| 2007-07-01 10:27:36 | 2007-07-01 10:27:36 |
| | |
| | *** UNSAT *** |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004 |
| | FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE |
| | SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL |
| | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST |
| | ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER |
| | AND NO COST TO CONTRACTOR. |
| | PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY |
| | THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE. |
| | |
| | 3) NOTE: PLEASE SEE COMMENTS FROM BUILDING, FIRE |
| | MARSHAL AND OTHER TRADES WHICH WILL REQUIRE A SEPARATE |
| | PERMIT APPLICATION FOR EACH BUILDING. PLEASE ALSO SEE |
| | AN ADDRESSING STOP HAS BEEN ADDED AS EACH BUILDING WILL |
| | NOT CONTAIN THE SAME ADDRESS. |
| | PLEASE ADJUST TITLE BLOCKS FOR EACH BUILDING SET OF |
| | PLANS ONCE THE ADDRESS HAS BEEN CORRECTED. |
| | FAC 61G1-16.004,61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE TITLE BLOCKS FOR THE ENGINEER DOES |
| | NOT CORRELATE WITH THE ADDRESS AS LISTED ON THE STATE |
| | WEBSITE FOR THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION. |
| | PLEASE ADJUST. FAC 61G1-16.004. |
| | |
| | 5) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON |
| | THE TITLE BLOCKS FOR MEP SHEETS. PLEASE SEE MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR THE |
| | FIRM. PLEASE SEE FAC 61G15-23.002 AND FLORIDA STATUTES |
| | 471.023. |
| | ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 6) NOTE: PLEASE SEE FS 471.025. PLEASE SEE PLANS APPEAR |
| | TO BE SIGNED WITH *INITIALS*, IF THIS IS INDEED THE |
| | LEGAL SIGNATURE FOR EACH OF THE DESIGN PROFESSIONALS ON |
| | PLANS, PLEASE SUBMIT A LETTER FOR SIGNATURE |
| | VERIFICATION WHICH WILL BE REQUIRED TO BE SIGNED, |
| | DATED, SEALED AND NOTARIZED. |
| | THE LETTER MUST BE ORIGINAL AND CORRECTLY NOTARIZED AS |
| | REQUIRED UNDER FS 117.05. |
| | ** THESE LETTERS WILL GO INTO OUR SIGNATURE FILE FOR |
| | ANY FUTURE PROJECTS OR SIGNATURE VERIFICATION. |
| | |
| | 7) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH SUBMITTED PANEL SCHEDULES. PLEASE SEE |
| | THERE ARE TOO NUMEROUS LOCATION MISSING TO IDENTIFY |
| | EACH IN NOTES. |
| | PLEASE SEE 700.12F FOR CIRCUITING OF ALL EMERGENCY AND |
| | EXIT LIGHTS. |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE FBC 2004 W/2006 REVISION FOR |
| | COMPLIANCE WITH CHAPTER 13. PLEASE SEE |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING |
| | CONTROLS WHICH ARE MISSING FROM PLANS AT THIS TIME. NO |
| | REVIEW OF ANY OF THESE ITEMS CAN BE DONE AT THIS TIME. |
| | PLEASE SUBMIT ALL INFORMATION IF A SYSTEM IS |
