Plan Review Details - Permit 07060501
Plan Review Stops For Permit 07060501
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-23 Cont ID  
Sent By lmartine Date 2008-05-23 Time 14:18 Rev Time 0.00
Received By lmartine Date 2008-05-23 Time 14:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-23 Cont ID  
Sent By jwitmer Date 2008-04-23 Time 13:52 Rev Time 4.44
Received By jwitmer Date 2008-04-23 Time 13:52 Sent To  
Notes
2008-04-23 13:56:51PLANS APPEAR TO BE CODE COMPLIANT, ONCE THE COUNTY
 IMPACT FEES ARE PAID AND THE BALANCE OF FEES TO THE
 CITY ($6,663.00) I'LL BE ABLE TO PASS AND ISSUE THIS
 PERMIT.
 NOTE THE ROOFING PERMIT WILL REQUIRE SEPERATE PERMIT,
 REVIEW, AND ASSOCIATEDFEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-19 Cont ID  
Sent By jwitmer Date 2008-03-19 Time 10:23 Rev Time 3.33
Received By jwitmer Date 2008-03-19 Time 10:23 Sent To  
Notes
2008-03-19 11:29:56SHELL 7204 S DIXIE HWY/ 07060501
 BUILDING PLAN REVIEW
 PERMIT: 07060501
 ADD: 7204 S DIXIE HWY
 CONT: BENCHMARK CUSTOM BUILDERS
 TEL: (954)802-0723
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) ADDITIONAL INFORMATION REQUIRED. THE PERMIT
 APPLICATION INDICATES A SHELL BUILDING WHILE THE PLANS
 INDICATE THIS TO BE A PHASED, PHASE I A COMMERCIAL
 FIRST FLOOR AND A PHASE II RESIDENTIAL
 SECOND FLOOR, ARE BOTH PHASES TO BE CONSIDERED WORK
 UNDER THIS PERMIT?
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. NOTE PLANS DO INDICATE 2004 FBC BUT NOT THE
 2006 AMENDMENTS, PLEASE CORRECT.
  
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. COMPLIED.
  
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. PARTIALLY COMPLIED. PLANS INDICATE A TYPE
 III BUILDING BUT NO DESIGNATION AS A OR B. NOTE: TABLE
 503WILL ALLOW THIS BUILDING TO BE BUILT AS A TYPE V-B
 EVEN FOR PHASE II, SEE SECTION 302.3.2 AND TABLE
 302.3.2. IF TO BE DESIGNED AS EITHER A TYPE III A OR B
 SEE TABLE 602 THAT WILL REQUIRE A 2HR RATED WALL FOR
 THE SOUTH WALL LOCATED 5.5' FROM THE PROPERTY LINE .
 PLEASE PROVIDE WHAT TYPE OF CONSTRUCTION THIS STRUCTURE
 WILL BE DESIGNED TOO.
  
 D) THE OCCUPANT LOAD, SEE 1004. NOTE WORST CASE
 SCENARIO WILL BE TAKEN 5863 SQ /30= 196 OCCUPANT LOAD
  
 E-K) COMPLIED.
  
 4) SHEET S-1 NOTE# 19 INDICATES THERE SHALL BE A
 SPECIAL INSPECTOR FOR THE REINFORCED MASONARY SHALL BE
 PROVIDED. ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL: 561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR,
 CONTRACTOR AND ENGINEER.
  
 5)COMPLIED.
  
 6) PROVISO 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7) PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 8)BOTH C1 - C4 HAVE TOTALLY DELETEDTHEJOBSITE
 LOCATION INTHE TITLE BLOCK.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS ANDTELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 XX - STATE PROJECT NAME AND LOCATION,IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE ANDDATED SEAL-
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 9)SEMI-COMPLIED SHEET A-2 INDICATES A MECHANICAL
 EQUIPMENT STANDBUT THE PRODUCT APPROVALS REQUIRED BY
 RULE 9B-72 DO NOT CONTAIN THE REPORT OR ASSCIATED
 TECHNICAL SHEETS.
  
 10) COMPLIED.
  
 11)2ND REQUEST,PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 12)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
  
 A) STOREFRONT- NO REPORT WAS SUBMITTED
  
 B) OUTSWING DOOR & TRANSOM - NO REPORT WAS SUBMITTED
  
 C) EXTERIOR METAL CORE DOOR
  
 D) PRE-ENGINEERED A/C STANDS- ONLY THE FLORIDA
 COVERSHEET SUBMITTED, NEEDS THE BACK UP REPORT AND
 TECNICAL DRAWINGS.
  
 E) GLASS BLOCK- REVIEWED OK
  
 F) TRUSS ANCHORS OR BUCKETS- NO REPORT SUBMITTED
  
 G) ROOFING ASSEMBLIES- NO REPORT SUBMITTED
  
 13) SHEET A-9 DETAIL# 5 INDICATES 2'X8' WOOD JOIST @
 2'-0" O. C. PLANS NOW INDICATE THE BUCKET TYPE BUT THE
 LENGHT OF THEEMBEDMENT OF THE 3/8" EXSPANSION BOLT IS
 NOT PROVIDED.
 106.1.2* ADITIONAL INFORMATION REQUIRED.
  
 14) 2ND REQUEST, SHEET A-1 STORAGE ROOM# 2THE DOOR ON
 THE RIGHT SIDE IS MISSING THE REQUIRED 18" SEE :
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 16)ARCHITECTURAL BUSINESS SOUTHEAST ARCHITECT
 SERVICES INC DOES NOT SHOW UP ON THE STATES DBPR
 WEBSITE USING THE FIRMS NAME NOR LICENSE NUMBER AA-C
 001953PLEASE PROVIDE CONFRAMATION OF THE FIRMS BUSINESS
 LICENSE. 481.219 F.S.CERTIFICATE OF AUTHORIZATION.
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 17) PROVISO: HOLLOW CORE SLAB PLANKS TO SUBMITT SHOP
 DRAWINGS REVIEWED BY THE DESIGN TEAM WITH APPROVAL
 STAMP.
  
 18-25) COMPLIED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-24 Cont ID  
Sent By jjohnsto Date 2007-10-24 Time 14:49 Rev Time 8.00
Received By jjohnsto Date 2007-10-24 Time 14:46 Sent To  
Notes
2007-10-24 14:48:57CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR,
 WEST PALM BEACH, FLORIDA33401
 TEL:561-805-6713FAX:561-805-6731
  
 JAMES JOHNSTON,
 E-MAIL:JJOHNSTON @WPB.ORG
 BUILDING PLAN EXAMINER II
  
 PERMIT NO 07060501
 ADDRESS7204 S. DIXIE HIGHWAY
 PROJECT FOREST POINT 1ST STORY
  
 DATE NOVEMBER 5, 2007
  
 BUILDINGPLANREVIEWFLORIDA BUILDING CODES
 2004
  
 THE FOLOWING COMMENTS ADDRESS THE PREVIOUS
 CRITQUE COMPLETED ON 7/29/07 BY JIM WHITMER
  
 1. COMPLIED
  
 2. COMPLIED
  
 3. COMPLIED
  
 4.
 NOT IN COMPLIANCE2ND REQUEST
  
 FBCBUILDING 104.3 EXAMINATION
 OF DOCUMENTS
 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL
 EXAMINE OR
 CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND
 THE
 ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS,
 SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND
 SHALL
 ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE
 CONSTRUCTION
 INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER
 PERTINENT
 LAWS OR ORDINANCES.
  
 COMMENT- PLEASE FURNISH THE THE FOLLOWING
 INFORMATION
  
 ON THE COVER SHEET
 PROJECT INFORMATION
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 ACCESSIBILITYCHAPTER 11
 TYPE OF CONSTRUCTION
 SPRINKLED / UN-SPRINKLED
 BASIC WIND SPEED - MPH
 WIND EXPOSURE
 WIND IMPORTANCE FACTOR & BUILDING CATEGORY INTERNAL
 PRESSURE COEFFICIENT
 TYPE OF OCCUPANCY
 OCCUPANT LOAD-GROSS - NET
 5
 NOT IN COMPLIANCE2ND REQUEST
  
 FBC BUILDING1802.6 SOIL REPORTS.
 THE SOIL CLASSIFICATION AND DESIGN LOAD-BEARING
 CAPACITY
 SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT.
 WHERE REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN
 REPORT
 OF THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES,
  
 BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION:
  
 1.A PLOT SHOWING THE LOCATION OF TEST BORINGS
 AND/OR
 EXCAVATIONS.
 2. A COMPLETE RECORD OF THE SOIL SAMPLES.
 3. A RECORD OF THE SOIL PROFILE.
 4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. 5.
 RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN
 CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING
 CAPACITY
 OF NATURAL OR COMPACTED SOIL; PROVISIONS TO
 MITIGATE
 THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF
 THE EFFECTS
 OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT AND
 VARYING SOIL
 STRENGTH; AND THE EFFECTS OF ADJACENT LOADS. 6.
 EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. 7. PILE
 AND PIER FOUNDATION INFORMATION IN ACCORDANCE
 WITH SECTION 1808.2.2 .
 8. SPECIAL DESIGN AND CONSTRUCTION PROVISIONS FOR
 FOOTINGS
 OR FOUNDATIONS FOUNDED ON EXPANSIVE SOILS, AS
 NECESSARY.
  
 COMMENT-PLEASE SUBMIT THE SOIL TEST REPORT FOR
 THIS
 PROJECT BY QUESTENGINEERING AS NOTED ON THE
 STRUCTURAL
 SHEETS-1.
  
  
 6
 COMPLIED
  
  
 7
 COMPLIED
  
  
 8
 COMPLIED
  
  
 9
 COMPLIED
  
 10
 COMPLIED
  
 11
 NOT IN COMPLIANCE2ND REQUEST
  
 PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
 SUBMIT TWO COPIES OF EACH APPROVAL
 ( 3 COPIES IF A THRESHOLD BUILDING ) WITH FLORIDA
 PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING
 ?TO THE BEST OF THEIR KNOWLEDGE THE PRODUCT APPROVAL
 COMPLIES WITH THE PLANS AND SPECIFICATIONS.
  
