | AS STATED ON PREVIOUS REVIEW THE ENTIRE | | | GENERATOR/SYSTEM NEEDS TO BE RE-LISTED. THE REPORT | | | SUBMITTED SPECIFICALLY STATES THE GAS TRAIN UNIT IS THE | | | ONLY ITEM WHICH WAS EVALUATED. THE REPORTS STATES THE | | | GENERATOR IS UL LISTED AND HAS BEEN MODIFIED FROM THE | | | ORIGINAL LISTING FROM CATERPILLAR AND NEEDS TO BE | | | LISTED. THIS REVIEWER HAS CONTACTED CSA INTERNATIONAL. | | | CONTACT WILL ALSO BE MADE TO PUBLIX DIRECTLY TO EXPRESS | | | CONCERNS OVER LISTING. | | | THE REPORT WILL BE RETAINED BY THIS OFFICE WAS REVIEWED | | | BY ALL RELEVANT TRADES. | | | 110.3, 90.7 | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-16 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-16 |
Time |
18:51 |
Sent To |
P |
|
| Notes |
| 2008-02-16 18:52:07 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE SUBMIT THE COMPLETE CSA REPORT AND | | | CERTIFICATION. THE DOCUMENTS SUBMITTED ARE NOT COMPLETE | | | WITH REPORT, SIGNATURES, CERTIFICATION ETC. | | | ONLY SOME BILLING SHEET AND REQUEST FOR CERTIFICATION | | | WAS SUBMITTED. | | | | | | UNIT AND ALL EQUIPMENT SHALL BE IN FULL COMPLIANCE AS | | | MODIFIED. | | | 110.3, 90.7. | | | PLEASE ALSO SEE NOTES FROM PLUMBING REVIEWER WHICH ARE | | | STILL IN NEED OF ADDRESSING ALONG WITH NOTES FROM THIS | | | REVIEW OF THESE DOCUMENTS. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-31 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-31 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2007-10-31 10:23:25 | ** PROVISO** | | | | | | 1) NOTE: MAIN SWITCHGEAR EQUIPMENT SHALL BE VIF BY | | | INSPECTOR FOR 230.76 AND 230.79. ENGINEER STATES MAIN | | | CAN BE TURNED OFF BY PUSHBUTTON WITHOUT POWER. | | | | | | 2) NOTE: GENERATOR IS TO BE RE-LISTED FROM A NATIONAL | | | RECOGNIZED TESTING LABORATORY (NRTL) AS THE AFTER | | | MARKET NATURAL GAS UNIT IS NOT PART OF THE LISTED | | | GENERATOR FROM MANUFACTURE. THE ENGINEER'S RESPONSE IS | | | THAT CSA WILL RE-LIST THE GENERATOR. THIS DOCUMENTATION | | | IS TO BE SUBMITTED TO THE CITY FOR REVIEW. | | | 110.3, 90.7 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-06 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-06 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2007-10-06 14:43:41 | | | | *** DENIED2ND REVIEW *** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED. | | | ** PLEASE SEE COMMENTS FROM ORIGINAL PERMIT *PROVISO* | | | ARE STILL PART OF THESE NOTES. | | | ** PLEASE SEE COMMENT WITH RESPECT TO THE GENERATOR NOW | | | BEING BI-FUEL WHICH WAS NOT PART OF THE ORIGINAL | | | GENERATOR PERMIT APPLICATION PACKAGE. | | | | | | 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. CODES | | | HAVE NOT CHANGED ON PLANS FOR NEW CODES AS APPLIED. ( | | | THIS SHOULD NOT AFFECT INSTALLATION OF ELECTRICAL). | | | 2005 NFPA-70 | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW #4 AND ALSO THE | | | ORIGINAL PERMIT NOTES AS PERMIT WAS ISSUED WITH A | | | *PROVISO*. THIS CONDITION OF ISSUANCE OF PERMIT WAS AT | | | CONTRACTORS OWN RISK AS THE INFORMATION SUBMITTED FOR | | | EQUIPMENT DID MEET THE CODES ARE REFLECT ON REDLINED | | | PLANS. | | | PLEASE SEE THE INFORMATION STILL SUBMITTED FOR THIS | | | PARALLEL SWITCHGEAR HAS NOT PROVED TO MEET 230.76 AND | | | 230.79. | | | 230.70, 230.71, 110.3, 90.7 ETC. | | | IT IS CLEAR THIS IS *PARALLEL SWITCH GEAR* HOWEVER THE | | | BREAKER(S) DOES NOT SHOW HOW IT MEETS THESE CODES WHEN | | | THE BREAKERS DO NOT SHOW ANY MANUAL MEANS OF DISCONNECT | | | REQUIRED FOR SERVICE MEANS OF DISCONNECT. | | | THIS IS CLEARLY THE NEW SERVICE MAIN FOR BUILDING. | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4 