| | INSTALLED. |
| | PLEASE SUBMIT ANY TIMED SCHEDULING. |
| | PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING. |
| | PLANS APPEAR TO SHOW SOME SORT OF LIGHTS HOWEVER NOT |
| | CLEAR THIS TIME. |
| | PLEASE SUBMIT TIME ON DEVICES AND/OR OVER RIDE DEVICES. |
| | PLEASE SEE THE SECTIONS GIVEN FOR THE MAXIMUM TIMES |
| | PERMITTED. |
| | PLEASE SUBMIT COMPLETED FIXTURE LEGENDS FOR ALL |
| | FIXTURES WHICH ARE TO CONTAIN ALL INFORMATION ON THESE |
| | FIXTURES AND WILL NEED TO CORRELATE WITH LIGHTING |
| | PERFORMANCE CALCULATIONS FOR COMMON AREAS. |
| | PLEASE SEE EGRESS PATHS AND CONTROLS PERMITTED IN THE |
| | FBC 1006.1.2, NFPA-101 7.8.1.2.2 |
| | AUTOMATIC, MOTION SENSOR?TYPE LIGHTING SWITCHES SHALL |
| | BE PERMITTED WITHIN THE MEANS OF EGRESS, PROVIDED THAT |
| | THE SWITCH CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE |
| | OPERATION, THE ILLUMINATION TIMERS ARE SET FOR MINIMUM |
| | 15-MINUTE DURATION, AND THE MOTION SENSOR IS ACTIVATED |
| | BY ANY OCCUPANT MOVEMENT IN THE AREA SERVED BY THE |
| | LIGHTING UNITS. |
| | |
| | PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS BASED ON NEW AREAS OF COMMON USE. THE |
| | SHEETS SUBMITTED APPEAR TO BE FOR UNITS ONLY. PLEASE |
| | KNOW WHEN THE ENERGY CALCULATIONS ARE CORRECTED AND |
| | SUBMITTED THE OWNER AGENT IS REQUIRED TO BE SIGNED ON |
| | EACH. 13-103.1.1.1 |
| | 13-415.1.AB.1.1, 13-415.1.C, 13-415.2. |
| | |
| | 9) NOTE: PLEASE SEE 620.22-620.24 AS THE DEDICATED |
| | CIRCUITS SHALL BE STATED ON PLANS AND COORDINATE WITH |
| | THE SUBMITTED PANEL SCHEDULE(S). PLEASE KNOW THESE |
| | REQUIRED DEDICATED CIRCUITS SHALL NOT FEED ANY OTHER |
| | AREAS AS THEY ARE SHOWN ON PLANS. |
| | |
| | 10) NOTE: PLEASE SEE 13-413.1.ABC.1 OF THE FBC CHAPTER |
| | 13. PLEASE SUBMIT WORST CASE SCENARIO FOR VOLTAGE DROP |
| | ON FEEDERS AND BRANCH CIRCUITS. |
| | |
| | 11) NOTE: PLEASE SEE ALL DISCONNECTING MEANS SHALL BE |
| | GROUPED IN WEST BUILDING AND EAST BUILDING FOR EACH |
| | SERVICE GRANTED AND MEETS 230.2. |
| | PLEASE SEE THE LOCATION OF MAINS AND THE AMOUNT OF |
| | SERVICES BEING REQUESTED AND SHOWN IN EAST BUILDING |
| | DOES NOT MEET CODE AND WILL NOT BE GRANTED. |
| | PLEASE ADJUST THE SIZE OF SERVICES AND PLEASE KNOW ALL |
| | MAINS SHALL BE GROUPED AS REQUIRED PER 225.34 AND |
| | 230.72. |
| | PLEASE SEE THE LOCATIONS OF SERVICE MAINS WILL ALSO BE |
| | REQUIRED IN A READILY ACCESSIBLE LOCATION FOR FIRE |
| | DEPARTMENT PERSONNEL. THIS HAS ALREADY BEEN CONFIRMED |
| | WITH THE FIRE MARSHAL?S OFFICE. |
| | PLEASE SEE THE LOCATION OF THE MAINS ON THE WEST |
| | BUILDING IS OK, HOWEVER PLEASE SEE THE NUMBER OF |