 COMMENT-IN ADDITION TO THE MIAMI-DADE NOA
 PLEASE PROVIDE FLORIDA PRODUCT APPROVALS FOR ALL
 PRODUCTS
 REQUIRED TO BE SUBMITTED.SEE INFORMATION SUBMITTED
 ABOVE.
 THE DELTA DOOR COMPANY DOES NOT HAVE FLORIDA PRODUCT
 APPROVAL.
  
 11A
 FLORIDA ADMINISTRATIVE CODE9B-72.030 EXCEPTIONS.
 LOCAL PRODUCT APPROVAL GENERALLY
 PRODUCTS LISTED IN RULE 9B-72.005, F.A.C., SHALL BE
 APPROVED
 ACCORDING TO THE PROVISIONS OF THIS RULE.
 (1) PRESCRIPTIVE.PRODUCTS THAT HAVE PRESCRIPTIVE
 SPECIFICATION STANDARDS AND ARE MANUFACTURED UNDER
 QUALITY ASSURANCE PROCEDURES AS SPECIFIED IN THE CODE
 WILL BE DEEMED APPROVED.
 SUCH PRODUCTS SHALL INCLUDE BUT NOT BE LIMITED TO THE
 FOLLOWING:
 (A) STRUCTURAL COMPONENTS COVERED BY UNITED STATES
 DEPARTMENT OF COMMERCE PRODUCT STANDARDS;
 (B) STRUCTURAL COMPONENTS COMPRISED OF PRODUCTS THAT
 ARE ASSEMBLED OR PLACED IN THE FIELD AND ARE SUBJECT
 TO
  
 STANDARDIZED FIELD TESTING PROCEDURES CONTAINED WITHIN
  
 NATIONALLY RECOGNIZED STANDARDS ADOPTED WITHIN THE
 CODE
  
 MAY DEMONSTRATE COMPLIANCE BY A BATCH TICKET OR BILL
 OF
 LADING MADE AVAILABLE AT THE SITE OF ASSEMBLY OR
 PLACEMENT;
 (C) CUSTOM (ONE OF A KIND) PRE-ENGINEERED BUILDINGS.
 (2) PERFORMANCE. PRODUCTS, METHODS AND SYSTEMS OF
 CONSTRUCTION SPECIFICALLY ADDRESSED IN THE CODE
 THROUGH
  
 PERFORMANCE CRITERIA SHALL DEMONSTRATE COMPLIANCE
 PURSUANT TO RULE 9B-72.070, F.A.C., AND SHALL BE
 APPROVED
 PURSUANT TO RULE 9B-72.090, F.A.C.
  
 COMMENT-FOR DELTA DOOR
  
  
 11B
 FLORIDA ADMINISTRATIVE CODE9B-72.050
 PRODUCT APPROVAL BY LOCAL JURISDICTION
 AND ACCEPTANCE
 (1) APPROVAL OF A PRODUCT FOR LOCAL USE SHALL BE
 PERFORMED
 BY THE BUILDING CODE OFFICIAL OR HIS/HER DESIGNEE BY
 VERIFYING THAT THE PRODUCT COMPLIES WITH THE CODE IN
 ACCORDANCE WITH RULE 9B-72.040, F.A.C.
 (A) THE AUTHORITY HAVING JURISDICTION OR BUILDING
 OFFICIAL
 SHALL VALIDATE THE METHOD OF COMPLIANCE PURSUANT TO
 RULE 9B-72.040, F.A.C.
 (B) UPON ACCEPTANCE OF REQUIRED DOCUMENTATION PURSUANT
 TO SUBSECTION 9B-72.040(5), F.A.C., THE AUTHORITY
 HAVING JURISDICTION OR BUILDING OFFICIAL MAY
  
 DEEM THE PRODUCT APPROVED FOR USE IN ACCORDANCE WITH
 ITS APPROVAL AND LIMITATION OF USE.
 (C) APPROVAL SHALL BE VALID UNTIL SUCH TIME AS THE
 PRODUCT
 CHANGES DECREASING THE PRODUCT?S PERFORMANCE,
 THE STANDARDS OF THE CODE CHANGE, OR THE APPROVAL IS
 OTHERWISE SUSPENDED OR REVOKED.
 CHANGES TO THE CODE SHALL NOT BE CONSTRUED AS VOIDING
 THE APPROVAL OF PRODUCTS PREVIOUSLY INSTALLED IN
 EXISTING
 BUILDINGS PROVIDED SUCH PRODUCTS MET BUILDING CODE
 REQUIREMENTS AT THE TIME THE PRODUCT WAS INSTALLED. (D)
 MANUFACTURER SHALL NOTIFY THE AUTHORITY HAVING
 JURISDICTION OR THE BUILDING OFFICIAL WHEN THE QUALITY
  
 ASSURANCE REQUIREMENTS OF SUBSECTION 9B-72.040(4),
 F.A.C.,
 ARE NO LONGER IN PLACE.
 (2) ACCEPTANCE OF A PRODUCT, MATERIAL OR SYSTEM OF
 CONSTRUCTION IS SPECIFIC TO A PROJECT AND REQUIRES
 APPROVAL BY A LOCAL JURISDICTION PURSUANT TO RULE
 9B-72.050, F.A.C., OR STATEWIDE APPROVAL BY THE
 COMMISSION PURSUANT TO RULE 9B-72.090, F.A.C.,
 AND VERIFICATION THAT THE PRODUCT IS BEING USED
 CONSISTENT WITH THE APPROVED EVALUATION AND
 LIMITATIONS
  
 OF USE ESTABLISHED BY THE APPROVED EVALUATION AS
 REQUIRED BY THE DESIGN SPECIFICATIONS.
  
 COMMENT-USE FLORIDA ADMINISTRATIVE CODES 9B-72.050
 AND9B-72.030FOR DELTA DOOR CO.
 PLEASE FIND THE CITY OF WEST PALM BEACH
 ?SITE SPECIFIC? ?LOCAL PRODUCT APPROVAL? ATTACHED
 FORMS.
 SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL
 COVER PAGE FOR THE FOLLOWING
 COMPONENTS THAT ARE APPLICABLE
 FIXED GLASS
 MULLION TUBES
 STORE FRONT GLAZING SYSTEM
 ALUMINUM OUT -SWING DOORS
 EXTERIOR HOLLOW METAL DOORS
 EXTERIOR GLAZED DOORS
 ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION,
 UNDERLAYMENT,ROOF TILE,ROOF SYSTEM
 PREENGINEERED AC STAND
 GLASS BLOCK
 TRUSS ANCHORS
  
  
 12
 NOT IN COMPLIANCE2ND REQUEST
  
 FBCBUILDING 1609.1.3COMPONENTS & CLADDING ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDING. STRUCTURAL
 MEMBERS AND SYSTEMS AND COMPONENTS
 AND CLADDING IN A BUILDING OR STRUCTURE SHALL BE
 ANCHORED
 TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING
 AND
 TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO
 THE
 FOUNDATION.
 WHERE A PORTION OF THE RESISTANCE TO THESE FORCES IS
 PROVIDED BY DEAD LOAD, THE DEAD LOAD, INCLUDING THE
 WEIGHT
 OF SOILS AND FOUNDATIONS, SHALL BE TAKEN AS THE
 MINIMUM
  
 DEAD LOAD LIKELY TO BE IN PLACE DURING A DESIGN WIND
 EVENT.
  
 COMMENT
 SEE ITEM 11
  
  
  
  
 FLORIDA ADMINISTRATIVE CODE61G15-23.002 SEAL,
 SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX
 HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER?S
 REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR ISSUED
 BY SAID REGISTRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED AS
 PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS
 IMMEDIATELY
  
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. (2)
 EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
  
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED,
 SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER,
 AND THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS WILL SATISFY THIS
 REQUIREMENT.
  
 COMMENT-CARMAN VERDE AND ASSOCIATE?S LICENSE
 IS LISTED WITH THE DBPR AS ?DELINQUENT, ACTIVE.
  
 PLEASE SUBMIT THE CORRECT SURVEY FOR
 THIS PROJECT
 SHEET 1 OF 1 - BOUNDARY AND TOPOGRAPHIC SURVEY SHALL
 BE-SIGNED, SEALED, PRINTED NAME AND INCLUDE THE
 COMPANY CERTIFICATE OF AUTHORIZATION.
  
  
  
  
 13
 COMPLIED
  
  
 14
 COMPLIED
  
 15
 NOTED FOR COMPLIANCE
 THE FOLLOWING COMMENTS ARE THE RESULTS OF ADDITIONAL
 INFORMATION WHICH WAS REQUESTED
 BY THE PREVIOUS PLAN REVIEWER
  
 16
 ARCHITECTURAL
 FLORIDA ADMINISTRATIVE CODE61G1-16.002
 ARCHITECTDESCRIPTION OF SEAL
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT
 OR INTERIOR DESIGNER AND THE REGISTRATION NUMBER; THE
 SEAL OF THE ARCHITECT SHALL BE CIRCULAR, AND THE SEAL
 OF
 THE INTERIOR DESIGNER SHALL BE HEXAGONAL.
 BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL SEAL,
 APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR LINES
 BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE
 WORDS
 ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS ?
 REGISTERED ARCHITECT? OR ?LICENSED INTERIOR DESIGNER,?
  