ALSO AS THE | | | ORIGINAL GENERATOR UNIT WAS DIESEL ONLY AND IS NOW A | | | BI-FUEL UNIT. | | | THE RESPONSE FROM THE ENGINEER MENTIONS TO SEE THE | | | ATTACHED LISTING FOR THE GTI FUEL SYSTEM. THE PREVIOUS | | | COMMENT WAS NOT FOR THE GTI FUEL SYSTEM. | | | THE NOTE APPLIED TO HOW THE AFTERMARKET INSTALLATION OF | | | THIS FUEL SYSTEM VOIDS THE EXISTING | | | CERTIFICATION/LISTING FROM THE GENERATOR MANUFACTURE. | | | THIS FUEL SYSTEM AND GAS CONNECTION WAS DONE WITHOUT | | | ANY PERMIT FOR INSTALLATION OF ANY OF THE GAS SYSTEMS. | | | PLEASE KNOW AS THE PERMIT WAS NEVER ISSUED FOR THE GAS | | | INSTALLATION AND THIS WORK WAS ALREADY DONE, A 4X | | | PERMIT FEE MAY STILL BE APPLIED TO THEGAS PERMIT AS | | | APPLIED FOR SUB-PERMIT. | | | ONLY ONE SUCH UNIT THIS OFFICE IS AWARE OF HAS BEEN | | | RE-LISTED BEFORE LEAVING THE FACTORY WITH THE FUEL | | | SYSTEM INSTALLED AT THE FACTORY. ALL DOCUMENTS FOR | | | RE-LISTING UNIT WOULD BE REQUIRED FOR ANY SUCH | | | PROCESS. | | | ANY AFTERMARKET PRODUCTS INSTALLED ON ANY LISTING | | | EQUIPMENT WILL REQUIRE THESE TO BE RE-LISTED/TESTED, | | | FIELD EVALUATED ETC.110.3, 90.7 ETC. (THIS WOULD ALSO | | | INCLUDE LISTING FOR POSSIBLE MECH/PLUMBING ETC). PLEASE | | | PROVIDE DOCUMENTATION FOR LISTING OF THIS LISTED | | | ASSEMBLY AS INSTALLED. | | | PLEASE HAVE THE LISTING AGENCY CONTACT THIS OFFICE IF | | | THERE ARE ANY QUESTIONS. | | | ALL WORK MUST BE DONE BY A NRTL. | | | | | | 47) NOTE:*** PLEASE KNOW THE VALUE FOR THE COMPLETE | | | SCOPE OF WORK WILL BE REQUIRED TO BE ADJUSTED AS THE | | | SCOPE OF WORK FROM ORIGINAL APPLICATION HAS GREATLY | | | INCREASED AND THE VALUE FOR ALL WORK AS SHOWN IS LOW. | | | PLEASE SEE FBC 108.3. | | | ALL LABOR, ALL MATERIALS, ALL EQUIPMENT, INSTALLAITON, | | | DESIGN COST ETC SHALL BE INCLUDED WHETHER OR NOT ANY OF | | | THESE ITEMS ARE OWNER SUPPLIED. THIS INCLUDE EQUIPMENT, | | | GENERATOR ETC. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-02 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-02 |
Time |
10:20 |
Sent To |
I |
|
| Notes |
| 2007-07-02 10:21:22 | | | | *** UNSAT *** | | | | | | | | | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET | | | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW | | | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE | | | REVIEWED AT THIS TIME. | | | | | | | | | 1) NOTE: PLEASE KNOW THIS PERMIT IS FOR COMPLETE ION OF | | | WORK STARTED UNDER PERVIOUS PERMIT THEREFORE THE NEW | | | ADOPTED CODES AS OF DECEMBER 8TH, 2006 DO NOT APPLY AT | | | THIS TIME. | | | PLEASE SEE PLANS NEED TO CONTAIN NOTES ACCORDINGLY. | | | PLEASE SUBMIT TWO COMPLETE PACKAGES OF PLANS AND SPECS. | | | PLEASE SEE NO SITE PLANS/SURVEYS SHOWING ALL EQUIPMENT | | | SET-BACKS ETC WERE SUBMITTED. | | | FBC 106.1 | | | | | | 2) NOTE: PLEASE BE SURE ALL PLANS AND SHEETS SIGNED, | | | DATED AND SEALED BY THE ENGINEER CONTAINS TITLE BLOCKS | | | AS REQUIRED PER FAC 61G15-23.002. | | | | | | 3) NOTE: PLEASE SUBMIT PLANS WHICH ARE SPECIFIC TO | | | INSTALL OF ELECTRICAL. PLANS INDICATE *AS-BUILT* | | | HOWEVER STILL INDICATE EITHER/OR FOR CONDUCTORS ETC. | | | PLEASE ADJUST PLANS FOR WHAT WAS INSTALLED. 310.16, | | | 215.5, 240.4 ETC. | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 4) NOTE: PLEASE KNOW THE ORIGINAL PERMIT WAS ISSUED | | | WITH CONDITIONS THAT THE EQUIPMENT INSTALLED MEETS THE | | | NEC FOR SEVERAL SECTIONS. 