Plan Review Details - Permit 07060502
Plan Review Stops For Permit 07060502
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-26 Cont ID  
Sent By mjacobs Date 2007-09-26 Time 17:23 Rev Time 0.00
Received By mjacobs Date 2007-09-26 Time 16:54 Sent To PC
Notes
2007-09-26 17:23:26PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-23 Cont ID  
Sent By mjacobs Date 2007-09-23 Time 08:52 Rev Time 0.00
Received By mjacobs Date 2007-09-23 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-01 Cont ID  
Sent By mjacobs Date 2007-09-01 Time 07:16 Rev Time 0.00
Received By mjacobs Date 2007-08-31 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By mjacobs Date 2007-06-25 Time 08:39 Rev Time 0.00
Received By mjacobs Date 2007-06-22 Time 15:42 Sent To  
Notes
2007-06-25 08:39:07BUILDING PLAN REVIEW
 PERMIT: 07060502
 ADD: 2101 OKEECHOBEE BLVD
 CONT: PROENACK CORP.
 TEL: (561)691-2400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE CALIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE WINDOW SCHEDULE UNIT 3 SHOWS WINDOW (A) AND
 (B), ARE THESE TWO WINDOWSBEING CHANGED TO IMPACT
 WINDOWS? IF SO, SUBMIT THE PRODUCT APPROVAL FOR WINDOW
 (A). DOOR SCHEDULE UNIT 2 HASTHE SAME PROBLEM, SO
 SUBMIT THE PRODUCT APPROVAL FOR THE EXTERIOR STEEL
 DOOR.
  
 4)THE CONTRACTOR SHALL PRINT AND SIGN HIS/HER NAME ON
 THE PERMIT APPLICATION. ALL SIGNATURES MUST BE
 ORIGINAL.
  
 5)THE DRAWINGS SUBMITTED ARE NOT ON THE STATE
 WEBSITE. THE STATE APPROVAL STAMP IS ALSO MISSING FROM
 THE PLANS. IF THESE PLANS WERE NOT APPROVED BY THE
 STATE, THEY WILL BE REVIEWED BY ALL THE TRADES OF THE
 BUILDING DEPARTMENT FOR CODE COMPLIANCE AND LIFESAFETY.
 THE PLANS ARE ALSO MISSING PAGES 3-5.
  
 6)FL ENERGY EFFICIENCY CODE 400.ABCD.2
 THE BUILDING'S OWNER, THE OWNER'S
 ARCHITECT, OR OTHER AUTHORIZED AGENT
 LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY TO THE BUILDING OFFICIAL THAT
 THE BUILDING IS IN COMPLIANCE WITH THE
 ENERGY EFFICIENTY CODE.
  
 7)A COMPLETE EXTERIOR WALL DETAIL INDICATING ALL
 MATERIALS SHALL BE SUBMITTED.
  
  
 NOTE; THERE IS FLAG IN OUR COMPUTER SYSTEM REGUARDING
 THE FOUNDATION PERMIT AT THIS LOCATION WHICH WILL SOON
 BE EXPIRED, SHOW HOW THIS STRUCTURE WILL MEET THE
 REQUIRED FOUNDATION REQUIREMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-18 Cont ID  
Sent By dpalmer Date 2007-09-18 Time 09:35 Rev Time 0.00
Received By dpalmer Date 2007-09-18 Time 09:35 Sent To I
Notes
2007-09-18 09:36:26PLANS REMOVED FROM INCOMING, ROUTED BACK TO INCOMING
 WHERE THEY ARE NEXT IN LINE FOR COMM BOARD.
 *NEW SHEETS, NEW SETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 10:16 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 09:27 Sent To  
Notes
2007-08-27 10:17:07*** DENIED ***
  
 1) NOTE: PLEASE SEE THE REVISED ENERGY CALCULATIONS
 SUBMITTED ARE MISSING THE INPUT DATA REPORTS FOR EACH
 SET.
 PLEASE SEE PAGE 2 OF THE SUMMARY SHEETS WHICH CLEARLY
 STATES THE INPUT DATA REPORT IS REQUIRED TO ACCOMPANY
 THE CALCULATIONS.
 13-415.1, 13-415.2, 13-103.1.1.1.
  
 2) NOTE: PLEASE KNOW THIS OFFICE IS AWARE OF THE PLANS
 AND SUPPORTING DOCUMENTS WHICH ARE *STATE APPROVED* ARE
 PERMITTED TO BE PHOTO-COPIES OF THE STATE STAMPED
 SIGNED AND SEALED PLANS AS LONG AS THEY MATCH WITH THE
 STATE PLANS ON FILE. * THIS IS BEING DONE ON SEVERAL
 SHEETS OF THE PLANS INCLUDING THE ENERGY CALCULATIONS.
 PLEASE SEE SOME SHEETS DO HOWEVER CONTAIN AN ORIGINAL
 SIGNATURE AND SEAL?
 PLEASE KNOW HOWEVER PLACING A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE VIOLATES FAC 61G15-23.002 AND FS
 471.025.
 THIS WAS CONFIRMED BY THE FLORIDA BOARD OF ENGINEERS
 SOME TIME AGO THAT THE ENGINEER OF RECORD MAY NOT PLACE
 A RAISED SEAL OVER THE SIGNATURE AS THIS IS LEADING TO
 PLANS AND DOCUMENTS BEING*ORIGINAL*, WHICH THEY ARE
 NOT.
 THIS OFFICE HAS CONTACTED THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AS OF THIS REVIEW AS THIS IS
 STILL BEING DONE ON SEVERAL PROJECTS BY THE SAME
 DESIGNER.
 WE WILL BE AWAITING RULING FROM THE BOARD. *MAY SUBMIT
 ONLY THE COPIED STATE STAMPED PLANS AS LONG AS THEY
 CORRELATE WITH THE STATE SITE.
  