 WHICHEVER IS APPLICABLE.
 (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT
 AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH
 CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN
 REGISTRATION NUMBERS, IN SUCH A MANNER:
  
 COMMENT-SOUTHEAST ARCHITECT SERVICES, INC. PLEASE
 VERIFY YOUR SEAL IS IN COMPLIANCE WITH RULE
 61G1-16.002
  
  
 17
 FBC BUILDING 104.3 EXAMINATION OF DOCUMENTS 104.3.1
 PLAN REVIEW. THE BUILDING OFFICIAL SHALL EXAMINE OR
 CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND
 THE ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS,
 SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND
 SHALL
 ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE
 CONSTRUCTION
 INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER
 PERTINENT
 LAWS OR ORDINANCES.
  
 COMMENT- PLEASE FURNISH THE HOLLOW CORE SLAB
 ENGINEERING DOCUMENTS.
 HAVE THE ARCHITECT OF RECORD NOTE ACCEPTANCE OF THIS
 PRODUCT
  
  
  
 CHAPTER11 ACCESSIBILITY
  
 18
 FBC BUILDING 11-4.3ACCESSIBLE ROUTE
 (1)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY
 OF THE SITE SHALL BE PROVIDED FROM PUBLIC
 TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND ACCESSIBLE PASSENGER
 LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE.
 THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM EXTENT
 FEASIBLE,
 COINCIDE WITH THE ROUTE FOR THE GENERAL PUBLIC. (2) AT
 LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, FACILITIES, ELEMENTS, AND SPACES THAT ARE ON
 THE
 SAME SITE.
 (3)AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDINGS OR FACILITY ENTRANCES WITH ALL
 ACCESSIBLE SPACES AND ELEMENTS AND WITH ALL ACCESSIBLE
  
 DWELLING UNITS WITHIN THE BUILDING OR FACILITY. (4) AND
 ACCESSIBLE ROUTE SHALL CONNECT AT LEAST ONE ACCESSIBLE
 ENTRANCE OF EACH ACCESSIBLE DWELLING UNIT.
  
 COMMENTDEFINETHE TRANSITION FROM THE BOUNDARY
 WALKWAY ACROSS THE DRIVEWAY ENTRANCES TO THE PUBLIC
 SIDEWALK WITHOUT A CHANGE IN ELEVATION
  
  
 18 B
 FBC BUILDING 11-4.1.3 ACCESSIBLE BUILDINGS:
 NEW CONSTRUCTION
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION
 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES
 WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE
 BUILDING
 OR FACILITY.
  
 COMMENT THE SIDEWALK ALONG THE FRONT OF THE BUILDING
 DOES NOT CONTINUE TO THE SIDEWALK LOCATED AT THE
 NORTH.
  
 SHOW ALL CONNECTIONS FOR VERIFICATION OF ELEVATION.
  
 19
 FBC BUILDING 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING
 SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED
 METHODS OF TERMITE PROTECTION LABELED FOR USE AS A
 PREVENTATIVE TREATMENT TO NEW CONSTRUCTION.
  
 COMMENTFURNISH THIS INFORMATION ON SHEET S-1
 OR WHERE APPLICABLE
  
  
 20
 FBC1905.1.1 CONCRETE STRENGTH.
 CONCRETE SHALL BE PROPORTIONED TO PROVIDE AN AVERAGE
 COMPRESSIVE STRENGTH AS PRESCRIBED IN SECTION 1905.3 ,
  
 AND SHALL SATISFY THE DURABILITY CRITERIA OF SECTION
 1904 .
  
 COMMENT-
 SHEET-SP-2 PROVIDE THE CONCRETE DESIGN MIX FOR THE
 DUMPSTER SLAB.
 SHEET - S-1 PROVIDE THE DESIGN MIX FOR THE SLAB.
 ?FOUNDATION NOTES? STATE THAT A SAFE BEARING CAPACITY
 IS
 2,500 LBS.SPECIFY IF THIS IS THE INTENDED DESIGN
 MIX.
  
  
  
 21
 WPB ADMENDMENT106.1.1.2 FOR ROOF ASSEMBLIES REQUIRED
 BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE, AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED.
  
  
  
 21A
 FBC BUILDING 1507.10.1 SLOPE.
 BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM
 OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR
 BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF A
 MINIMUM
 ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
  
 COMMENT-DEFINE THE ROOF SLOPE FOR DRAINAGE ON SHEET
 A-2.
 INDICATE THE ROOF SURFACE ELEVATION AT THE EAST AND
 WEST.
 COORDINATE THE ARCHITECTURALWITH THE STRUCTURAL
 DETAILS
 REFERENCING THE TIE BEAM ELEVATION
  
  
  
 22
 FBC BUILDING 13-404.1.ABC.1 ROOF/CEILING THERMAL
 ENVELOPES.
 THE ROOF OR CEILING WHICH FUNCTIONS AS THE BUILDING?S
 THERMAL ENVELOPE SHALL BE INSULATED TO AN R -VALUE OF
 AT LEAST R-10. ROOF INSULATION SHALL NOT BE INSTALLED
 ON A
 SUSPENDED CEILING WITH REMOVABLE CEILING PANELS.
  
 COMMENT-ROOF INSULATION CANNOT BE USED IN THE
 SUSPENDED CEILING.
 PLEASE PROVIDE THE ROOF INSULATION MINIMUM OF R-10 AS
 NOTED FBC 13-404.1 ABOVE.
  
  
 23
 FBC BUILDINGTABLE 601
  
 COMMENT-DEFINE FIRE RESISTANT RATING FOR STEEL TUBE
 COLUMNS
  
  
 24
 FBC BUILDING TABLE 2304.7(3)
  
 COMMENTS IDENTIFY STRUCTURAL PANEL SHEATHING BY ITS
 RATING AND THIS TABLE FOR USE ON THIS PROJECT
  
  
 25
 FBC BUILDING 2121.2.5.1 PARAPET WALLS.
 MASONRY PARAPET WALLS SHALL BE NOT LESS THAN 8 INCHES
 THICK, SHALL BE REINFORCED WITH MINIMUMTIE COLUMNS
 AND SHALL BE COPED WITH A CONCRETE BEAM NOT LESS THAN
 64 SQUARE INCHES (.04 M 2 ) IN CROSS- SECTION,
 REINFORCED WITH TWO #4 REINFORCING BARS.
  
 COMMENTS- PROVIDE DETAILS FOR ANCHORING THE PARAPET
 WALL TO THE BUILDING STRUCTURE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-29 Cont ID  
Sent By jwitmer Date 2007-07-29 Time 20:54 Rev Time 1.22
Received By jwitmer Date 2007-07-29 Time 20:54 Sent To  
Notes
2007-07-29 22:08:12SHELL 7204 S DIXIE HWY/ 07060501
 BUILDING PLAN REVIEW
 PERMIT: 07060501
 ADD: 7204 S DIXIE HWY
 CONT: BENCHMARK CUSTOM BUILDERS
 TEL: (954)802-0723
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) ADDITIONAL INFORMATION REQUIRED. THE PERMIT
 APPLICATION INDICATES A SHELL BUILDING WHILE THE PLANS
 INDICATE THIS TO BE A PHASED, PHASE I A COMMERCIAL
 FIRST FLOOR AND A PHASE II RESIDENTIAL
 SECOND FLOOR, ARE BOTH PHASES TO BE CONSIDERED WORK
 UNDER THIS PERMIT?
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 H) NUMBER OF UNITS
 I) NUMBER OF FLOORS
 J) SQ. FT. LIV SPACE/ FL
 K) SQ. FT. FOOTPRINT
  
 4) SHEET S-1 NOTE# 19 INDICATES THERE SHALL BE A
 SPECIAL INSPECTOR FOR THE REINFORCED MASONARY SHALL BE
 PROVIDED. ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL: 561 805 6711), A
 MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR,
 CONTRACTOR AND ENGINEER.
  
 5) FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7)109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 8)BOTH C1 & C2 BOTH INDICATE THIS JOBSITE LOCATION TO
 BE ON NORTH DIXIE HWY, PLEASE CORRECT.
  
 9)SHEET A-2 INDICATES A MECHANICAL EQUIPMENT STAND
 WITH A NOTE SEE M-2 FOR DETAIL, MISSING SHEET M-2.
  
 10) SHEET A-2 ALSO INDICATES THE USE OF AN ATTACHED
 LADDER PLEASE PROVIDE MANUFACTURERS SPECS. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 12)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) STOREFRONT- NOTE THE STOREFRONT REPORT NOA
 04-0331.02 SECTION (3) CALCULATIONS HAS NOT BEEN
 VERIFIED UNDER THE 2004 FBC. THE ANCHOR CALCULATIONS
 WERE UNDER THE 2001 FBC WHEN FASTENERS WERE STILL
 TAKING THE 1 1/3 INCREASE PLEASE VERIFY THAT THE ANCHOR
 CALCULATION WILL COMPLY WITH THE 2004 FBC. 1606.3.1.1
 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR MORE LOADS IN
 COMBINATION WITH DEAD LOAD ARE INVESTIGATED IN LOAD
 COMBINATIONS OF 1605.3.1.1 THE COMBINED PLIED BY 0.75
 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS FROM THE LOAD
 COMBINATION OF THE DEAD LOAD PLUS THE LOAD PRODUCING
 THE LARGEST EFFECTS. INCREAS IN ALLOWABLE STRESS
 SPECIFIED IN THE MATERIALS SECTIONS OF THIS CODE OR A
 REFRENCED STANDARD SHALL NOT BE USED WITH THESE LOAD
 COMBINATIONS EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER 23.
  
 B) DH-350 ALUMINUM OUTSWING DOOR & TRANSOM REQUIRES
 FLORIDA COVER SHEET.
  
 C) EXTERIOR METAL CORE DOOR
  
 D) PRE-ENGINEERED A/C STANDS
  
 E) GLASS BLOCK
  
 F) TRUSS ANCHORS OR BUCKETS
  
 G) ROOFING ASSEMBLIES
  
 13) SHEET A-9 DETAIL# 5 INDICATES 2'X8' WOOD JOIST @
 2'-0" O. C. BUT THERE IS NO INFORMATION HOW THEY WILL
 BE SECURED IN PLACE?
 106.1.2* ADITIONAL INFORMATION REQUIRED.
  