230.70, 230.71, 230.76, | | | 230.79 ETC. | | | THIS WAS GIVEN AS NOTES AND REDLINED ON PLANS FOR | | | INSPECTOR HOWEVER THIS HAS NOT YET BEEN VERIFIED TO | | | THIS DATE. | | | PLEASE SEE THIS EQUIPMENT IS THE FIRST MEANS OF | | | DISCONNECT AS WELL AS THE SERVICE MEANS OF DISCONNECT. | | | PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT SHEETS | | | FOR ALL EQUIPMENT, GENERATOR, SUB BASE FUEL TANK ETC. | | | PLEASE KNOW THIS PERMIT RECORD SET OF PLANS WILL NEED | | | TO BE COMPLETE WITH ALL NEW INFORMATION. | | | PLEASE SUBMIT INFORMATION AS THE GENERATOR IS NOW A | | | BI-FUELED UNITS. PLEASE KNOW ANY LISTINGS FOR EQUIPMENT | | | WILL STILL NEED TO BE MAINTAINED FOR MANUFACTURING | | | STANDARDS. ANY MODIFICATION WHICH CHANGES THE LISTING | | | FOR THE MANUFACTURING OF THE GENERATOR MAY REQUIRE A | | | NEW ON-SITE LISTING FORM UL OR NRTL AS RECORD. PLEASE | | | KNOW AS THE EQUIPMENT FOR THE SERVICE HAS NOT BEEN | | | VERIFIED WITH THIS OFFICE NO COMMENTS CAN BE MADE AT | | | THIS TIME. | | | 90.7, 110.3 | | | FBC 106.1.2 | | | | | | 5) NOTE: PLEASE SEE THE NOTES AT THE EXISTING MDP1 AND | | | MDP2 STATE THAT SIGNAGE WILL READ * OPTIONAL STAND-BY | | | SYSTEM MAY BE PRESENT* OR WORDS TO THAT AFFECT. THIS | | | WORDING WILL BE REQUIRED TO CHANGE AS THERE ARE MORE | | | THAN ONE STAND-BY SYSTEMS AND SIGNS AND MAPPING OF | | | THESE OTHER SYSTEMS MUST BE DETAILED AND NOTED AS BEING | | | PRESENT, NOT *MAY*. | | | 230.2, 702.8 700.8, 701.8 ETC. | | | | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | 2007-07-02 10:21:15 | | | | PLANS REMOVED FROM INCOMING, PLANS RETURNED TO INCOMING | | | WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS DONE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-02 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-02 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-10-11 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-10-11 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2007-10-11 15:06:10 | ***DENIED*** | | | | | | THE RESPONSE LETTER IS DATED TWO (2) DAYS BEFORE THE | | | FIRST FIRE PLAN REVIEW WAS COMPLETED. IT DOES NOT | | | APPEAR THAT THE FIRE COMMENTS WERE CONSIDERED FOR THIS | | | SUBMITTAL. PLEASE SEE THE FOLLOWING COMMENTS TAKEN | | | DIRECTLY FROM THE FIRST FIRE REVIEW: | | | | | | 1) STATIONARY GENERATORS FOR EMERGENCY USE OR STAND BY | | | POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA | | | 110. | | | | | | 2) ABOVE GROUND FUEL TANKS SHALL BE PERMITTED TO BE | | | INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30. NFPA | | | 704 LABELS WILL BE REQUIRED. | | | | | | 3) SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | | GENERATOR. | | | | | | 4) PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT | | | LEAST 10' DISTANCE TO BUILDING OPENINGS. | | | | | | 5) PROVIDE MANUFACTURE SPEC SHEETS FOR THE | | | EQUIPMENT.-OK | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-25 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-25 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2007-07-25 16:09:11 | *****DENIED***** | | | | | | | | | 1.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY | | | POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA | | | 110. | | | | | | 2.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE | | | INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA | | | 704 LABELS WILL BE REQUIRED. | | | | | | 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE | | | GENERATOR. | | | | | | 4.PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT | | | LEAST 10' DISTANCE TO BUILDING OPENINGS. | | | | | | 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE EQUIPMENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
