Plan Review Details - Permit 07060501
| Plan Review Stops For Permit 07060501 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-05-23 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-05-23 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-05-23 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-04-23 |
Time |
13:52 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2008-04-23 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2008-04-23 13:56:51 | PLANS APPEAR TO BE CODE COMPLIANT, ONCE THE COUNTY | | | IMPACT FEES ARE PAID AND THE BALANCE OF FEES TO THE | | | CITY ($6,663.00) I'LL BE ABLE TO PASS AND ISSUE THIS | | | PERMIT. | | | NOTE THE ROOFING PERMIT WILL REQUIRE SEPERATE PERMIT, | | | REVIEW, AND ASSOCIATEDFEES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-03-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-03-19 |
Time |
10:23 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-03-19 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2008-03-19 11:29:56 | SHELL 7204 S DIXIE HWY/ 07060501 | | | BUILDING PLAN REVIEW | | | PERMIT: 07060501 | | | ADD: 7204 S DIXIE HWY | | | CONT: BENCHMARK CUSTOM BUILDERS | | | TEL: (954)802-0723 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) ADDITIONAL INFORMATION REQUIRED. THE PERMIT | | | APPLICATION INDICATES A SHELL BUILDING WHILE THE PLANS | | | INDICATE THIS TO BE A PHASED, PHASE I A COMMERCIAL | | | FIRST FLOOR AND A PHASE II RESIDENTIAL | | | SECOND FLOOR, ARE BOTH PHASES TO BE CONSIDERED WORK | | | UNDER THIS PERMIT? | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. NOTE PLANS DO INDICATE 2004 FBC BUT NOT THE | | | 2006 AMENDMENTS, PLEASE CORRECT. | | | | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. COMPLIED. | | | | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. PARTIALLY COMPLIED. PLANS INDICATE A TYPE | | | III BUILDING BUT NO DESIGNATION AS A OR B. NOTE: TABLE | | | 503WILL ALLOW THIS BUILDING TO BE BUILT AS A TYPE V-B | | | EVEN FOR PHASE II, SEE SECTION 302.3.2 AND TABLE | | | 302.3.2. IF TO BE DESIGNED AS EITHER A TYPE III A OR B | | | SEE TABLE 602 THAT WILL REQUIRE A 2HR RATED WALL FOR | | | THE SOUTH WALL LOCATED 5.5' FROM THE PROPERTY LINE . | | | PLEASE PROVIDE WHAT TYPE OF CONSTRUCTION THIS STRUCTURE | | | WILL BE DESIGNED TOO. | | | | | | D) THE OCCUPANT LOAD, SEE 1004. NOTE WORST CASE | | | SCENARIO WILL BE TAKEN 5863 SQ /30= 196 OCCUPANT LOAD | | | | | | E-K) COMPLIED. | | | | | | 4) SHEET S-1 NOTE# 19 INDICATES THERE SHALL BE A | | | SPECIAL INSPECTOR FOR THE REINFORCED MASONARY SHALL BE | | | PROVIDED. ALSO, PLEASE ARRANGE WITH HAROLD PISKURA | | | (INSPECTION SERVICES MANAGER - TEL: 561 805 6711), A | | | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, | | | CONTRACTOR AND ENGINEER. | | | | | | 5)COMPLIED. | | | | | | 6) PROVISO 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY | | | THIS CODE SHALL BE PERMORMED IN A MANNER | | | SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS | | | SUCH ACTIVITY IS PERMITTED TO AFFECT | | | SAID PROPERTY PURSUANT TO A CONSENT BY | | | THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE | | | APPLICABLE PROPERTY OWNER.THIS INCLUDES | | | BUT IS NOT LIMITED TO THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, | | | DEBRIS, AND THE STORAGE OF CONSTRUCTION | | | MATERIALS. NEW CONSTRUCTION ACTIVITY | | | SHALL NOT ADVERSELY IMPACT HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING | | | ADJACENT PROPERTIES, & MAY REQUIRE | | | SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, | | | AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR | | | ITEMS, ON EXISTING PROPERTIES RESULTING | | | IN A DECREASE IN EXCESS OF 800SQ FT OF | | | PERMEABLE LAND AREA ON ANY PARCELL SHALL | | | AS A PERMIT CONDITION, PROVIDE A | | | PROFESSIONALLY PREPARED DRAINAGE PLAN | | | CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 7) PROVISO:109.3.10.1 HURRICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 8)BOTH C1 - C4 HAVE TOTALLY DELETEDTHEJOBSITE | | | LOCATION INTHE TITLE BLOCK. | | | 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A | | | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH | | | MUST: | | | - STATE THE FIRM NAME, ADDRESS ANDTELEPHONE | | | NUMBER | | | - STATE THE FIRM LICENSE NUMBER | | | XX - STATE PROJECT NAME AND LOCATION,IDENTIFICATION | | | - STATE DATE PREPARED | | | - INCLUDE AN ORIGINAL SIGNATURE ANDDATED SEAL- | | | INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE | | | PLANS | | | | | | 9)SEMI-COMPLIED SHEET A-2 INDICATES A MECHANICAL | | | EQUIPMENT STANDBUT THE PRODUCT APPROVALS REQUIRED BY | | | RULE 9B-72 DO NOT CONTAIN THE REPORT OR ASSCIATED | | | TECHNICAL SHEETS. | | | | | | 10) COMPLIED. | | | | | | 11)2ND REQUEST,PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED | | | TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE | | | STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | WWW.FLORIDABUILDING.ORG | | | | | | 12)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT | | | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS | | | ARE AS FOLLOWS: | | | | | | A) STOREFRONT- NO REPORT WAS SUBMITTED | | | | | | B) OUTSWING DOOR & TRANSOM - NO REPORT WAS SUBMITTED | | | | | | C) EXTERIOR METAL CORE DOOR | | | | | | D) PRE-ENGINEERED A/C STANDS- ONLY THE FLORIDA | | | COVERSHEET SUBMITTED, NEEDS THE BACK UP REPORT AND | | | TECNICAL DRAWINGS. | | | | | | E) GLASS BLOCK- REVIEWED OK | | | | | | F) TRUSS ANCHORS OR BUCKETS- NO REPORT SUBMITTED | | | | | | G) ROOFING ASSEMBLIES- NO REPORT SUBMITTED | | | | | | 13) SHEET A-9 DETAIL# 5 INDICATES 2'X8' WOOD JOIST @ | | | 2'-0" O. C. PLANS NOW INDICATE THE BUCKET TYPE BUT THE | | | LENGHT OF THEEMBEDMENT OF THE 3/8" EXSPANSION BOLT IS | | | NOT PROVIDED. | | | 106.1.2* ADITIONAL INFORMATION REQUIRED. | | | | | | 14) 2ND REQUEST, SHEET A-1 STORAGE ROOM# 2THE DOOR ON | | | THE RIGHT SIDE IS MISSING THE REQUIRED 18" SEE : | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT | | | ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN | | | IN FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. | | | | | | 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 16)ARCHITECTURAL BUSINESS SOUTHEAST ARCHITECT | | | SERVICES INC DOES NOT SHOW UP ON THE STATES DBPR | | | WEBSITE USING THE FIRMS NAME NOR LICENSE NUMBER AA-C | | | 001953PLEASE PROVIDE CONFRAMATION OF THE FIRMS BUSINESS | | | LICENSE. 481.219 F.S.CERTIFICATE OF AUTHORIZATION. | | | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN | | | ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | | SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 17) PROVISO: HOLLOW CORE SLAB PLANKS TO SUBMITT SHOP | | | DRAWINGS REVIEWED BY THE DESIGN TEAM WITH APPROVAL | | | STAMP. | | | | | | 18-25) COMPLIED. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-10-24 |
Time |
14:49 |
Rev Time |
8.00 |
| Received By |
jjohnsto |
Date |
2007-10-24 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2007-10-24 14:48:57 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, | | | WEST PALM BEACH, FLORIDA33401 | | | TEL:561-805-6713FAX:561-805-6731 | | | | | | JAMES JOHNSTON, | | | E-MAIL:JJOHNSTON @WPB.ORG | | | BUILDING PLAN EXAMINER II | | | | | | PERMIT NO 07060501 | | | ADDRESS7204 S. DIXIE HIGHWAY | | | PROJECT FOREST POINT 1ST STORY | | | | | | DATE NOVEMBER 5, 2007 | | | | | | BUILDINGPLANREVIEWFLORIDA BUILDING CODES | | | 2004 | | | | | | THE FOLOWING COMMENTS ADDRESS THE PREVIOUS | | | CRITQUE COMPLETED ON 7/29/07 BY JIM WHITMER | | | | | | 1. COMPLIED | | | | | | 2. COMPLIED | | | | | | 3. COMPLIED | | | | | | 4. | | | NOT IN COMPLIANCE2ND REQUEST | | | | | | FBCBUILDING 104.3 EXAMINATION | | | OF DOCUMENTS | | | 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL | | | EXAMINE OR | | | CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND | | | THE | | | ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS, | | | SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND | | | SHALL | | | ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE | | | CONSTRUCTION | | | INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE | | | REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER | | | PERTINENT | | | LAWS OR ORDINANCES. | | | | | | COMMENT- PLEASE FURNISH THE THE FOLLOWING | | | INFORMATION | | | | | | ON THE COVER SHEET | | | PROJECT INFORMATION | | | FBC2004 BUILDING W/ 2005 AND 6 REVISIONS | | | FBC2004 ACCESSIBILITYCHAPTER 11 | | | TYPE OF CONSTRUCTION | | | SPRINKLED / UN-SPRINKLED | | | BASIC WIND SPEED - MPH | | | WIND EXPOSURE | | | WIND IMPORTANCE FACTOR & BUILDING CATEGORY INTERNAL | | | PRESSURE COEFFICIENT | | | TYPE OF OCCUPANCY | | | OCCUPANT LOAD-GROSS - NET | | | 5 | | | NOT IN COMPLIANCE2ND REQUEST | | | | | | FBC BUILDING1802.6 SOIL REPORTS. | | | THE SOIL CLASSIFICATION AND DESIGN LOAD-BEARING | | | CAPACITY | | | SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT. | | | WHERE REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN | | | REPORT | | | OF THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES, | | | | | | BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: | | | | | | 1.A PLOT SHOWING THE LOCATION OF TEST BORINGS | | | AND/OR | | | EXCAVATIONS. | | | 2. A COMPLETE RECORD OF THE SOIL SAMPLES. | | | 3. A RECORD OF THE SOIL PROFILE. | | | 4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. 5. | | | RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN | | | CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING | | | CAPACITY | | | OF NATURAL OR COMPACTED SOIL; PROVISIONS TO | | | MITIGATE | | | THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF | | | THE EFFECTS | | | OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT AND | | | VARYING SOIL | | | STRENGTH; AND THE EFFECTS OF ADJACENT LOADS. 6. | | | EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. 7. PILE | | | AND PIER FOUNDATION INFORMATION IN ACCORDANCE | | | WITH SECTION 1808.2.2 . | | | 8. SPECIAL DESIGN AND CONSTRUCTION PROVISIONS FOR | | | FOOTINGS | | | OR FOUNDATIONS FOUNDED ON EXPANSIVE SOILS, AS | | | NECESSARY. | | | | | | COMMENT-PLEASE SUBMIT THE SOIL TEST REPORT FOR | | | THIS | | | PROJECT BY QUESTENGINEERING AS NOTED ON THE | | | STRUCTURAL | | | SHEETS-1. | | | | | | | | | 6 | | | COMPLIED | | | | | | | | | 7 | | | COMPLIED | | | | | | | | | 8 | | | COMPLIED | | | | | | | | | 9 | | | COMPLIED | | | | | | 10 | | | COMPLIED | | | | | | 11 | | | NOT IN COMPLIANCE2ND REQUEST | | | | | | PRODUCT APPROVALS REQUIRED | | | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 | | | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS | | | SUBMIT TWO COPIES OF EACH APPROVAL | | | ( 3 COPIES IF A THRESHOLD BUILDING ) WITH FLORIDA | | | PRODUCT | | | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S | | | SIGNATURE AS APPLICABLE, STATING | | | ?TO THE BEST OF THEIR KNOWLEDGE THE PRODUCT APPROVAL | | | COMPLIES WITH THE PLANS AND SPECIFICATIONS. | | | | | | COMMENT-IN ADDITION TO THE MIAMI-DADE NOA | | | PLEASE PROVIDE FLORIDA PRODUCT APPROVALS FOR ALL | | | PRODUCTS | | | REQUIRED TO BE SUBMITTED.SEE INFORMATION SUBMITTED | | | ABOVE. | | | THE DELTA DOOR COMPANY DOES NOT HAVE FLORIDA PRODUCT | | | APPROVAL. | | | | | | 11A | | | FLORIDA ADMINISTRATIVE CODE9B-72.030 EXCEPTIONS. | | | LOCAL PRODUCT APPROVAL GENERALLY | | | PRODUCTS LISTED IN RULE 9B-72.005, F.A.C., SHALL BE | | | APPROVED | | | ACCORDING TO THE PROVISIONS OF THIS RULE. | | | (1) PRESCRIPTIVE.PRODUCTS THAT HAVE PRESCRIPTIVE | | | SPECIFICATION STANDARDS AND ARE MANUFACTURED UNDER | | | QUALITY ASSURANCE PROCEDURES AS SPECIFIED IN THE CODE | | | WILL BE DEEMED APPROVED. | | | SUCH PRODUCTS SHALL INCLUDE BUT NOT BE LIMITED TO THE | | | FOLLOWING: | | | (A) STRUCTURAL COMPONENTS COVERED BY UNITED STATES | | | DEPARTMENT OF COMMERCE PRODUCT STANDARDS; | | | (B) STRUCTURAL COMPONENTS COMPRISED OF PRODUCTS THAT | | | ARE ASSEMBLED OR PLACED IN THE FIELD AND ARE SUBJECT | | | TO | | | | | | STANDARDIZED FIELD TESTING PROCEDURES CONTAINED WITHIN | | | | | | NATIONALLY RECOGNIZED STANDARDS ADOPTED WITHIN THE | | | CODE | | | | | | MAY DEMONSTRATE COMPLIANCE BY A BATCH TICKET OR BILL | | | OF | | | LADING MADE AVAILABLE AT THE SITE OF ASSEMBLY OR | | | PLACEMENT; | | | (C) CUSTOM (ONE OF A KIND) PRE-ENGINEERED BUILDINGS. | | | (2) PERFORMANCE. PRODUCTS, METHODS AND SYSTEMS OF | | | CONSTRUCTION SPECIFICALLY ADDRESSED IN THE CODE | | | THROUGH | | | | | | PERFORMANCE CRITERIA SHALL DEMONSTRATE COMPLIANCE | | | PURSUANT TO RULE 9B-72.070, F.A.C., AND SHALL BE | | | APPROVED | | | PURSUANT TO RULE 9B-72.090, F.A.C. | | | | | | COMMENT-FOR DELTA DOOR | | | | | | | | | 11B | | | FLORIDA ADMINISTRATIVE CODE9B-72.050 | | | PRODUCT APPROVAL BY LOCAL JURISDICTION | | | AND ACCEPTANCE | | | (1) APPROVAL OF A PRODUCT FOR LOCAL USE SHALL BE | | | PERFORMED | | | BY THE BUILDING CODE OFFICIAL OR HIS/HER DESIGNEE BY | | | VERIFYING THAT THE PRODUCT COMPLIES WITH THE CODE IN | | | ACCORDANCE WITH RULE 9B-72.040, F.A.C. | | | (A) THE AUTHORITY HAVING JURISDICTION OR BUILDING | | | OFFICIAL | | | SHALL VALIDATE THE METHOD OF COMPLIANCE PURSUANT TO | | | RULE 9B-72.040, F.A.C. | | | (B) UPON ACCEPTANCE OF REQUIRED DOCUMENTATION PURSUANT | | | TO SUBSECTION 9B-72.040(5), F.A.C., THE AUTHORITY | | | HAVING JURISDICTION OR BUILDING OFFICIAL MAY | | | | | | DEEM THE PRODUCT APPROVED FOR USE IN ACCORDANCE WITH | | | ITS APPROVAL AND LIMITATION OF USE. | | | (C) APPROVAL SHALL BE VALID UNTIL SUCH TIME AS THE | | | PRODUCT | | | CHANGES DECREASING THE PRODUCT?S PERFORMANCE, | | | THE STANDARDS OF THE CODE CHANGE, OR THE APPROVAL IS | | | OTHERWISE SUSPENDED OR REVOKED. | | | CHANGES TO THE CODE SHALL NOT BE CONSTRUED AS VOIDING | | | THE APPROVAL OF PRODUCTS PREVIOUSLY INSTALLED IN | | | EXISTING | | | BUILDINGS PROVIDED SUCH PRODUCTS MET BUILDING CODE | | | REQUIREMENTS AT THE TIME THE PRODUCT WAS INSTALLED. (D) | | | MANUFACTURER SHALL NOTIFY THE AUTHORITY HAVING | | | JURISDICTION OR THE BUILDING OFFICIAL WHEN THE QUALITY | | | | | | ASSURANCE REQUIREMENTS OF SUBSECTION 9B-72.040(4), | | | F.A.C., | | | ARE NO LONGER IN PLACE. | | | (2) ACCEPTANCE OF A PRODUCT, MATERIAL OR SYSTEM OF | | | CONSTRUCTION IS SPECIFIC TO A PROJECT AND REQUIRES | | | APPROVAL BY A LOCAL JURISDICTION PURSUANT TO RULE | | | 9B-72.050, F.A.C., OR STATEWIDE APPROVAL BY THE | | | COMMISSION PURSUANT TO RULE 9B-72.090, F.A.C., | | | AND VERIFICATION THAT THE PRODUCT IS BEING USED | | | CONSISTENT WITH THE APPROVED EVALUATION AND | | | LIMITATIONS | | | | | | OF USE ESTABLISHED BY THE APPROVED EVALUATION AS | | | REQUIRED BY THE DESIGN SPECIFICATIONS. | | | | | | COMMENT-USE FLORIDA ADMINISTRATIVE