 14) SHEET A-2 STORAGE ROOM# 2THE DOOR ON THE RIGHT
 SIDE IS MISSING THE REQUIRED 18" SEE :
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2008-04-03 Time 19:02 Sent To  
Notes
2008-04-03 19:03:162008-04-03 19:03:16
  
 ELECTRICAL PLANS STAMPED , ENERGY CALCS OK FOR
 ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:42 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:42 Sent To  
Notes
2008-02-11 08:42:54** DENIED**
  
 ** PLEASE SEE THE NOTES BELOW. IF ALL OTHER TRADES PASS
 THEIR REVIEWS PLEASE CONTACT THIS REVIEWER.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. PLEASE
 SEE FOR EXAMPLE INTERIOR FIXTURES ON PLANS CALL FOR
 11-100 WATT FIXTURES, YET THE INPUT DATA REPORT SHOWS
 9.
 PLEASE SEE THE CERTIFICATION SHEET PAGE #3 NEEDS TO
 CONTAIN THE SIGNATURE, DATE AND SEAL FROM THE ENGINEER
 MR. BUCHANAN. THE SEAL WAS PLACED ON COVER SHEET WHICH
 IS OK, HOWEVER THIS NEEDS TO BE ON THE CERTIFICATION
 SHEET AS STATED.
 13-103.1.1.1, FAC 61G15-23.002, FS 471.025
 PLEASE COMPLETE THE FIXTURE LEGENDS WITH THE TYPE OF
 FIXTURES WITH MORE DETAIL THAN ONLY STATING IT IS A
 100W FIXTURE OR SIMPLY A 75 WATT FIXTURE. PLEASE BE
 SURE TO CORRELATE WITH THE IDR.
  
 2) NOTE: PLEASE SUBMIT LIGHTING CONTROL DETAIL FOR THE
 OCCUPANCY SENSORS IN SPACE. COULD NOT LOCATE ANY RELAY
 DETAIL FOR POWER PACKS, WIRING METHODS ETC. WILL THESE
 BE LOW VOLTAGE TO POWER PACKS? WILL THESE BE 120V UNITS
 HARDWIRED? THIS IS THE SAME FOR THE TYPE OF DEVICE
 WHICH IS SHOWN IN SYMBOL LEGEND AS SM FOR WALL
 CONTROL.
 13-415.1.ABC.1.1, .1.2
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 3) NOTE: PLEASE SEE THE VA LOAD SHOWN ON PANEL SCHEDULE
 FOR HS-5 SHOWS 720 VA YET THE REVISED LOADS ON FIXTURES
 FOR OUTSIDE WALKWAYS ADDS UP TO A LOAD OF 900VA.
 IT IS VERY WELL THE SERVICE AND PANEL IS SIZED OK FOR
 LOAD, HOWEVER THIS NEEDS TO BE REVISED TO COORDINATE.
 NEC 220,
 FBC 106.3.5.1.2, 106.1.2
  
 ** PLEASE KNOW SOME OF THE ABOVE ITEMS MAY BE ABLE TO
 BE SET UP AS A *PROVISO*, HOWEVER THERE ARE FEW ITEMS
 WHICH MUST BE ADDRESSED AT THIS TIME. IF*ALL *OTHER
 REVIEWS PASS REVIEWS, PLEASE CONTACT THIS REVIEWER TO
 GO OVER WHAT WILL BE NEEDED FOR PERMIT ISSUANCE AND
 OTHER ITEMS CAN BE PART OF A *PROVISO*.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER DIRECTLY AT THE INFORMATION
 PROVIDED BELOW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By dpalmer Date 2007-10-05 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2007-10-04 Time 10:59 Sent To  
Notes
2007-10-05 09:02:03 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
  
 1) NOTE:PLEASE SEE COMMENT #3 FROM PREVIOUS REVIEW
 WHICH SPECIFICALLY REQUESTED NOT TO ATTACH PRODUCT
 APPROVALS AND SUPPORTING DOCUMENTS DOWN THE LEFT HAND
 SIDE OF PLANS. THESE WERE REMOVED BY THIS OFFICE ON THE
 TWO NEW SETS. PLEASE SEE THE PREVIOUS NOTE #3 BELOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ONLY COMPLETED SIGNED, DATED AND SEALED
 SETS COMPLETELY BOUND TOGETHER.
 PLEASE DO NOT SUBMIT COPIES OF PLANS.
 PLEASE DO NOT ATTACHED PRODUCT APPROVALS, ENERGY
 CALCULATIONS AND OTHER SUPPORTING DOCUMENTS ATTACHED
 DOWN THE LEFT HAND SIDE OF PLANS. PLEASE SUBMIT THESE
 IN FOLDERS/SPIRAL NOTE BOOKS OR SOME FASHION WHICH WILL
 BE SEPARATE FROM PLANS AND EACH SET.
 FBC 106.1
  
 2) NOTE: PLEASE CORRELATE ARCHITECTURAL FLOOR PLAN AND
 ELECTRICAL FLOOR PLANS. PLEASE SEE A SHEET INDICATES
 TENANT /BAY WALLS BEING INSTALLED YET THESE WALLS ARE
 NOT ON ELECTRICAL PLANS.
 PLEASE SEE NOTE BELOW WITH RESPECT TO CONTROLS FOR
 CHAPTER 13.
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW COMPLIANCE WITH FBC CHAPTER 13 HAS
 NOT YET BEEN ACHIEVED.
 PLEASE SEE NOTE #4 ABOVE FOR INSTANCE AS COMPLIANCE
 WITH 13-415.1.ABC.1.1 AND .1.3 IS NOT POSSIBLE IF THE
 WALLS AS SHOWN ON A-SHEETS ARE INSTALLED.
 PLEASE SEE THE EXACT SAME ENERGY CALCULATIONS WERE
 SUBMITTED BACK WITHOUT BEING REVISED. THESE
 CALCULATIONS DO NOT COORDINATE WITH PLANS ON SEVERAL
 ITEMS.
 PLEASE SEE THE ADDRESS IS NOT COMPLETE.
 PLEASE SEE THE SQ FT DOES NOT CORRELATE WITH PLANS WITH
 ARCHITECTURAL OR ELECTRICAL.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT
 DOES NOT CORRELATE FOR FIXTURES, WATTAGE, ETC. FOR
 EXAMPLE, THE PLANS ARE MISSING A FIXTURE LEGEND FOR ALL
 TYPES OF FIXTURES SO ACTUAL INPUT ON THE IDR CAN NOT BE
 VERIFIED AT THIS TIME.
 PLEASE ALSO SEE FOR EXAMPLE THE EXTERIOR LIGHTING WHICH
 STILL DOES NOT MATCH WITH PLANS FOR NUMBER OF FIXTURES
 ETC.
 PLEASE SEE 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3
 PLEASE SEE AS PREVIOUSLY NOTED, PLEASE BE SURE ALL ARE
 SIGNED, DATED AND SEALED ON THE *CERTIFICATION SHEET*,
 ALONG WITH OWNER AGENT.
 13-103.1.1.1, FS 471.025
 THESE WERE THE SAME COMMENTS FROM PREVIOUS REVIEW NOTE
 #5.
  
 4) NOTE:PLEASE SEE AS NOTED ON PREVIOUS REVIEW, IF
 BUILDING IS REQUIRED TO HAVE A FIRE ALARM SYSTEM
 INSTALLED EVEN THOUGH THIS IS TO BE DONE A SEPARATE
 PERMIT, THE BASE PLANS ARE REQUIRED UNDER THE FBC
 106.3.5.1.2 AND FLORIDA STATUTES 633 TO CONTAIN A BASE
 SYSTEM AND BASE COMPLIANCE. IF REQUIRED PER OTHER
 CODES, THE MINIMUM LOCATIONS AND LEVELS OF DEVICES ARE
 REQUIRED TO BE SHOWN FOR ADA COMPLIANCE.
 AS STATED ABOVE, THIS IS ONLY IF A SYSTEM IS REQUIRED.
 THE PLANS DO INDICATE A FA SYSTEM WILL BE INSTALLED.
 **PREVIOUS NOTE **
 PLEASE KNOW IF THERE IS ANY FIRE SPRINKLER OR FIRE
 ALARM PLANS WHICH MAY BE REQUIRED UNDER A SEPARATE
 PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE
 MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND
 .3(4).
 PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING
 REQUIRED INFORMATION.
  
 5) NOTE: PLEASE SEE SHEET E-3 WHICH IS MISSING BUILDING
 LAYOUT FROM PLANS.
 PLEASE SEE THE TITLE BLOCK ON THIS SAME SHEET IS ALSO
 MISSING THE ADDRESS AS SHOWN ON OTHER SHEETS.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-01 Cont ID  
Sent By dpalmer Date 2007-07-01 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2007-07-01 Time 11:08 Sent To  
Notes
2007-07-01 11:57:01 
  
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING
 ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED
 FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006
 THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004
 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER
 AND NO COST TO CONTRACTOR.
 PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY
 THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE.
  
 3) NOTE:PLEASE SUBMIT ONLY COMPLETED SIGNED, DATED
 AND SEALED SETS COMPLETELY BOUND TOGETHER.
 PLEASE DO NOT SUBMIT COPIES OF PLANS.
 PLEASE DO NOT ATTACHED PRODUCT APPROVALS, ENERGY
 CALCULATIONS AND OTHER SUPPORTING DOCUMENTS ATTACHED
 DOWN THE LEFT HAND SIDE OF PLANS. PLEASE SUBMIT THESE
 IN FOLDERS/SPIRAL NOTE BOOKS OR SOME FASHION WHICH WILL
 BE SEPARATE FROM PLANS AND EACH SET.
 FBC 106.1
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL TRADES ARE
 TO BE COMPLETE WITH ALL INFORMATION AS REQUIRED PER FAC
 61G1-16.004, 61G15-23.002 AND FLORIDA STATUTES 481.219
 AND 471.023.
 PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 LANDSCAPE ARCHITECT.
 PLEASE SEE THE PLANS SUBMITTED FOR LANDSCAPE SHEETS ARE
 IN FACT PHOTO-COPIES IN ALL SETS OF WHAT SHOULD BE
 SIGNED, DATED AND SEALED PLANS.
 FS 481.221.
  