4 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-12-13 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-12-13 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
3 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-03 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-03 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2007-11-03 15:29:22 | REVIEW #: 3RD | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. THERE IS NO PLAN WITHIN THIS SUBMITTAL WHICH SHOWS | | | APPROVAL BY PALM BEACH COUNTY DERM. THIS IS THE 3RD | | | TIME THIS HAS BEEN REQUESTED. PBC DERM MAY BE CONTACTED | | | AT 561-233-2400 OR | | | HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP | | | | | | 2. OK | | | | | | 3. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
2 |
Status |
F |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-16 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-16 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-10-16 15:06:25 | REVIEW #: 2 | | | ACTION: | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. NO PBC DERM APPROVAL COULD BE FOUND IN SUBMITTED | | | PAPERWORK. PLEASE PROVIDE 2 COPIES OF PLANS WITTH PBC | | | DERM APPROVAL AFFIXED TO EACH. | | | | | | 2. SITE PLAN DOES NOT PROVIDE DISTANCE TO ADJACENT | | | BUILDINGS. SHOW COMPLIANCE WITH NFPA 30 SEC 2.3.2.1. | | | | | | 3. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-18 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-18 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2007-07-18 16:09:01 | -------------DENIED--------------- | | | | | | 1. ABOVE GROUND FUEL STORAGE TANKS IN EXCESS OF 550 | | | GALLONS REQUIRE APPROVAL OF THE PALM BEACH COUNTY | | | DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT. PLEASE | | | SUBMIT 2 COPIES OF PLANS APPROVED BY PBC DERM PRIOR TO | | | PERMIT ISSUANCE. FOR ADDITIONAL INFORMATION PLEASE CALL | | | 561-233-2400 OR VISIT WWW.PBCGOV.COM/ERM | | | | | | 2. PLEASE PROVIDE SITE PLANS SHOWING THE LOCATION AND | | | DISTANCE OF THE FUEL STORAGE TANK FROM PROPERTY LINES | | | AND ADJACENT BUILDINGS. | | | | | | 3. PLAN SHOWS A DETAIL FOR INSTALLATION OF BOLLARDS, | | | BUT THE PLAN DOES NOT INDICATE THE LOCATION OF THE | | | BOLLARDS. PLEASE SHOW PROTECTION FROM VEHICLE DAMAGE | | | PER FBC,M 303.4 | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
7 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-05-02 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-05-02 |
Time |
16:02 |
Sent To |
PC |
|
| Notes |
| 2008-05-02 16:18:34 | **SUBMITTAL DENIED** | | | | | | 1. THE CSA EVALUATION WAS FOR THE GAS TRAIN ONLY NOT | | | THE ENTIRE GENERATOR. THE CATERPILLAR GENERATOR HAS | | | BEEN MODIFIED FROM THE ORIGINAL UL LISTING. | | | NOTE: THE ENTIRE GENERATOR NEEDS RECERTIFICATION DUE | | | TO THE FACT THE ADDED BI-FUEL SYSTEM WAS RETROFITTED. | | | PLEASE PROVIDE THIS REQUIRED CERTIFICATION OF THE | | | ENTIRE GENERATOR SYSTEM WITH THE ADDED RETROFITTED | | | BI-FUEL SYSTEM. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
F |
Date |
2008-02-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-23 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-23 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2008-02-23 16:06:48 | SUBMITTAL DENIED | | | | | | 1. SEE COMMENTS FROM ELECTRICAL REVIEW OF SUBMITTAL. | | | | | | 2. FROM PREVIOUS GAS REVIEW: | | | THE LETTER CONCERNING THE CSA LISTING WILL BE RETURNED | | | AT THIS TIME. PLEASE RESUBMIT WITH THE FIELD EVALUATION | | | REPORT FOR THE AFTER MARKET ADAPTION LISTING FOR THE | | | BI-FUEL FROM CSA. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-06 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-06 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2008-02-06 11:56:10 | REVISION DENIED | | | REFERENCE: FBC-2004 BUILDING | | | NFPA-110 | | | | | | 1. LETTER DATED JANUARY 18, 2008 INDICATING THAT A | | | VIBRATION HOSE CONNECTION IS NOT REQUIRED IS NOT | | | APPROVED. PER NFPA 110 SECTION 7.9.3.2 APPROVED | | | FLEXIBLE FUEL LINES SHALL BE USED BETWEEN THE PRIME | | | MOVER AND THE FUEL PIPING. (ALSO SEE FBC-2004 SECTION | | | 2702.1 REQUIREMENTS FOR EMERGENCY AND STANDBY | | | GERERATORS). | | | | | | 2. THE LETTER CONCERNING THE CSA LISTING WILL BE | | | RETURNED AT THIS TIME. PLEASE RESUBMIT WITH THE FIELD | | | EVALUATION REPORT FOR THE AFTER MARKET ADAPTION LISTING | | | FOR THE BI-FUEL FROM CSA. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-19 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-19 |
Time |
12:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-01 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-01 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2007-11-01 17:18:34 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN | | | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. | | | ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS ARE | | | NOT INDICATED ON THE ISOMETRIC FOR ALL CUT SECTIONS AS | | | REQUESTED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE | | | PLAN REVIEW. | | | | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING | | | EXISTING. | | | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN | | | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. | | | ******RESPONSE NOTED, BUT THE BTU LOAD OF EACH | | | APPLIANCE AND THE TOTAL BTU LOAD OF THE SYSTEM HAVE NOT | | | BEEN INDICATED AS REQUESTED. ALL INFORMATION IS | | | REQUIRED TO DO A COMPLETE PLAN REVIEW. | | | | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN | | | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. | | | ******RESPONSE NOTED, BUT THE DISTANCE FROM THE METER | | | TO THE MOST REMOTE OUTLET AS REQUESTED HAS NOT BEEN | | | INDICATED. ALL INFORMATION IS REQUIRED TO DO A COMPLETE | | | PLAN REVIEW. | | | | | | | | | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL | | | INDICATE MAXIMUM BTU LOAD AT 100%. | | | ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION | | | INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE | | | COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE | | | ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE | | | GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR | | | RELISTING THE GENERATOR AS WELL AS THE MANUF. | | | INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES. | | | ******RESPONSE NOTED AND THIS CAN BE A PROVISO AS | | | INDICATED IN THE ELECTRICAL PLAN REVIEW, BUT SINCE THE | | | GENERATOR HAS BEEN INSTALLED ALREADY, THIS SHALL BE | | | DONE AS SOON AS POSSIBLE AS TO NOT DELAY ANY | | | INSPECTIONS. | | | | | | B. OK | | | | | | C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS | | | REGULATORS. SECTION 106.1.2. | | | ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE | | | REGULATORS WERE NOT SUBMITTED. | | | ******NO RESPONSE, NOT ADDRESSED. WHEN SUBMITTING THE | | | REGULATOR INFORMATION, INDICATE THE MODEL NUMBER AND | | | THE TOTAL BTU LOAD ON EACH LOW PRESSURE SYSTEM | | | DOWNSTREAM OF THE REGULATOR. | | | | | | D. OK | | | E. OK | | | | | | ********NEW COMMENT******** | | | | | | 1B. OK | | | 2B. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-18 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-18 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2007-10-18 14:55:53 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW:: | | | | | | A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN | | | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. | | | | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING | | | EXISTING. | | | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN | | | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****RESPONSE NOTED, BUT SHTS P1, P2, & P3 HAVE NOT BEEN | | | SUBMITTED. ONLY THE PREVIOUS SHT P1 WAS RESUBMITTED. | | | | | | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL | | | INDICATE MAXIMUM BTU LOAD AT 100%. | | | ****RESPONSE NOTED, BUT THE LISTING AND INSTALLATION | | | INSTRUCTIONS FOR THE GENERATOR ARE NOT INDICATED. SEE | | | COMMENT #3 OF THE ELECTRICAL PLAN REVIEW CONCERNING THE | | | ORIGINAL LISTING AND THE REQUIREMENT OF RELISTING THE | | | GENERATOR. PLEASE SUBMIT THE CERTIFICATION PAPERS FOR | | | RELISTING THE GENERATOR AS WELL AS THE MANUF. | | | INSTALLATION INSTRUCTIONS SHOWING ALL CLEARANCES. | | | | | | B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS | | | NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT SHT P2 WAS NOT SUBMITTED. | | | | | | C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS | | | REGULATORS. SECTION 106.1.2. | | | ****RESPONSE NOTED, BUT THE MANUF. SPEC. SHEETS FOR THE | | | REGULATORS WERE NOT SUBMITTED. | | | | | | D. OK | | | | | | E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. FAC 61G15-23.002(2) & FS 471.025 ****RESPONSE | | | NOTED, BUT SHTS P1, P2 & P3 HAVE NOT BEEN SUBMITTED. | | | | | | ********NEW COMMENT******** | | | | | | 1B. SHT SD1 IS NOT SHOWN IN THE ELECTRICAL SHEET INDEX, | | | BUT SUBMITTED WITH THE ELECTRICAL SHEETS. PLEASE | | | CLARIFY. | | | | | | 2B.SHTS P1, P2 & P3 ARE INDICATED ON THE ELECTRICAL | | | SHEET INDEX, BUT NOT SUBMITTED. PLEASE CLARIFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-16 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-07-16 |
Time |
18:25 |
Sent To |
|
|
| Notes |
| 2007-07-16 18:51:52 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. GAS PERMIT INFORMATION REQUIRED AS FOLLOWS: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). - INDICATE TOTAL BTU LOAD INCLUDING | | | EXISTING. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. SHEETS SHALL | | | INDICATE MAXIMUM BTU LOAD AT 100%. | | | | | | B. SHT P1 NOTES (A) REFERENCES DRAWING P2, BUT P2 HAS | | | NOT BEEN SUBMITTED. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | C. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS | | | REGULATORS. SECTION 106.1.2. | | | | | | D. NO SITE PLANSOR SURVEYSHAS BEEN SUBMITTED | | | SHOWING SET BACKS. | | | | | | E. SHTS E3 (TWO) AND P1. ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. FAC 61G15-23.002(2) & FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-16 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-16 |
Time |
08:31 |
Sent To |
E |
|
| Notes |
| 2008-05-16 08:31:38 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-04-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-22 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-22 |
Time |
14:33 |
Sent To |
E |
|
| Notes |
| 2008-04-22 14:34:02 | TO "DPALMER"DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-14 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-14 |
Time |
14:59 |
Sent To |
E |
|
| Notes |
| 2008-02-14 14:59:44 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-18 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-18 |
Time |
11:57 |
Sent To |
P |
|
| Notes |