CODES 9B-72.050 | | | AND9B-72.030FOR DELTA DOOR CO. | | | PLEASE FIND THE CITY OF WEST PALM BEACH | | | ?SITE SPECIFIC? ?LOCAL PRODUCT APPROVAL? ATTACHED | | | FORMS. | | | SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL | | | COVER PAGE FOR THE FOLLOWING | | | COMPONENTS THAT ARE APPLICABLE | | | FIXED GLASS | | | MULLION TUBES | | | STORE FRONT GLAZING SYSTEM | | | ALUMINUM OUT -SWING DOORS | | | EXTERIOR HOLLOW METAL DOORS | | | EXTERIOR GLAZED DOORS | | | ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION, | | | UNDERLAYMENT,ROOF TILE,ROOF SYSTEM | | | PREENGINEERED AC STAND | | | GLASS BLOCK | | | TRUSS ANCHORS | | | | | | | | | 12 | | | NOT IN COMPLIANCE2ND REQUEST | | | | | | FBCBUILDING 1609.1.3COMPONENTS & CLADDING ANCHORAGE | | | AGAINST OVERTURNING, UPLIFT AND SLIDING. STRUCTURAL | | | MEMBERS AND SYSTEMS AND COMPONENTS | | | AND CLADDING IN A BUILDING OR STRUCTURE SHALL BE | | | ANCHORED | | | TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING | | | AND | | | TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO | | | THE | | | FOUNDATION. | | | WHERE A PORTION OF THE RESISTANCE TO THESE FORCES IS | | | PROVIDED BY DEAD LOAD, THE DEAD LOAD, INCLUDING THE | | | WEIGHT | | | OF SOILS AND FOUNDATIONS, SHALL BE TAKEN AS THE | | | MINIMUM | | | | | | DEAD LOAD LIKELY TO BE IN PLACE DURING A DESIGN WIND | | | EVENT. | | | | | | COMMENT | | | SEE ITEM 11 | | | | | | | | | | | | | | | FLORIDA ADMINISTRATIVE CODE61G15-23.002 SEAL, | | | SIGNATURE AND DATE SHALL BE AFFIXED. | | | (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND | | | AFFIX | | | HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL | | | BID | | | DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER?S | | | REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR ISSUED | | | BY SAID REGISTRANT AND BEING FILED FOR PUBLIC RECORD. | | | THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED AS | | | PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, | | | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS | | | IMMEDIATELY | | | | | | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. (2) | | | EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED | | | | | | UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE | | | SEALED, | | | SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR | | | NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF | | | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME | | | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, | | | AND THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION | | | NUMBER OF THE ENGINEERING BUSINESS WILL SATISFY THIS | | | REQUIREMENT. | | | | | | COMMENT-CARMAN VERDE AND ASSOCIATE?S LICENSE | | | IS LISTED WITH THE DBPR AS ?DELINQUENT, ACTIVE. | | | | | | PLEASE SUBMIT THE CORRECT SURVEY FOR | | | THIS PROJECT | | | SHEET 1 OF 1 - BOUNDARY AND TOPOGRAPHIC SURVEY SHALL | | | BE-SIGNED, SEALED, PRINTED NAME AND INCLUDE THE | | | COMPANY CERTIFICATE OF AUTHORIZATION. | | | | | | | | | | | | | | | 13 | | | COMPLIED | | | | | | | | | 14 | | | COMPLIED | | | | | | 15 | | | NOTED FOR COMPLIANCE | | | THE FOLLOWING COMMENTS ARE THE RESULTS OF ADDITIONAL | | | INFORMATION WHICH WAS REQUESTED | | | BY THE PREVIOUS PLAN REVIEWER | | | | | | 16 | | | ARCHITECTURAL | | | FLORIDA ADMINISTRATIVE CODE61G1-16.002 | | | ARCHITECTDESCRIPTION OF SEAL | | | (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE | | | ARCHITECT | | | OR INTERIOR DESIGNER AND THE REGISTRATION NUMBER; THE | | | SEAL OF THE ARCHITECT SHALL BE CIRCULAR, AND THE SEAL | | | OF | | | THE INTERIOR DESIGNER SHALL BE HEXAGONAL. | | | BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL SEAL, | | | APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR LINES | | | BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE | | | WORDS | | | ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS ? | | | REGISTERED ARCHITECT? OR ?LICENSED INTERIOR DESIGNER,? | | | | | | WHICHEVER IS APPLICABLE. | | | (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT | | | AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH | | | CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN | | | REGISTRATION NUMBERS, IN SUCH A MANNER: | | | | | | COMMENT-SOUTHEAST ARCHITECT SERVICES, INC. PLEASE | | | VERIFY YOUR SEAL IS IN COMPLIANCE WITH RULE | | | 61G1-16.002 | | | | | | | | | 17 | | | FBC BUILDING 104.3 EXAMINATION OF DOCUMENTS 104.3.1 | | | PLAN REVIEW. THE BUILDING OFFICIAL SHALL EXAMINE OR | | | CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND | | | THE ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS, | | | SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND | | | SHALL | | | ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE | | | CONSTRUCTION | | | INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE | | | REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER | | | PERTINENT | | | LAWS OR ORDINANCES. | | | | | | COMMENT- PLEASE FURNISH THE HOLLOW CORE SLAB | | | ENGINEERING DOCUMENTS. | | | HAVE THE ARCHITECT OF RECORD NOTE ACCEPTANCE OF THIS | | | PRODUCT | | | | | | | | | | | | CHAPTER11 ACCESSIBILITY | | | | | | 18 | | | FBC BUILDING 11-4.3ACCESSIBLE ROUTE | | | (1)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY | | | OF THE SITE SHALL BE PROVIDED FROM PUBLIC | | | TRANSPORTATION | | | STOPS, ACCESSIBLE PARKING, AND ACCESSIBLE PASSENGER | | | LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE | | | ACCESSIBLE BUILDING ENTRANCE THEY SERVE. | | | THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM EXTENT | | | FEASIBLE, | | | COINCIDE WITH THE ROUTE FOR THE GENERAL PUBLIC. (2) AT | | | LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE | | | BUILDINGS, FACILITIES, ELEMENTS, AND SPACES THAT ARE ON | | | THE | | | SAME SITE. | | | (3)AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT | | | ACCESSIBLE BUILDINGS OR FACILITY ENTRANCES WITH ALL | | | ACCESSIBLE SPACES AND ELEMENTS AND WITH ALL ACCESSIBLE | | | | | | DWELLING UNITS WITHIN THE BUILDING OR FACILITY. (4) AND | | | ACCESSIBLE ROUTE SHALL CONNECT AT LEAST ONE ACCESSIBLE | | | ENTRANCE OF EACH ACCESSIBLE DWELLING UNIT. | | | | | | COMMENTDEFINETHE TRANSITION FROM THE BOUNDARY | | | WALKWAY ACROSS THE DRIVEWAY ENTRANCES TO THE PUBLIC | | | SIDEWALK WITHOUT A CHANGE IN ELEVATION | | | | | | | | | 18 B | | | FBC BUILDING 11-4.1.3 ACCESSIBLE BUILDINGS: | | | NEW CONSTRUCTION | | | (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH | | | SECTION | | | 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR FACILITY | | | ENTRANCES | | | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE | | | BUILDING | | | OR FACILITY. | | | | | | COMMENT THE SIDEWALK ALONG THE FRONT OF THE BUILDING | | | DOES NOT CONTINUE TO THE SIDEWALK LOCATED AT THE | | | NORTH. | | | | | | SHOW ALL CONNECTIONS FOR VERIFICATION OF ELEVATION. | | | | | | 19 | | | FBC BUILDING 1816.1 TERMITE PROTECTION. | | | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED | | | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, | | | BAITING | | | SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR OTHER | | | APPROVED | | | METHODS OF TERMITE PROTECTION LABELED FOR USE AS A | | | PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. | | | | | | COMMENTFURNISH THIS INFORMATION ON SHEET S-1 | | | OR WHERE APPLICABLE | | | | | | | | | 20 | | | FBC1905.1.1 CONCRETE STRENGTH. | | | CONCRETE SHALL BE PROPORTIONED TO PROVIDE AN AVERAGE | | | COMPRESSIVE STRENGTH AS PRESCRIBED IN SECTION 1905.3 , | | | | | | AND SHALL SATISFY THE DURABILITY CRITERIA OF SECTION | | | 1904 . | | | | | | COMMENT- | | | SHEET-SP-2 PROVIDE THE CONCRETE DESIGN MIX FOR THE | | | DUMPSTER SLAB. | | | SHEET - S-1 PROVIDE THE DESIGN MIX FOR THE SLAB. | | | ?FOUNDATION NOTES? STATE THAT A SAFE BEARING CAPACITY | | | IS | | | 2,500 LBS.SPECIFY IF THIS IS THE INTENDED DESIGN | | | MIX. | | | | | | | | | | | | 21 | | | WPB ADMENDMENT106.1.1.2 FOR ROOF ASSEMBLIES REQUIRED | | | BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL | | | ILLUSTRATE, DESCRIBE, AND DELINEATE THE TYPE OF ROOFING | | | SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE INSTALLED. | | | | | | | | | | | | 21A | | | FBC BUILDING 1507.10.1 SLOPE. | | | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM | | | OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | | (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR | | | BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF A | | | MINIMUM | | | ONE-EIGHTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | | | | | COMMENT-DEFINE THE ROOF SLOPE FOR DRAINAGE ON SHEET | | | A-2. | | | INDICATE THE ROOF SURFACE ELEVATION AT THE EAST AND | | | WEST. | | | COORDINATE THE ARCHITECTURALWITH THE STRUCTURAL | | | DETAILS | | | REFERENCING THE TIE BEAM ELEVATION | | | | | | | | | | | | 22 | | | FBC BUILDING 13-404.1.ABC.1 ROOF/CEILING THERMAL | | | ENVELOPES. | | | THE ROOF OR CEILING WHICH FUNCTIONS AS THE BUILDING?S | | | THERMAL ENVELOPE SHALL BE INSULATED TO AN R -VALUE OF | | | AT LEAST R-10. ROOF INSULATION SHALL NOT BE INSTALLED | | | ON A | | | SUSPENDED CEILING WITH REMOVABLE CEILING PANELS. | | | | | | COMMENT-ROOF INSULATION CANNOT BE USED IN THE | | | SUSPENDED CEILING. | | | PLEASE PROVIDE THE ROOF INSULATION MINIMUM OF R-10 AS | | | NOTED FBC 13-404.1 ABOVE. | | | | | | | | | 23 | | | FBC BUILDINGTABLE 601 | | | | | | COMMENT-DEFINE FIRE RESISTANT RATING FOR STEEL TUBE | | | COLUMNS | | | | | | | | | 24 | | | FBC BUILDING TABLE 2304.7(3) | | | | | | COMMENTS IDENTIFY STRUCTURAL PANEL SHEATHING BY ITS | | | RATING AND THIS TABLE FOR USE ON THIS PROJECT | | | | | | | | | 25 | | | FBC BUILDING 2121.2.5.1 PARAPET WALLS. | | | MASONRY PARAPET WALLS SHALL BE NOT LESS THAN 8 INCHES | | | THICK, SHALL BE REINFORCED WITH MINIMUMTIE COLUMNS | | | AND SHALL BE COPED WITH A CONCRETE BEAM NOT LESS THAN | | | 64 SQUARE INCHES (.04 M 2 ) IN CROSS- SECTION, | | | REINFORCED WITH TWO #4 REINFORCING BARS. | | | | | | COMMENTS- PROVIDE DETAILS FOR ANCHORING THE PARAPET | | | WALL TO THE BUILDING STRUCTURE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-29 |