 5) NOTE: PLEASE SEE FBC 2004 W/2006 REVISION FOR
 COMPLIANCE WITH CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING
 CONTROLS WHICH ARE MISSING FROM PLANS AT THIS TIME.
 PLEASE SEE THE DEVICE AS NOTED ON PLANS DO NOT SHOW UP
 IN THE SYMBOL LEGEND, SO THE DEVICES CAN NOT BE
 VERIFIED AT THIS TIME.
 PLEASE SUBMIT ALL INFORMATION IF A SYSTEM IS INSTALLED.
 IF ONLY OS TYPE DEVICES, PLEASE COMPLETE THE
 INFORMATION ON THESE.
 PLEASE BE SURE TO DETAIL THE WIRING OF ALL EMERGENCY
 AND EXIT LIGHTS AHEAD OF THESE DEVICES.
 PLEASE SUBMIT ANY TIMED SCHEDULING.
 PLEASE SUBMIT TIME ON DEVICES AND/OR OVER RIDE DEVICES.
 PLEASE SEE THE SECTIONS GIVEN FOR THE MAXIMUM TIMES
 PERMITTED.
 PLEASE SUBMIT COMPLETED FIXTURE LEGENDS FOR ALL
 FIXTURES WHICH ARE TO CONTAIN ALL INFORMATION ON THESE
 FIXTURES AND WILL NEED TO CORRELATE WITH LIGHTING
 PERFORMANCE CALCULATIONS FOR COMMON AREAS.
 PLEASE SEE NUMBER OF LUMINARIES, THE TYPE OF
 LUMINARIES, THE CONTROL OF LUMINARIES AS STATED ON THE
 ENERGY CALCULATIONS DO NOT CORRELATE WITH THE PLANS AS
 SUBMITTED.
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS PLEASE KNOW WHEN THE ENERGY CALCULATIONS
 ARE CORRECTED AND SUBMITTED THE OWNER AGENT IS REQUIRED
 TO BE SIGNED ON EACH. 13-103.1.1.1
 PLEASE SEE THE SHEET 3 FOR CERTIFICATIONS FROM ALL
 DESIGNER(S) IS THE SHEET WHICH IS REQUIRED TO BE
 SIGNED, DATED AND SEALED.
 13-415.1.AB.1.1, 13-415.1.C, 13-415.2.
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.1 OF THE FBC CHAPTER
 13. PLEASE SUBMIT WORST CASE SCENARIO FOR VOLTAGE DROP
 ON FEEDERS AND BRANCH CIRCUITS.
  
 7) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS FROM UNITS WHICH ARE BEING NOTED ON PLANS
 AS FUTURE DWELLING UNITS UPSTAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS.
 PLEASE SUBMIT AND INDICATE LEVELS UNDER NORMAL AND
 EMERGENCY.
 PLEASE SEE THERE IS NOT LIGHTING SHOWNFOR STAIRS
 PLEASE SEE 700.12F, 700.16
  
 PLEASE SEE NOT #5 ABOVE WITH RESPECT TO THE TYPE OF
 FIXTURES AND THE FIXTURE LEGEND TO BE COMPLETED.
  
 8) NOTE: PLEASE SEE AS PLANS ARE INCOMPLETE FOR ANY
 NOTES ON FUTURE UPSTAIRS UNITS ETC, THE ADDITIONAL
 SERVICE AS SHOWN ON PLANS AND RISER AS FUTURE IS NOT
 GRANTED AT THIS TIME.
 PLEASE COMPLETE PLANS WITH THE FUTURE INFORMATION AND
 INFORMATION TO DETERMINE WHETHER OR NOT THE ADDITIONAL
 SERVICE AS SHOWN MAY BE GRANTED. AT THIS TIME THIS IS
 NOT PERMITTED AS SHOWN ON PLANS AND RISER.
 230.2, 230.70, 220, ETC.
  
 9) NOTE: PLEASE VERIFY IF A CT WILL BE ON RISER FOR THE
 LINE SIDE OF THE 800A MDP.
 FBC 106.3.5.1.2 (FPL REQUIRED?)
  
 10) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM NOTES
 *STRUCTURAL STEEL*WHICH IS OK AND REQUIRED IF PRESENT
 PER 250.50 HOWEVER PLEASE CLARIFY IF THIS IS MEANT TO
 BE THE *FOOTER STEEL* ?
  
 11) NOTE: PLEASE KNOW IF THERE IS ANY FIRE SPRINKLER OR
 FIRE ALARM PLANS WHICH MAY BE REQUIRED UNDER A SEPARATE
 PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE
 MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND
 .3(4).
 PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING
 REQUIRED INFORMATION.
  
 12) NOTE: PLEASE SUBMIT/INDICATE ALL OF THE REQUIRED
 AIC RATINGS FOR SERVICE EQUIPMENT/MAINS AND BRANCH
 BREAKERS.
 110.9.
 FBC 106.1.2, 106.3.5.1.2
  
 13) NOTE: PLEASE SUBMIT WIND LOAD ENGINEERING FOR SITE
 LIGHT POLES.PLEASE KNOW THESE WILL BE REVIEWED BY
 BUILDING REVIEWER AND WILL BE REQUIRED TO MEET THE FBC
 140MPH MIN FOR 3-SEC GUST, 120 SUSTAINED OR ABOVE. FBC
 106.1.2
  
  
  
 *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES
 REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH
 ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENT SON
 THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2008-05-15 Cont ID  
Sent By rchokshi Date 2008-05-15 Time 14:42 Rev Time 0.00
Received By rchokshi Date 2008-05-15 Time 14:36 Sent To B
Notes
2008-05-15 14:41:56PASSED, WITH FOLLOWING PROVISO:
 PLEASE MAKE SUREYOU CORRECT ITEM #1 & ITEM#3 OF
 MOCK-ROOS FOLLOWING LETTER
 RASIK CHOKSHI 805-6723
  
 MARTIN PILOTE, P.E.
 GLOBE ENGINEERING, INC.
 N. LAUDERDALE, FL
  
 HI MARTIN:
  
 THE FOLLOWING LETTER IS FROM OUR CONSULTANT MOCK-ROOS.
 THEY MADE SOME MINOR COMMENTS ON YOUR WATER QUALITY
 CALCULATIONS.THEREFORE, WE ASK YOU TO INCORPORATE
 THEIR ITEM #1 & ITEM # 3 STATED IN MOCK ROOS'S
 FOLLOWING LETTER FOR YOUR WATER CALCULATION PACKAGE AND
 YOUR DRAWINGS. HOWEVER, WE HAVE PROVISIONALLY APPROVED
 YOUR PLANS THAT YOU WILL CORRECT THE STORM WATER
 CALCULATIONS AND DRAWINGS SUGGESTED BY MOCK-ROOS AS
 SOON AS POSSIBLE.
 THANKS,
  
 RASIK
  
 MAY 6, 2008
 MR. EMERY FABIAN
 CITY OF WEST PALM BEACH
 ENGINEERING PROJECT COORDINATOR
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH, FL 33407
 REF. NO. W7700.16
 SUBJECT: FOREST POINT DRAINAGE REVIEW
 DEAR EMERY:
 WE HAVE COMPLETED OUR REVIEW OF THE PLANS AND
 CALCULATIONS PROVIDED FOR THE ABOVE REFERENCED
 PROJECT. OUR OBSERVATIONS ARE AS FOLLOWS:
 1. THE PROPOSED EXFILTRATION TRENCH DETAIL SPECIFIES
 ONLY 12 INCHES OF BACKFILL OVER THE TRENCH, RATHER
 THAN THE 18 INCHES THAT IS SPECIFIED BY THE SFWMD
 TYPICAL EXFILTRATION TRENCH DETAIL.
 2. NO GEOTECHNICAL REPORT WAS PROVIDED TO SUBSTANTIATE
 THE HYDRAULIC CONDUCTIVITY (K VALUE) OR THE
 GROUND WATER TABLE LEVEL. HOWEVER, THE K VALUE APPEARS
 TO BE CONSERVATIVE.
 3. THE CALCULATIONS INDICATE THAT THE PROPOSED SITE
 PROVIDES STORAGE FOR UP TO THE 10-YEAR/1-DAY
 RAINFALL EVENT. HOWEVER, THIS CALCULATION IS BASED ON
 AN EFFECTIVE HEAD VALUE OF 10.2? (INLET GRATE
 ELEVATION LESS THE GROUND WATER ELEVATION). IT IS MORE
 CONVENTIONALLY ACCEPTED THAT THIS VALUE
 SHOULD BE THE INLET GRATE ELEVATION LESS THE BOTTOM OF
 THE TRENCH, 16.25? ? 9.75 = 6.5?. USING THE
 LOWER VALUE, THE PROPOSED VOLUME OF THE TRENCH IS
 SUFFICIENT FOR THE 5-YEAR/1-HOUR, WHICH IS THE
 SFWMD CRITERION FOR PARKING AREAS, AND IT IS ALSO
 ENOUGH STORAGE VOLUME TO PROVIDE FOR THE
 RUNOFF FROM THE 5-YEAR/1-DAY; HOWEVER, IT IS NOT ENOUGH
 FOR THE 10-YEAR/1-DAY EVENT RUNOFF. ANY
 RUNOFF IN EXCESS OF THE 5-YEAR/1-DAY WILL LEAVE THE
 SITE. THE PLANS DO NOT INDICATE THE OFF-SITE FLOW
 PATTERN AND IT IS UNKNOWN IF THE DISCHARGE FLOWS TO THE
 CITY?S SYSTEM OR THAT OF FDOT.
 ALL THINGS CONSIDERED, THE PROPOSED DRAINAGE MEETS
 SFWMD WATER QUALITY CRITERIA, PROVIDES THE
 MINIMUM LEVEL OF PARKING PROTECTION AND WILL BE AN
 IMPROVEMENT OVER THE EXISTING CONDITIONS. WE
 RECOMMEND THAT THE CITY CONTINUE TO PROCESS THE
 PROPOSED SITE APPLICATION.
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT 683-3113,
 EXTENSION 231.
 SINCERELY,
 MOCK, ROOS & ASSOCIATES, INC.
 ALAN D. WERTEPNY, P.E.
 AC:JEH SENIOR PROJECT MANAGER

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2008-04-04 Cont ID  
Sent By rchokshi Date 2008-04-04 Time 14:32 Rev Time 0.00
Received By rchokshi Date 2008-04-04 Time 14:32 Sent To  
Notes
2008-04-04 14:32:00*****FAILED******
  
 1. PLEASE PROVIDE A COPYOF GEO-TECH REPORT AND A
 LATESTEST COPY OF STORM STORM WATER QUALITY
 CALCULATIONSTOMR. BRAMLEY100045TH STREET
 ENGINEERINGFOR THEIR REVIEW.STORM WATER QUALITY
 CALS MUST BE APPROVED FROM 45TH STREET BEFORE WE ISSUE
 PERMIT.
  