| 2008-01-18 11:57:27 | TO "G" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-12 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-12 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2007-12-12 14:52:59 | TO "COMM" BD#19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-29 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-29 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2007-10-29 16:38:59 | TO "COMM" BD#9--EXPEDITED-- NEW SHEETS FOR "MECH" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-06 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-06 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2007-09-28 15:53:24 | TO "COMM" BD#25 | | 2007-09-06 15:45:39 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-25 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-19 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2007-07-03 10:56:15 | TO "COMM" BD#6 | | 2007-06-19 16:53:06 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-16 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-16 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-18 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-18 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2007-07-18 16:17:22 | --------------DENIED---------------- | | | | | | 1. PLEASE SEE FUEL REVIEW FOR ADDITIONAL COMMENTS. | | | | | | 2. PLEASE SHOW GENERATOR EXHAUST TERMINATION LOCATION | | | TO BE MINIMUM 10' FROM ANY OPENINGS INTO ADJACENT | | | BUILDINGS SUCH AS DOORS, WINDOWS, SOFFIT VENTS OR AIR | | | INAKES PER FBC,M 401.5.1. | | | | | | 3. PLEASE SUBMIT FULL DOCUMENTATION FOR THIS PERMIT | | | APPLICATION PER FBC 106.1 INCLUDING GENERATOR SUBMITTAL | | | DATA. | | | | | | 4. PERMIT APPLICATION STATES A DIESEL GENERATOR IS | | | BEING INSTALLED, HOWEVER THE PLANS SHOW NATURAL GAS. IS | | | THIS GENERATOR BEING MODIFIED? | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-10-30 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-10-30 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-09-12 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-09-12 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-09-12 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2007-09-12 15:40:50 | ***FAILED*** | | | | | | *REPEAT COMMENT* | | | | | | THE UNIT IS REQUIRED TO BE SCREENED BY MEANS OF A WALL | | | AND LANDSCAPING INDEPENDENT OF THE SOUND/WEATHER | | | PROOFING ENCLOSURE. PLEASE REFER TO SEC. 94-444(B) FOR | | | THE REQUIREMENTS. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | OR [email protected] WITH QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-07-06 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-07-06 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2007-07-06 16:40:44 | ** FAILED** | | | | | | RESPONSE NOTED, HOWEVER THE UNIT IS REQUIRED TO BE | | | SCREENED BY MEANS OF A WALL AND LANDSCAPING INDEPENDENT | | | OF THE SOUND/WEATHER PROOFING ENCLOSURE. PLEASE REFER | | | TO SEC. 94-444(B) FOR THE REQUIREMENTS. AS PART OF YOUR | | | RESUBMITTAL, PLEASE INCLUDE LANDSCAPE PLANS AND | | | ELEVATIONS FOR THE ENCLOSURE. | | | | | | REGARDING THE SURVEY YOUR RESPONSE IS NOTED, HOWEVER, | | | WHAT WAS INCLUDED IS NOT A SURVEY. PLEASE INCLUDE A | | | SURVEY SHOWING THE LOCATION OF THE GENERATOR AND ALL | | | EASEMENTS ON THE PROPERTY. | | | | | | ADDITIONALLY, THE ADDITION OF THE GENERATOR WILL | | | REQUIRE A MINOR PLANNED DEVELOPMENT AMENDMENT. PLEASE | | | VISIT WWW.WPB.ORG/PLAN AND DOWNLOAD THE 2006-2007 | | | DEVELOPMENT APPLICATION. THE REQUIREMENTS FOR THE | | | AMENDMENT ARE CONTAINED WITHIN THE APPLICATION. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561) | | | 822-1435 OR [email protected] WITH ANY QUESTIONS YOU | | | MAY HAVE. |
|
|