| | SERVICES IS NOT GRANTED. |
| | PLEASE SEE LOCATIONS OF DISCONNECTING MEANS, SERVICES |
| | AND MAIN LOCATIONS ON THE EAST BUILDING ARE NOT |
| | ACCEPTABLE TO THIS JURISDICTION. |
| | PLEASE SEE THE MAIN MAY NOT BE LOCATED ON THE SECOND |
| | FLOOR AS SHOWN. THIS AHJ DOES NOT HAVE AN ISSUE WITH |
| | MAINS LOCATED ON THE MEZZANINE LEVEL OR 2ND FLOOR AS |
| | LONG AS DIRECT ACCESS TO MAINS FROM THE OUTSIDE OF THE |
| | BUILDING IS DESIGNED. AS SHOWN ON PLANS THIS IS NOT |
| | DONE. |
| | 230.70.230.71.230.72 ETC |
| | THE METER CENTERS MAY BE LOCATED IN ELECTRICAL ROOMS |
| | ABOVE THE FIRST FLOOR HOWEVER MAINS MUST BE GROUPED AND |
| | LOCATED ON FIRST FLOOR. |
| | ** AS THERE WILL BE SEVERAL DESIGN CHANGES TO THE |
| | ELECTRICAL SERVICE MANY OF THE COMMENTS WILL NOT APPLY |
| | HOWEVER COMMENTS ARE MADE BASED ON THE PLANS |
| | SUBMITTED. |
| | |
| | 12) NOTE: PLEASE SEE THE LOCATIONS OF ELECTRICAL PANELS |
| | IN MANY UNITS DO NOT MEET 110.26, 408.7, 240.24. PLEASE |
| | SEE MANY OF THESE WILL BE REQUIRED TO BE MOVED. PLEASE |
| | ALSO SEE MANY SHEETS INDICATE A SHIFT OF SOME KIND |
| | WHICH PLACES SOME OF THESE PANELS IN LOCATIONS WHERE NO |
| | WALLS ETC ARE PRESENT. |
| | |
| | 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE PROPOSED INSTA-HOT WATER HEATING UNITS. |
| | 90.7,110.3 |
| | FBC 106.1.2 |
| | |
| | 14) NOTE: PLEASE SEE THERE ARE MISSING EXIT SIGNS AND |
| | LIGHTING REQUIRED PER NFPA-101. 7.8 AND 7.9. PLEASE SEE |
| | FIRE MARSHAL OFFICE COMMENTS ALSO. |
| | |
| | 15) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL |
| | EGRESS PATHS FORM CONDO UNITS. PLEASE SEE NFPA-101 |
| | 7.8.1.3, 7.9.2.2 FOR STAIRS. PLEASE SUBMIT AND INDICATE |
| | LEVELS UNDER NORMAL AND EMERGENCY. |
| | PLEASE SEE THE LIGHTING AS SHOWN IN STAIRS DOES NOT |
| | MEET THE LS 101 SECTIONS FOR MINIMUM REQUIREMENTS. |
| | PLEASE SEE MISSING LIGHTING IN GARAGE. |
| | PLEASE SEE THE FOLLOWING LOCATIONS WILL BE REQUIRED TO |
| | CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND. |
| | MAIN ELECTRICAL ROOMS, FIRE COMMAND ROOMS ,STAIRS ETC |
| | AS STATED. |
| | PLEASE ALSO SEE 700.16, 700.12F |
| | |
| | |
| | PLEASE SEE NOT #8 ABOVE WITH RESPECT TO THE TYPE OF |
| | FIXTURES AND THE FIXTURE LEGEND TO BE COMPLETED. |
| | |
| | 16) NOTE: PLEASE PLANS INDICATE SMOKE DETECTORS AND NOT |
| | SMOKE ALARMS HOWEVER NO INFORMATION IS SHOWN FOR |
| | SOUNDING DEVICES OR SYSTEM IF THESE DEVICES ARE INDEED |
| | SMOKE DETECTORS. |
| | PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE DETECTORS AND |
| | SMOKE ALARMS. |
| | PLEASE ADJUST PLANS ACCORDINGLY AND CIRCUIT PLANS AS |
| | NEED. |
| | PLEASE SEE 115.1.1.1 AND 11.8.3. |