 2. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET ( EMERY FABIAN ), UTILITY DEPT BEFORE WE
 APPROVE.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-02-25 Cont ID  
Sent By rchokshi Date 2008-02-25 Time 15:39 Rev Time 0.00
Received By rchokshi Date 2008-02-25 Time 15:35 Sent To  
Notes
2008-02-25 15:39:13****FAILED*****
  
 PLEASE RESPOND REV 2, 10/19/07 COMMENTS TO EXPEDITE
 PERMIT PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-10-19 Cont ID  
Sent By rchokshi Date 2007-10-19 Time 14:03 Rev Time 0.00
Received By rchokshi Date 2007-10-19 Time 13:36 Sent To  
Notes
2007-10-19 14:03:02***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. FIRST FLOOR ELEVATION=18', PLEASE SHOW IN YOUR WATER
 QUALITY CALS. THAT YOU CONSIDEREDCENTER LINE OF ROAD
 (CROWN OF THE ROAD), FLOOD ZONE AREA, & 5,10, 25, 100
 YEAR FLOOD CRITERIATO DETERMINE THE FIRST FLOOR
 ELEVATION. FLOOR ELEVATION SHUOLD BE HIGHER THAN CROWN
 OF THE ROAD BY 1', PLEASE SHOW ALL THESE IN CALS &
 DRAWINGS.
 3. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 4. ALSO PLEASE SHOW ALL STORM WATER CATCH BASINS
 NEAREST AROUND YOUR SITE.
 5. PLEASE PROVIDE A COPY OF NPBID PERMIT, OR SFWMD
 PERMIT OR ENVOROMENTAL RESOURCE PERMIT , A COPY OF
 GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM
 WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH
 STREET. STORM WATER QUALITY CALS MUST BE APPROVED FROM
 45TH STREET BEFORE WE ISSUE PERMIT.
 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By rchokshi Date 2007-07-12 Time 11:31 Rev Time 0.00
Received By rchokshi Date 2007-07-12 Time 11:19 Sent To  
Notes
2007-07-12 11:31:26***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER ,
 ITS ENCLOSURE & THEIR DETAILS PER CITY OF WPB, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 PLEASE SHOW IN YOUR STORM WATER QUALITY CALS.
 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION
 TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS
 WITH 100% FILL OF STORM WATER ELEVATION IF YOU HAVE IT?
 PLEASE TELL US WHERE THE STORM WATER GOES IN CITY CANAL
 OR SFWMD CANAL AFTER CONTROL STRUCTURE?
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE.
 7. PLEASE PROVIDE A COPY OF NPBID PERMIT, OR SFWMD
 PERMIT OR ENVOROMENTAL RESOURCE PERMIT , A COPY OF
 GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM
 WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH
 STREET.
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS
 IFTHOSE WERE APPROVED AT 45TH STREET .
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-24 Cont ID  
Sent By mwennerg Date 2008-04-24 Time 11:00 Rev Time 0.00
Received By mwennerg Date 2008-04-24 Time 10:59 Sent To  
Notes
2008-04-24 11:01:36STAMPED, SIGNED AND DATED SHEET A-1

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-03-18 Cont ID  
Sent By mawillia Date 2008-03-18 Time 14:24 Rev Time 0.00
Received By mawillia Date 2008-03-18 Time 13:16 Sent To  
Notes
2008-03-18 14:24:07*****DENIED*****
  
 THE FOLLOWINGS COMMENTS (NOT MARKED OK) TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.OK
  
 2.OK
  
 3.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY.
 AS PER WEST PALM BEACH CODE, THE ADDRESS NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.ADD TO PROJECT INFORMATION UNDER APPLICABLE
 CODES (COVER & TITLE SHEET)
  
 5.CONSTRUCTION, ALTERATION, AND DEMOLITION SHALL
 COMPLY WITH NFPA 241.ADD TO PROJECT INFORMATION UNDER
 APPLICABLE CODES (COVER & TITLE SHEET)
  
 6.OK
  
 7.MORE INFORMATION WILL BE REQUIRED TO ADDRESS
 CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF
 THIS SCOPE OF WORK.
  
 8.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATIFIY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 MIKE WENNERGREN,ASSISTANT FIRE MARSHAL
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 FIRE PLAN REVIEW
 FIRE PREVENTION 561-804-4756
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 13:58 Sent To  
Notes
2007-11-02 14:02:43**DENIED***
  
 TAKEN DIRECTLY FROM FIRST REVIEW:
 1) BOUNDARY AND CIVIL DRAWINGS INDICATE NORTH DIXIE
 HIGHWAY. PLEASE MAKE CORRECTION TO REFLECT SOUTH DIXIE
 HIGHWAY.
  
 2) IT APPEARS THAT BAY-2 ONLY HAS ONE (1) EXIT. PLEASE
 VERIFY, AND IF SO DOES SPACE MEET REQUIREMENTS FOR
 SINGLE EXIT?
  
 3) ADDRESS IS REQUIRED ON BUILDING THAT MEETS THE
 STANDARDS FOR THE CITY OF WEST PALM BEACH FOR
 COMMERCIAL BUILDINGS. CITY CODE SEC. 78.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 6) SHEET SP-1 ILLUSTRATES A RESTAURANT. MORE
 INFORMATION WOULD BE REQUIRED SUCH AS PROPOSED
 HOOD/SUPPRESSION EQUIPMENT, SEATING LAY OUT, OCCUPANT
 LOAD ETC.
  
 7) MORE INFORMATION WILL BE REQUIRED TO ADDRESS
 CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF
 THIS SCOPE OF WORK.
  
 8) 2A-10B,C RATED FIRE EXTINGUISHERS REQUIRED TO MEET
 MINIMUM 75' TRAVEL DISTANCE REQUIREMENT.
  
 IT WOULD BE HELPFUL TO INCLUDE A RESPONSE LETTER
 INDICATING HOW AND WHERE ON PLANS COMMENTS HAVE BEEN
 ADDRESSED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By mwennerg Date 2007-07-31 Time 15:42 Rev Time 0.00
Received By mwennerg Date 2007-07-31 Time 15:42 Sent To  
Notes
2007-07-31 15:55:22***DENIED***
  
 1) BOUNDARY AND CIVIL DRAWINGS INDICATE NORTH DIXIE
 HIGHWAY. PLEASE MAKE CORRECTION TO REFLECT SOUTH DIXIE
 HIGHWAY.
  
 2) IT APPEARS THAT BAY-2 ONLY HAS ONE (1) EXIT. PLEASE
 VERIFY, AND IF SO DOES SPACE MEET REQUIREMENTS FOR
 SINGLE EXIT?
  
 3) ADDRESS IS REQUIRED ON BUILDING THAT MEETS THE
 STANDARDS FOR THE CITY OF WEST PALM BEACH FOR
 COMMERCIAL BUILDINGS. CITY CODE SEC. 78.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 6) SHEET SP-1 ILLUSTRATES A RESTAURANT. MORE
 INFORMATION WOULD BE REQUIRED SUCH AS PROPOSED
 HOOD/SUPPRESSION EQUIPMENT, SEATING LAY OUT, OCCUPANT
 LOAD ETC.
  
 7) MORE INFORMATION WILL BE REQUIRED TO ADDRESS
 CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF
 THIS SCOPE OF WORK.
  