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By dpalmer Date 2007-06-28 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2007-06-28 Time 12:55 Sent To I
Notes
2007-06-28 12:56:46PLANS ROUTED BACK TO INCOMING.
2007-06-28 12:56:31*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE THE PLANS AS LISTED ON THE STATE
 WEBSITE DO NOT CONTAIN THE CHANGES AS SUBMITTED AND
 REVISED.
 PLEASE KNOW IT APPEARS THE STATE LISTING MAY BE VOID
 BASED ON THE REVISION SUBMITTED.
 PLEASE SUBMIT COMPLETE ELECTRICAL DETAILS AS THE SCOPE
 OF WORK WHICH WAS ON PREVIOUS PLANS IS BEING CHANGED.
 PLEASE ADJUST CIRCUITING, PANEL SCHEDULE ETC
 408.4, 310.16,
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SUBMIT COMPLETED AND REVISED ENERGY
 CALCULATIONS BASED ON THE MODIFICATIONS OF THIS UNIT.
 FBC 13-415.1.AB.1.1, 13-415.1.C ETC
 13-103.1.1.1
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK IS
 VERY LOW, PLEASE SEE THE VALUE IS TO INCLUDE ALL LABOR,
 MATERIALS, EQUIPMENT, DESIGN COST ETC.
 PLEASE SEE FBC 108.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-26 Cont ID  
Sent By mwennerg Date 2007-09-26 Time 15:45 Rev Time 0.00
Received By mwennerg Date 2007-09-26 Time 15:45 Sent To  
Notes
2007-09-26 15:45:56PLANS APPROVED ON 9/6/07 AND STAMPED ON THIS DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-06 Cont ID  
Sent By mwennerg Date 2007-09-06 Time 13:54 Rev Time 0.00
Received By mwennerg Date 2007-09-06 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By mwennerg Date 2007-06-25 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2007-06-25 Time 10:27 Sent To  
Notes
2007-06-25 10:30:56***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW COMMENTS AND COMPLY.
  
 2) WILL THIS WORK HAVE ANY IMPACT ON EXISTING FIRE
 PROTECTION SYSTEMS, IE FIRE ALARM ETC?
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241. PLEASE ADD TO DESIGN DATA.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 15:26 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 15:26 Sent To  
Notes
2007-09-18 14:31:33TO "COMM" BD#18--EXPEDITED--
2007-09-17 15:26:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 15:59 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 15:59 Sent To  
Notes
2007-08-27 08:24:02 
 8/27/07 **SPECIAL MAGISTRATE CASE. EXPEDITE PLAN
 REVIEW**.RB
  
2007-08-03 15:59:47WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By mwennerg Date 2007-06-25 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2007-06-18 Time 14:32 Sent To  
Notes
2007-06-29 10:57:27TO"COMM" BD#30
2007-06-26 10:56:056/26/07--PULLED FROM "BOB"--WAITING FOR "COMM" BD
2007-06-18 14:39:06TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-09-20 Cont ID  
Sent By rregueir Date 2007-09-20 Time 17:55 Rev Time 0.00
Received By rregueir Date 2007-09-20 Time 17:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-17 Cont ID  
Sent By rregueir Date 2007-07-17 Time 15:44 Rev Time 0.00
Received By rregueir Date 2007-07-17 Time 15:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-08-27 Cont ID  
Sent By kstevens Date 2007-08-27 Time 12:56 Rev Time 0.00
Received By kstevens Date 2007-08-27 Time 12:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 18:06 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 18:06 Sent To  
Notes
2007-07-14 18:22:04DENIED
 REFERENCE: FBC-2004
 CHAPTER 1
 CHAPTER 11
  
 1.SEE COMMENT #5 FROM THE BUILDING PLAN REVIEW AND
 COMMENT #1 FROM THE ELECTRICAL PLAN REVIEW.IF THE
 PLANS ARE TO BE REVIEWED BY ALL REVIEWERS THEN THE
 FOLLOWING INFORMATION WILL BE REQUIRED TO BE SHOWN ON
 THE PLANS.
  
 FOR THE TOILET ROOMS:
 __FOR THE W.C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.19.6 DISPENSERS
  
 FOR THE LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
  
 A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
  
 BAR SINK SHALL SHOW COMPLIANCE WITH SECTION 11-4.24
 WITH ALL SUBSECTIONS.
  
 2. THE FOLLOWING INFORMATION IS REQUIRED IN ANY CASE
 FOR PLUMBING PERMIT:
  
 AN RPZV BACKFLOW IS REQUIRED PER SECTION 608.13.2.
  
 A SITE PLAN SHOWING THE SEWER LATERAL AND THE WATER
 METER LOCATIONS. BACKFLOW SHALL BE AS CLOSE TO THE
 METER BUT ON PRIVATE PROPERTY .
  
 SHOW THE WATER SERVICE AND THE SEWER LINES AND INDICATE
 THEIR ROUTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]