| | |
| | 11) NOTE: PLEASE KNOW EVEN AS ANY FIRE SPRINKLER OR |
| | FIRE ALARM PLANS WILL BE REQUIRED UNDER A SEPARATE |
| | PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE |
| | MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND |
| | .3(4). |
| | PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING |
| | REQUIRED INFORMATION. |
| | |
| | 12) NOTE: PLEASE INDICATE ALL THE REQUIRED ARC FAULT |
| | PROTECTED CIRCUITS ON PANE SCHEDULE(S). PLEASE SEE THE |
| | NOTE LOCATED ON PLANS QUOTING THE CODE INSTEAD OF |
| | SHOWING THE REQUIRED DETAIL IS NOT ACCEPTABLE. |
| | FBC 106.3.5.1.2, 106.1.2, NEC 408.4, 210.12 |
| | |
| | 13) NOTE: PLEASE SEE THERE IS A SHIFT ON PLANS IN MANY |
| | LOCATIONS WHICH SEEMS TO MISPLACE CIRCUITING AND OTHER |
| | ITEMS FOR REVIEW. |
| | PLEASE BE SURE PLANS ARE CORRECTED. |
| | FBC 106.1 |
| | |
| | 14) NOTE: PLEASE SEE NEC 210.52B1, 210.11C1, 220.53 AS |
| | THE TWO MINIMUM SMALL APPLIANCE CIRCUITS COULD NOT BE |
| | LOCATED ON PLANS. PLEASE SEE VA SHALL MEET THE MINIMUM |
| | AS STATED IN THE NEC, NOT THE VA AS STATED ON PANEL |
| | SCHEDULE. |
| | PLEASE SEE SOME UNITS INDICATE SOME SORT OF |
| | DINING/BREAKFAST AREAS WHICH CIRCUITING IS REQUIRED TO |
| | MEET THE SAME CODE SECTIONS AS GIVEN. |
| | |
| | 15) NOTE: PLEASE SEE MISSING THE *ENLARGED ROOM LAYOUT* |
| | FOR THE WEST ELECTRICAL ROOM. |
| | FBC 106.1, 106.1.2 |
| | |
| | 16) NOTE: PLEASE SEE LOAD CALCULATIONS FOR SERVICE(S) |
| | DO NOT CORRELATE WITH ALL LOADS AS STATED ON ELECTRICAL |
| | PANELS. |
| | PLEASE SEE THERE ARE SUBSTANTIAL LOADS MISSING FROM |
| | BUILDING LOAD CALCULATIONS ALL TOGETHER? |
| | PLEASE SEE THE LOADS ARE ALREADY SHOWN ON UNIT PANELS |
| | AT 70AMPS AND SOME LOADS ARE NOT SHOWN CORRECTLY AND |
| | NOT FIGURED AT ALL. PLEASE KNOW AS SHOWN EACH OF THESE |
| | UNITS WILL BE REQUIRED TO HAVE A LARGER FEEDER, SERVICE |
| | TO EACH UNIT. NO DESIGN HAS BEEN TAKEN FOR FUTURE |
| | LOADS. 90.8 |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125% PLEASE SEE |
| | NEC 220 |
| | FBC 106.3.5.1.2 |
| | |
| | 17) NOTE: PLEASE SEE THE PLANS SHALL ALL INDICATE A |
| | MINIMUM OF 1/8INCH SCALE. FBC ADMIN SECTION. 106.1 |
| | |
| | 18) NOTE: PLEASE SEE THERE ARE MULTIPLE VOLTAGES SHOWN |
| | ON THE SAME SERVICE EQUIPMENT? |
| | PLEASE CORRELATE. |
| | FBC 106.3.5.1.2, NEC 230, 240 ETC |
| | |
| | 19) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS TO UNITS AS REQUIRED PER 250.24, 250.110, |
| | 250.122. |
| | PLEASE BE SURE TO INDICATE ALL AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 20) NOTE: PLEASE CLARIFY COLD WATER AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. 250.50. |