 8) 2A-10B,C RATED FIRE EXTINGUISHERS REQUIRED TO MEET
 MINIMUM 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 09:51 Sent To ENG
Notes
2008-04-29 09:52:48TO "RCHOKSHI" DESK/RESUB--PLANS ONLY NEED ENG PER
 "LMARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 09:51 Sent To  
Notes
2008-04-03 09:51:25TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 08:35 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 08:35 Sent To  
Notes
2008-02-01 08:38:41TO "COMM" BD#29/PLANS ON RACK--LARGE FOLDED PLANS AND
 PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 11:32 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 11:32 Sent To  
Notes
2007-10-02 14:11:52TO "COMM" BD#37
2007-09-11 11:32:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By mwennerg Date 2007-07-31 Time 15:57 Rev Time 0.00
Received By mwennerg Date 2007-06-19 Time 09:22 Sent To  
Notes
2007-07-02 08:31:56TO "COMM" BD#54
2007-06-19 09:22:47WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-23 Cont ID  
Sent By rregueir Date 2008-04-23 Time 17:14 Rev Time 0.00
Received By rregueir Date 2008-04-23 Time 16:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-02-26 Cont ID  
Sent By rregueir Date 2008-02-26 Time 17:48 Rev Time 0.00
Received By rregueir Date 2008-02-26 Time 15:05 Sent To  
Notes
2008-02-26 17:47:44REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 COMMENTS 1 AND 2: ASSUMPTIONS SHALL BE MADE AND
 APPENDED TO THE ENERGY CALCULATIONS IN ACCORDANCE WITH
 FBC 13-101.1.6. ASSUMPTIONS REGARDING OCCUPANT LOAD AND
 VENTILATION REQUIREMENTS NEED TO BE INCLUDED, SINCE
 THAT INFORMATION IS REQUIRED TO PERFORM COOLING LOAD
 CALCULATIONS IN ACCORDANCE WITH FBC 13-407.1.ABC.1.
 ASSUMPTIONS REGARDING THE SIZE OF THE EQUIPMENT
 INCLUDED IN THE ENERGY CALCULATIONS SHALL BE BASED ON
 THESE CALCULATIONS. MAKE SURE ALL ASSUMPTIONS AND
 COOLING LOAD CALCULATIONS ARE APPENDED TO THE ENERGY
 CALCULATIONS IN ACCORDANCE WITH THESE SECTIONS.
  
 3. PG A-1 IS STILL CALLING FOR R-30 BATTS ABOVE A GRID
 CEILING WHILE A-2 CALLS FOR SPRAY FOAM INSULATION ON
 UNDERSIDE OF DECK. ADDITIONALLY, ON PAGES A-2 AND A-5
 THE PLANS CALL FOR R-75 INSULATION. PLEASE COORDINATE
 PLANS AND SHOW WHICH METHOD IS TO BE USED.
  
 4. PLEASE PROVIDE THE COMPONENTS OF THE EXTERIOR BLOCK
 WALL ASSEMBLY WITH THEIR RESPECTIVE R-VALUES IN ORDER
 TO COME TO A TOTAL OF R-12.5. FBC 13-403.2.AB.
  
 5. OK
  
 6. THE ?PRODUCT APPROVAL? FOR THE A/C STAND INCLUDED IN
 THE BINDER ONLY HAS A COPY OF THE SEARCH SCREEN FROM
 THE DCA WEBSITE STAMPED AND REVIEWED BY THE DESIGNER. A
 COMPLETE PRODUCT APPROVAL WITH DETAILED INSTALLATION
 INSTRUCTIONS SHALL BE PROVIDED AND THE ACTUAL PRODUCT
 APPROVAL SHALL BE APPROVED IN WRITING BY THE DESIGNER
 OF RECORD IN ACCORDANCE WITH FBC 106.4.
  
 7. OK
  
 8. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-03 Cont ID  
Sent By rregueir Date 2007-11-03 Time 15:48 Rev Time 0.00
Received By rregueir Date 2007-11-03 Time 15:37 Sent To  
Notes
2007-11-03 15:47:59REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 COMMENTS 1 THROUGH 8: NONE OF THE PREVIOUS MECHANICAL
 REVIEW COMMENTS WERE ADDRESSED EITHER IN WRITING OR IN
 THE SUPPORTING DOCUMENTATION/PLANS. SEE ATTACHED COPY
 OF PREVIOUS REVIEW COMMENTS AND ADDRESS EACH OF THEM
 ACCORDINGLY PRIOR TO RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By rregueir Date 2007-07-17 Time 11:23 Rev Time 0.00
Received By rregueir Date 2007-07-16 Time 15:29 Sent To  
Notes
2007-07-17 11:23:30--------------DENIED---------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO INFORMATION WAS PROVIDED REGARDING VENTILATION
 REQUIREMENTS. PLEASE PROVIDE OCCUPANCY CLASSIFICATION,
 OCCUPANT LOAD AND OUTDOOR AIR CALCULATIONS BASED ON
 FBC,M 403.3.
  
 2. NO INFORMATION WAS INCLUDED IN ENERGY CALCULATIONS
 FOR AIR CONDITIONING OR OTHER FEATURES OF THE SPACE.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED. FBC 13-101.1.6
  
 3. PG A-1: NOTE #1 INDICATES R-30 INSULATION IS TO BE
 PROVIDED LATER ABOVE A FUTURE DROP CEILING. ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE PANELS PER FBC 13-404.1.ABC.1.
  
 4. PG A-1: NOTE #3 INDICATES R-5 INSULATION ON EXTERIOR
 MASONRY WALLS, BUT ENERGY CALCULATIONS SHOW R-12.5.
 PLEASE COORDINATE PLANS WITH INFORMATION USED IN THE
 INPUT DATA REPORT. FBC 13-403.2.AB
  
 5. PLEASE INCLUDE EXTERIOR DOOR INFORMAION ON ENERGY
 CALCULATIONS/ INPUT DATA REPORT. FBC 13-403.2.AB
  
 6. PG A-2 SUPPORT DETAIL: PRE-ENGINEERED A/C STANDS ARE
 STRUCTURAL COMPONENTS AS DEFINED IN FAC RULE 9B-72 AND
 AS SUCH ARE SUBJECT TO THE FLORIDA PRODUCT APPROVAL
 SYSTEM. PLEASE PROVIDE NOA WITH INSTALLATION DETAILS.
 ALSO, DRAWING REFERS TO A DETAIL ON PAGE M-2, BUT THERE
 IS NO PG M-2 PROVIDED. PLEASE CLARIFY. FBC 106.1.1
  
 7. M-1: OUTSIDE AIR OPENINGS IN THE EXTERIOR WALLS
 SHALL BE LOCATED A MINIMUM OF 10' FROM ANY HAZARDOUS
 CONTAMINANT SUCH AS STREETS, ALLEYS, PARKING LOTS AND
 LOADING DOCKS PER FBC,M 401.5.1.
  
 8. M-1: WALL LEGEND ON A-1 SHOWS EXTERIOR BLOCK WALLS
 TO BE 1-HOUR RATED. HOW ARE OUTDOOR AIR AND EXHAUST
 OPENINGS TO BE PROTECTED IN ACCORDANCE WITH FBC,M
 401.6?
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-14 Cont ID  
Sent By kstevens Date 2008-03-14 Time 15:57 Rev Time 0.00
Received By kstevens Date 2008-03-14 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 10:08 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 10:08 Sent To  
Notes
2007-11-03 10:33:20DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND
 FLOOR PIPING****
  
 ****FROM PREVIOUS REVIEW. COMMENT NUMBER SHALL BE THE
 SAME TO AVOID CONFUSION:
  
 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED.
 SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE
 FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED
 SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR
 REVIEW.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING
 FOR REVIEW.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE
 TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.--
 THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS
 THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT.
 PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS
 SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2. ****NO
 RESPONSE, NOT ADDRESSED. NOW SHT IR-1 ADDED AND THE
 SAME COMMENT APPLIES.
  
 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER
 WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1. ****NO
 RESPONSE, NOT ADDRESSED.
  
 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE
 BUILDING. 106.3.5.1.1(2).
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER
 TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE
 TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN
 THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA
 BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE
 SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE
 GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1&
 106.1.2.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE SUBMITTED.
 THE SQUARE FOOTAGE BEING DRAINED BY EACH DOWNSPOUT CAN
 NOT BE DETERMINED UNTIL THE HIGH POINT IS ESTABLISHED.
 IT APPEARS THAT THE SQUARE FOOTAGE DRAINING INTO EACH
 DOWNSPOUT WILL BE DIFFERENT BECAUSE OF THE FACT THAT
 THE DOWNSPOUTS ARE NOT EVENLY SPACED THROUGH THE
 GUTTER.
  
 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION
 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. N/A
  
 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON
 THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE
 INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN.
 SHOW ALL DOWNSPOUTS. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. OK
 11. OK
  
 **********NEW COMMENTS**********
  
 1B. SHT P-3 THE RISER DIAGRAM FOR UNIT/BAY-1 NOW
 INDICATES A GREASE INTERCEPTOR. THIS DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 106.1.1. THE GREASE INTERCEPTOR
 IS NOT APPROVED FOR INSIDE THE BUILDING AND SHALL BE
 LOCATED OUTSIDE THE BUILDING. ALSO A NOTE ON THE RISER
 DIAGRAM STATES "TERMINATE AND CAP ABOVE THE CEILING FOR
 FUTURE USE". WILL THERE BE A RESTAURANT ON THE SECOND
 FLOOR? PLEASE CLARIFY.
  
 2B. ALL GREASE INTERCEPTORS SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRE-TREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS,
 (561) 822-2284, E-MAIL [email protected]. THERE FAX
 NUMBER IS (561) 822-2287. A WRITTEN DETERMINATION FROM
 ENVIRONMENTAL COMPLIANCE WILL BE SUBMITTED WITH THE
 PLANS WHEN RESUBMITTING FOR REVIEW OF BLDG PERMIT.
  
 3B. NO VENTING FOR THE FIRST FLOOR IS INDICATED ON THE
 SANITARY RISER DIAGRAMS. PLEASE INDICATE HOW THE TENANT
 BUILD-OUTS WILL BE VENTED. SECTION 901.2.1.
  
 4B. SHT P-3 RISERS 4 & 5 DO NOT REFLECT THE FLOOR PLAN.
 RISER 4 INDICATES AN OFFSET AT THE TOP OF THE STACK
 THAT IS NOT INDICATED ON THE FLOOR PLAN, AND ON RISER 5
 AN OFFSET IS REQUIRED TO REFLECT THE FLOOR PLAN. TO
 CLEAR UP THE CONFUSION INDICATE THE RISER NUMBERS ON
 THE FLOOR PLANS OF THE FIRST AND SECOND FLOORS SHTS P-1
 & P-2. RISERS START OFF RISER 1 ON THE LEFT AND
 CONTINUE TO RISER 5 ON THE RIGHT. PLEASE
 CLARIFY.SECTION 106.1.1.
  