Time |
20:54 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-07-29 |
Time |
20:54 |
Sent To |
|
|
| Notes |
| 2007-07-29 22:08:12 | SHELL 7204 S DIXIE HWY/ 07060501 | | | BUILDING PLAN REVIEW | | | PERMIT: 07060501 | | | ADD: 7204 S DIXIE HWY | | | CONT: BENCHMARK CUSTOM BUILDERS | | | TEL: (954)802-0723 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) ADDITIONAL INFORMATION REQUIRED. THE PERMIT | | | APPLICATION INDICATES A SHELL BUILDING WHILE THE PLANS | | | INDICATE THIS TO BE A PHASED, PHASE I A COMMERCIAL | | | FIRST FLOOR AND A PHASE II RESIDENTIAL | | | SECOND FLOOR, ARE BOTH PHASES TO BE CONSIDERED WORK | | | UNDER THIS PERMIT? | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT | | | H) NUMBER OF UNITS | | | I) NUMBER OF FLOORS | | | J) SQ. FT. LIV SPACE/ FL | | | K) SQ. FT. FOOTPRINT | | | | | | 4) SHEET S-1 NOTE# 19 INDICATES THERE SHALL BE A | | | SPECIAL INSPECTOR FOR THE REINFORCED MASONARY SHALL BE | | | PROVIDED. ALSO, PLEASE ARRANGE WITH HAROLD PISKURA | | | (INSPECTION SERVICES MANAGER - TEL: 561 805 6711), A | | | MEETING INVOLVING THE OWNER, SPECIAL INSPECTOR, | | | CONTRACTOR AND ENGINEER. | | | | | | 5) FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE | | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 6) ) 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY | | | THIS CODE SHALL BE PERMORMED IN A MANNER | | | SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS | | | SUCH ACTIVITY IS PERMITTED TO AFFECT | | | SAID PROPERTY PURSUANT TO A CONSENT BY | | | THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE | | | APPLICABLE PROPERTY OWNER.THIS INCLUDES | | | BUT IS NOT LIMITED TO THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, | | | DEBRIS, AND THE STORAGE OF CONSTRUCTION | | | MATERIALS. NEW CONSTRUCTION ACTIVITY | | | SHALL NOT ADVERSELY IMPACT HISTORIC | | | SURFACE WATER DRAINAGE FLOWS SERVING | | | ADJACENT PROPERTIES, & MAY REQUIRE | | | SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, | | | AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR | | | ITEMS, ON EXISTING PROPERTIES RESULTING | | | IN A DECREASE IN EXCESS OF 800SQ FT OF | | | PERMEABLE LAND AREA ON ANY PARCELL SHALL | | | AS A PERMIT CONDITION, PROVIDE A | | | PROFESSIONALLY PREPARED DRAINAGE PLAN | | | CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 7)109.3.10.1 HURRICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 8)BOTH C1 & C2 BOTH INDICATE THIS JOBSITE LOCATION TO | | | BE ON NORTH DIXIE HWY, PLEASE CORRECT. | | | | | | 9)SHEET A-2 INDICATES A MECHANICAL EQUIPMENT STAND | | | WITH A NOTE SEE M-2 FOR DETAIL, MISSING SHEET M-2. | | | | | | 10) SHEET A-2 ALSO INDICATES THE USE OF AN ATTACHED | | | LADDER PLEASE PROVIDE MANUFACTURERS SPECS. 106.1.2 | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE | | | STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | WWW.FLORIDABUILDING.ORG | | | | | | 12)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | | | | A) STOREFRONT- NOTE THE STOREFRONT REPORT NOA | | | 04-0331.02 SECTION (3) CALCULATIONS HAS NOT BEEN | | | VERIFIED UNDER THE 2004 FBC. THE ANCHOR CALCULATIONS | | | WERE UNDER THE 2001 FBC WHEN FASTENERS WERE STILL | | | TAKING THE 1 1/3 INCREASE PLEASE VERIFY THAT THE ANCHOR | | | CALCULATION WILL COMPLY WITH THE 2004 FBC. 1606.3.1.1 | | | LOAD REDUCTION. | | | WHEN STRUCTURAL EFFECTS DUE TO TWO OR MORE LOADS IN | | | COMBINATION WITH DEAD LOAD ARE INVESTIGATED IN LOAD | | | COMBINATIONS OF 1605.3.1.1 THE COMBINED PLIED BY 0.75 | | | PLUS EFFECTS DUE TO DEAD | | | LOADS SHALL NOT BE LESS THAN THE EFFECTS FROM THE LOAD | | | COMBINATION OF THE DEAD LOAD PLUS THE LOAD PRODUCING | | | THE LARGEST EFFECTS. INCREAS IN ALLOWABLE STRESS | | | SPECIFIED IN THE MATERIALS SECTIONS OF THIS CODE OR A | | | REFRENCED STANDARD SHALL NOT BE USED WITH THESE LOAD | | | COMBINATIONS EXCEPT THAT A DURATION OF LOAD INCREASE | | | SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER 23. | | | | | | B) DH-350 ALUMINUM OUTSWING DOOR & TRANSOM REQUIRES | | | FLORIDA COVER SHEET. | | | | | | C) EXTERIOR METAL CORE DOOR | | | | | | D) PRE-ENGINEERED A/C STANDS | | | | | | E) GLASS BLOCK | | | | | | F) TRUSS ANCHORS OR BUCKETS | | | | | | G) ROOFING ASSEMBLIES | | | | | | 13) SHEET A-9 DETAIL# 5 INDICATES 2'X8' WOOD JOIST @ | | | 2'-0" O. C. BUT THERE IS NO INFORMATION HOW THEY WILL | | | BE SECURED IN PLACE? | | | 106.1.2* ADITIONAL INFORMATION REQUIRED. | | | | | | 14) SHEET A-2 STORAGE ROOM# 2THE DOOR ON THE RIGHT | | | SIDE