| | |
| | 21) NOTE: PLEASE SEE 210.52 AS SOME UNITS ARE MISSING |
| | REQUIRED RECEPTACLES FOR 2FT OR MORE OF WALL SPACE. |
| | PLEASE SEE THIS INCLUDES KITCHEN WALLS. |
| | |
| | 22) NOTE: PLEASE SUBMIT/INDICATE ALL OF THE REQUIRED |
| | AIC RATINGS FOR SERVICE EQUIPMENT/MAINS AND BRANCH |
| | BREAKERS. |
| | 110.9. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 23) NOTE: PLEASE SEE THE CIRCUITING FORWASHERS AND |
| | DRYERS CAN NOT BE CORRECT. PLEASE SEE SOME WASHERS |
| | INDICATE 240V CIRCUITS TO THEM AND THE DRYERS INDICATE |
| | 120V CIRCUITS? PLEASE CORRELATE ALL OF THESE. |
| | FBC 106.1.2 |
| | |
| | 24) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI |
| | PROTECTION OF ALL RECEPTACLES LOCATED WITHIN 6FT OF |
| | LAUNDRY TUBS. THIS INCLUDES 15/20AMP 120V DEDICATED |
| | CIRCUITS. THIS IS NEW IN THE 2005 NEC> |
| | |
| | 25) NOTE: PLEASE SEE PLANS INDICATE 310.15B6 FOR |
| | DE-RATING OF FEEDERS AND SERVICE CONDUCTORS. PLEASE SEE |
| | THE SECTION OF THE CODE DOES NOT APPLY TO THE SERVICE |
| | AS SHOWN. |
| | PLEASE ADJUST. |
| | |
| | 26) NOTE: PLEASE SEE BUILDING REVIEW NOTES AND CLARIFY |
| | *BUILDING* SEPARATIONS. PLEASE SEE AT THIS TIME THIS IS |
| | BEING SHOWN AS TWO SEPARATE BUILDINGS AND BASED ON |
| | PLANS THE SEPARATION OF THESE BUILDINGS DOES NOT APPEAR |
| | TO GIVE IT THE DEFINITION OF TWO SEPARATE BUILDING |
| | BASED ON THE FBC. |
| | PLEASE SEE THIS WILL GREATLY AFFECT THE NOTE # 11 |
| | ABOVE. |
| | |
| | 27) NOTE: PLEASE SHOW LOCATIONS FOR ALL PANELS. WHERE |
| | ARE THE HOUSE PANELS ALL LOCATED? |
| | |
| | 28) NOTE: PLEASE KNOW AS PER FPL GUIDELINES, NO |
| | ELECTRICAL FROM BUILDING MAY BE INSTALLED IN FPL |
| | VAULT/TRANSFORMER ROOMS. |
| | PLEASE ALSO SEE MINIMUM FIRE SEPARATION REQUIRED PER |
| | 450.42 |
| | |
| | 29) NOTE: PLEASE SEE 680.41, 680.44 ETC AS THE LOCATION |
| | S SHOWN FOR THE ELECTRICAL FOR THE JACUZZIS ARE SHOWN |
| | TOO CLOSE. PLEASE ALSO INDICATE THE EPO LOCATIONS. |
| | |
| | |
| | *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES |
| | REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH |
| | ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENT SON |
| | THE FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-01 08:52:00 | 2007-07-01 08:52:00 |
| | REVIEW IN PROGRESS, NOTES TO FOLLOW. |
| 2007-06-29 20:01:49 | 2007-06-29 20:01:49 |
| | REVIEW NOT COMPLETE. NOTES WILL FOLLOW. |
| 2007-06-29 18:56:54 | 2007-06-29 18:56.54 |
| | REVIEW IN PROGRESS |
| 2007-06-29 07:32:26 | 2007-06-29 07:32:26 |
| | RREMOVED FROM INCOMING, IN ELEC FOR REVIEW. WILL ROUTE |
| | BACK TO INCOMING ONCE REVIEW IS COMPLETE. |