 5B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED. BY NOT ADDRESSING THE
 COMMENTS WITH A WRITTEN RESPONSE, REVIEW TIME TAKES
 LONGER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By kstevens Date 2007-07-16 Time 11:29 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 18:31 Sent To  
Notes
2007-07-16 12:23:34DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND
 FLOOR PIPING****
  
 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED.
 SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE
 FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED
 SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR
 REVIEW.
  
 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING
 FOR REVIEW.
  
 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE
 TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.--
 THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS
 THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT.
 PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS
 SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2.
  
 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER
 WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1.
  
 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE
 BUILDING. 106.3.5.1.1(2).
  
 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER
 TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE
 TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN
 THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA
 BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE
 SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE
 GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1&
 106.1.2.
  
 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION
 106.1.1.
  
 8. SHT A-3 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON
 THE ROOF PLAN. PLEASE CORRELATE. SECTION 106.1.1.--
 NO DOWNSPOUTS ARE INDICATED ON THE ELEVATION. PLEASE
 SHOW THE LOCATION OF EACH DOWNSPOUT. SECTION 106.1.1.
 SHOW THE SIZE OF THE GUTTER AND THE DOWNSPOUTS. TABLES
 1106.6 & 1106.2.
  
 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON
 THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE
 INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN.
 SHOW ALL DOWNSPOUTS. SECTION 106.1.1.
  
 10. SHT P-3 THE SANT RISER TO UNIT #1 SHOWS 2" TO ONE
 LAV, BUT THE FLOOR PLAN SHOWS 3".--RISER TO UNIT
 #3 SHOWS 3" TO LAVS AND 3" TO ONE LAV BUT SHOWS 2" ON
 THE FLOOR PLANS. --RISER TO UNIT #4 SHOWS 2" TO THE
 W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS SHOWN
 ON THE FLOOR PLAN. - 3" IS SHOWN TO TWO LAVS BUT SHOWN
 AS 2" ON THE FLOOR PLAN.--RISER TO UNIT #5 SHOWS 2"
 TO THE W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELAT INFORMATION
 BETWEEN THE FLOOR PLAN AND THE RISER DIAGRAMS.
  
 11. SHT P-3 BAY 1 WATER RISER. PLEASE SHOW ALL PIPE
 SIZES.--BAY 2 WATER RISER IS SHOWN AS 1-1/4"
 METER/BACKFLOW BUT FLOOR PLAN SHOWS 2" METER/BACKFLOW.
 PLEASE CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND
 THE RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-04-10 Cont ID  
Sent By adavila Date 2008-04-10 Time 11:13 Rev Time 0.00
Received By adavila Date 2008-04-09 Time 11:13 Sent To  
Notes
2008-04-10 11:13:41PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO SHEET SP-1 SHALL GOVERN FOR BENCH AND PLANTER
 LAYOUT.
  
 PROVISO SHEET A-1 SHALL GOVERN FOR BENCH
 LAYOUT/ORIENTATION.
  
 A SIGN PERMIT SHALL BE SUBMITTED FOR ALL SIGNS.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-06 Cont ID  
Sent By adavila Date 2008-02-06 Time 15:34 Rev Time 0.00
Received By adavila Date 2008-02-06 Time 08:45 Sent To  
Notes
2008-02-06 15:35:27PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO SHEET SP-1 SHALL GOVERN FOR BENCH AND PLANTER
 LAYOUT.
  
 PROVISO SHEET A-1 SHALL GOVERN FOR BENCH
 LAYOUT/ORIENTATION.
  
 A SIGN PERMIT SHALL BE SUBMITTED FOR ALL SIGNS.
  
2008-02-06 08:45:36IN ZONING FOR REVIEW.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-26 Cont ID  
Sent By adavila Date 2007-09-26 Time 12:26 Rev Time 0.00
Received By adavila Date 2007-09-20 Time 09:11 Sent To  
Notes
2007-09-26 12:27:00PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE LANDSCAPE PLANS SHOW A LARGER NUMBER OF TREES TO
 BE REMOVED THAN THE NUMBER STATED ON THE TREE
 ALTERATION PERMIT APPLICATION.PLEASE SUBMIT TWO (2)
 COPIES OF A REVISED LANDSCAPE PLAN AND TREE SURVEY, AS
 WELL AS A STATEMENT EXPLAINING THE ADDITIONAL TREES TO
 BE REMOVED, TO AMEND YOUR TREE ALTERATION PERMIT
 APPLICATION.PLEASE NOTE THAT APPROVAL OF THE TREE
 ALTERATION PERMIT IS REQUIRED PRIOR TO BUILDING PERMIT
 APPROVAL.
  
 2. SURVEY STILL SHOWS NORTH DIXIE HIGHWAY INSTEAD OF
 SOUTH DIXIE HIGHWAY.PLEASE NOTE THAT ALL COPIES OF
 THE SURVEY SHALL BE SIGNED AND SEALED.IN ADDITION,
 PLEASE NOTE THAT THE STORMWATER PREVENTION PLAN, SHEET
 C2 OF 4, ALSO READS NORTH DIXIE HIGHWAY.
  
 3. STAFF'S COMMENTS AT THE AUGUST 20, 2007 MEETING WERE
 TO COME UP WITH ALTERNATIVES TO ADJUST THE SLABS OF THE
 FUTURE BALCONIES SO THAT THEY MAY BE MORE IN CHARACTER
 WITH THE PROPORTION OF PHASE I.
 A. ONE OF THE SUGGESTIONS MADE BY STAFF WAS TO REDUCE
 THE THICKNESS OF THE FACIA CONCEALING THE SLABS.
 HOWEVER, THE PLANS SUBMITTED ONLY SHOW THE THICKNESS
 REDUCED ON TWO (2) OF THE SLABS.THERE SHOULD BE A
 CONSISTENCY THROUGHOUT THE BUILDING.IF THE THICKNESS
 OF THE THIRD SLAB CAN NOT BE REDUCED DUE TO STRUCTURAL
 PURPOSES, THEN THE REMAINING SLABS SHOULD REMAIN THE
 SAME.
 B. THE SECOND SUGGESTION MADE BY STAFF WAS TO INSTALL
 LIGHTING FIXTURES UNDERNEATH THE SLABS.PLEASE PROVIDE
 DETAILS AND A CROSS-SECTION OF THE LIGHT FIXTURES
 LOCATED UNDERNEATH THE SLABS.AS MENTIONED IN THE
 MEETING, THERE SHOULD BE ENOUGH FACIA DEPTH TO CONCEAL
 THE LIGHTING FIXTURE BELOW THE SLAB AND BEHIND THE BEAM
 SO THAT IT WILL NOT BE VISIBLE.
  
 4. PLEASE NOTE THAT THERE APPEARS TO BE SOME
 DISCREPANCY BETWEEN THE PLANS (I.E. NAME OF SOUTH DIXIE
 HIGHWAY, AND LAYOUT OF THE BENCH AT THE NORTHWEST
 CORNER OF THE SITE).PLEASE ENSURE THAT ALL PLANS SHOW
 THE SAME CONDITIONS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By adavila Date 2007-06-29 Time 14:04 Rev Time 0.00
Received By adavila Date 2007-06-26 Time 13:11 Sent To  
Notes
2007-06-29 14:06:13PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE COPY OF THE APPROVAL LETTER FROM PALM TRAN
 FOR THE NEW BUS STOP LOCATION.
  
 2. PROPOSED BUS STOP LOCATION SHALL BE SHOWN ON THE
 LANDSCAPE PLAN.
  
 3. PROVIDE A COPY OF FDOT APPROVAL FOR THE REMOVAL OF
 THE EXISTING CURB CUTS ON SOUTH DIXIE HIGHWAY.
  
 4. PROVIDE A COPY OF THE APPROVED PLANS/LETTER FOR THE
 TREES THAT ARE TO BE REMOVED AND/OR RELOCATED.
  
 5. SURVEY AND PLANS SHALL BE CORRECTED TO SHOW SOUTH
 DIXIE HIGHWAY INSTEAD OF NORTH DIXIE HIGHWAY.
  
 6. THE PROPOSED BUILDING SQUARE FOOTAGE ON THE
 PHOTOMETRIC PLAN DOES NOT MATCH THE PROPOSED BUILDING
 SQUARE FOOTAGE ON THE SITE PLAN AND FLOOR PLAN.ALL
 PLANS SHALL SHOW THE SAME DATA.PROVIDE CORRECT
 BUILDING SQUARE FOOTAGE ON THE PHOTOMETRIC PLAN.
  
 7. HANDICAP SYMBOL SHALL BE PAINTED IN WHITE.
  
 8. FLOOR PLAN (SHEET A-1) SHOWS TWO (2) COLUMNS ALONG
 THE SIGHT LINE, WHICH ARE NOT SHOWN ON ANY OF THE OTHER
 PLANS.PLEASE CLARIFY THE PRESENCE OF THE NEW COLUMNS.
 IN THE EVENT THAT THE COLUMNS ARE FOR STRUCTURAL
 SUPPORT PURPOSES, STAFF RECOMMENDS USING ALTERNATIVE
 DESIGN OPTIONS SO THAT THEY MAY NOT TAKE AWAY FROM THE
 VISUAL EMPHASIS AND INTEREST TO THE MAIN ENTRANCE.
  
 9. PLEASE CONTACT THE PLANNING AND ZONING DEPARTMENT TO
 DISCUSS DESIGN OPTIONS FOR THE BALCONY SLABS AND
 PARAPET.
  
 10.ALL SIGNS SHALL BE APPROVED ON A SEPARATE
 PERMIT.
  
 11.PLEASE PROVIDE ONE OF THE FOLLOWING.
 A. AN IRRIGATION PLAN TO BE INCLUDED WITH THIS
 PERMIT APPLICATION; OR
 B. AN IRRIGATION PLAN UNDER A SEPARATE
 PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.