IS MISSING THE REQUIRED 18" SEE : | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 15)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-04-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-03 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-03 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2008-04-03 19:03:16 | 2008-04-03 19:03:16 | | | | | | ELECTRICAL PLANS STAMPED , ENERGY CALCS OK FOR | | | ELECTRICAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-09 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-09 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2008-02-11 08:42:54 | ** DENIED** | | | | | | ** PLEASE SEE THE NOTES BELOW. IF ALL OTHER TRADES PASS | | | THEIR REVIEWS PLEASE CONTACT THIS REVIEWER. | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS | | | NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. PLEASE | | | SEE FOR EXAMPLE INTERIOR FIXTURES ON PLANS CALL FOR | | | 11-100 WATT FIXTURES, YET THE INPUT DATA REPORT SHOWS | | | 9. | | | PLEASE SEE THE CERTIFICATION SHEET PAGE #3 NEEDS TO | | | CONTAIN THE SIGNATURE, DATE AND SEAL FROM THE ENGINEER | | | MR. BUCHANAN. THE SEAL WAS PLACED ON COVER SHEET WHICH | | | IS OK, HOWEVER THIS NEEDS TO BE ON THE CERTIFICATION | | | SHEET AS STATED. | | | 13-103.1.1.1, FAC 61G15-23.002, FS 471.025 | | | PLEASE COMPLETE THE FIXTURE LEGENDS WITH THE TYPE OF | | | FIXTURES WITH MORE DETAIL THAN ONLY STATING IT IS A | | | 100W FIXTURE OR SIMPLY A 75 WATT FIXTURE. PLEASE BE | | | SURE TO CORRELATE WITH THE IDR. | | | | | | 2) NOTE: PLEASE SUBMIT LIGHTING CONTROL DETAIL FOR THE | | | OCCUPANCY SENSORS IN SPACE. COULD NOT LOCATE ANY RELAY | | | DETAIL FOR POWER PACKS, WIRING METHODS ETC. WILL THESE | | | BE LOW VOLTAGE TO POWER PACKS? WILL THESE BE 120V UNITS | | | HARDWIRED? THIS IS THE SAME FOR THE TYPE OF DEVICE | | | WHICH IS SHOWN IN SYMBOL LEGEND AS SM FOR WALL | | | CONTROL. | | | 13-415.1.ABC.1.1, .1.2 | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION. | | | | | | 3) NOTE: PLEASE SEE THE VA LOAD SHOWN ON PANEL SCHEDULE | | | FOR HS-5 SHOWS 720 VA YET THE REVISED LOADS ON FIXTURES | | | FOR OUTSIDE WALKWAYS ADDS UP TO A LOAD OF 900VA. | | | IT IS VERY WELL THE SERVICE AND PANEL IS SIZED OK FOR | | | LOAD, HOWEVER THIS NEEDS TO BE REVISED TO COORDINATE. | | | NEC 220, | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | ** PLEASE KNOW SOME OF THE ABOVE ITEMS MAY BE ABLE TO | | | BE SET UP AS A *PROVISO*, HOWEVER THERE ARE FEW ITEMS | | | WHICH MUST BE ADDRESSED AT THIS TIME. IF*ALL *OTHER | | | REVIEWS PASS REVIEWS, PLEASE CONTACT THIS REVIEWER TO | | | GO OVER WHAT WILL BE NEEDED FOR PERMIT ISSUANCE AND | | | OTHER ITEMS CAN BE PART OF A *PROVISO*. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS REVIEWER DIRECTLY AT THE INFORMATION | | | PROVIDED BELOW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | 561-805-6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-05 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-04 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2007-10-05 09:02:03 | | | | *** DENIED 2ND REVIEW *** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED. | | | | | | | | | 1) NOTE:PLEASE SEE COMMENT #3 FROM PREVIOUS REVIEW | | | WHICH SPECIFICALLY REQUESTED NOT TO ATTACH PRODUCT | | | APPROVALS AND SUPPORTING DOCUMENTS DOWN THE LEFT HAND | | | SIDE OF PLANS. THESE WERE REMOVED BY THIS OFFICE ON THE | | | TWO NEW SETS. PLEASE SEE THE PREVIOUS NOTE #3 BELOW. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT ONLY COMPLETED SIGNED, DATED AND SEALED | | | SETS COMPLETELY BOUND TOGETHER. | | | PLEASE DO NOT SUBMIT COPIES OF PLANS. | | | PLEASE DO NOT ATTACHED PRODUCT APPROVALS, ENERGY | | | CALCULATIONS AND OTHER SUPPORTING DOCUMENTS ATTACHED | | | DOWN THE LEFT HAND SIDE OF PLANS. PLEASE SUBMIT THESE | | | IN FOLDERS/SPIRAL NOTE BOOKS OR SOME FASHION WHICH WILL | | | BE SEPARATE FROM PLANS AND EACH SET. | | | FBC 106.1 | | | | | | 2) NOTE: PLEASE CORRELATE ARCHITECTURAL FLOOR PLAN AND | | | ELECTRICAL FLOOR PLANS. PLEASE SEE A SHEET INDICATES | | | TENANT /BAY WALLS BEING INSTALLED YET THESE WALLS ARE | | | NOT ON ELECTRICAL PLANS. | | | PLEASE SEE NOTE BELOW WITH RESPECT TO CONTROLS FOR | | | CHAPTER 13. | | | FBC 106.1.2 | | | | | | 3) NOTE: PLEASE KNOW COMPLIANCE WITH FBC CHAPTER 13 HAS | | | NOT YET BEEN ACHIEVED. | | | PLEASE SEE NOTE #4 ABOVE FOR INSTANCE AS COMPLIANCE | | | WITH 13-415.1.ABC.1.1 AND .1.3 IS NOT POSSIBLE IF THE | | | WALLS AS SHOWN ON A-SHEETS ARE INSTALLED. | | | PLEASE SEE THE EXACT SAME ENERGY CALCULATIONS WERE | | | SUBMITTED BACK WITHOUT BEING REVISED. THESE | | | CALCULATIONS DO NOT COORDINATE WITH PLANS ON SEVERAL | | | ITEMS. | | | PLEASE SEE THE ADDRESS IS NOT COMPLETE. | | | PLEASE SEE THE SQ FT DOES NOT CORRELATE WITH PLANS WITH | | | ARCHITECTURAL OR ELECTRICAL. | | | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT | | | DOES NOT CORRELATE FOR FIXTURES, WATTAGE, ETC. FOR | | | EXAMPLE, THE PLANS ARE MISSING A FIXTURE LEGEND FOR ALL | | | TYPES OF FIXTURES SO ACTUAL INPUT ON THE IDR CAN NOT BE | | | VERIFIED AT THIS TIME. | | | PLEASE ALSO SEE FOR EXAMPLE THE EXTERIOR LIGHTING WHICH | | | STILL DOES NOT MATCH WITH PLANS FOR NUMBER OF FIXTURES | | | ETC. | | | PLEASE SEE 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3 | | | PLEASE SEE AS PREVIOUSLY NOTED, PLEASE BE SURE ALL ARE | | | SIGNED, DATED AND SEALED ON THE *CERTIFICATION SHEET*, | | | ALONG WITH OWNER AGENT. | | | 13-103.1.1.1, FS 471.025 | | | THESE WERE THE SAME COMMENTS FROM PREVIOUS REVIEW NOTE | | | #5. | | | | | | 4) NOTE:PLEASE SEE AS NOTED ON PREVIOUS REVIEW, IF | | | BUILDING IS REQUIRED TO HAVE A FIRE ALARM SYSTEM | | | INSTALLED EVEN THOUGH THIS IS TO BE DONE A SEPARATE | | | PERMIT, THE BASE PLANS ARE REQUIRED UNDER THE FBC | | | 106.3.5.1.2 AND FLORIDA STATUTES 633 TO CONTAIN A BASE | | | SYSTEM AND BASE COMPLIANCE. IF REQUIRED PER OTHER | | | CODES, THE MINIMUM LOCATIONS AND LEVELS OF DEVICES ARE | | | REQUIRED TO BE SHOWN FOR ADA COMPLIANCE. | | | AS STATED ABOVE, THIS IS ONLY IF A SYSTEM IS REQUIRED. | | | THE PLANS DO INDICATE A FA SYSTEM WILL BE INSTALLED. | | | **PREVIOUS NOTE ** | | | PLEASE KNOW IF THERE IS ANY FIRE SPRINKLER OR FIRE | | | ALARM PLANS WHICH MAY BE REQUIRED UNDER A SEPARATE | | | PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE | | | MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND | | | .3(4). | | | PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING | | | REQUIRED INFORMATION. | | | | | | 5) NOTE: PLEASE SEE SHEET E-3 WHICH IS MISSING BUILDING | | | LAYOUT FROM PLANS. | | | PLEASE SEE THE TITLE BLOCK ON THIS SAME SHEET IS ALSO | | | MISSING THE ADDRESS AS SHOWN ON OTHER SHEETS. | | | | | | ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS. | | | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | | OFFICE/REVIEWER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-01 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-01 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2007-07-01 11:57:01 | | | | | | | *** UNSAT *** | | | | | | | | | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET | | | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW | | | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE | | | REVIEWED AT THIS TIME. | | | | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE | | | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING | | | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED | | | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 | | | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC | | | AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004 | | | FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE | | | SCOPE OF WORK AS APPLIED ON PERMIT APPLICATION SHALL | | | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST | | | ETC. THIS APPLIES EVEN IS ANY IS SUPPLIED BY THE OWNER | | | AND NO COST TO CONTRACTOR. | | | PLEASE SEE FBC 108.3 AS THIS VALUE MAY BE ADJUSTED BY | | | THE ADOPTED GUIDES UNDER THE FLORIDA BUILDING CODE. | | | | | | 3) NOTE:PLEASE SUBMIT ONLY COMPLETED SIGNED, DATED | | | AND SEALED SETS COMPLETELY BOUND TOGETHER. | | | PLEASE DO NOT SUBMIT COPIES OF PLANS. | | | PLEASE DO NOT ATTACHED PRODUCT APPROVALS, ENERGY | | | CALCULATIONS AND OTHER SUPPORTING DOCUMENTS ATTACHED | | | DOWN THE LEFT HAND SIDE OF PLANS. PLEASE SUBMIT THESE | | | IN FOLDERS/SPIRAL NOTE BOOKS OR SOME FASHION WHICH WILL | | | BE SEPARATE FROM PLANS AND EACH SET. | | | FBC 106.1 | | | | | | 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL TRADES ARE | | | TO BE COMPLETE WITH ALL INFORMATION AS REQUIRED PER FAC | | | 61G1-16.004, 61G15-23.002 AND FLORIDA STATUTES 481.219 | | | AND 471.023. | | | PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR | | | LANDSCAPE ARCHITECT. | | | PLEASE SEE THE PLANS SUBMITTED FOR LANDSCAPE SHEETS ARE | | | IN FACT PHOTO-COPIES IN ALL SETS OF WHAT SHOULD BE | | | SIGNED, DATED AND SEALED PLANS. | | | FS 481.221. | | | | | | 5) NOTE: PLEASE SEE FBC 2004 W/2006 REVISION FOR | | | COMPLIANCE WITH CHAPTER 13. PLEASE SEE | | | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING | | | CONTROLS WHICH ARE MISSING FROM PLANS AT THIS TIME. | | | PLEASE SEE THE DEVICE AS NOTED ON PLANS DO NOT SHOW UP | | | IN THE SYMBOL LEGEND, SO THE DEVICES CAN NOT BE | | | VERIFIED AT THIS TIME. | | | PLEASE SUBMIT ALL INFORMATION IF A SYSTEM IS INSTALLED. | | | IF ONLY OS TYPE DEVICES, PLEASE COMPLETE THE | | | INFORMATION ON THESE. | | | PLEASE BE SURE TO DETAIL THE WIRING OF ALL EMERGENCY | | | AND EXIT LIGHTS AHEAD OF THESE DEVICES. | | | PLEASE SUBMIT ANY TIMED SCHEDULING. | | | PLEASE SUBMIT TIME ON DEVICES AND/OR OVER RIDE DEVICES. | | | PLEASE SEE THE SECTIONS GIVEN FOR THE MAXIMUM TIMES | | | PERMITTED. | | | PLEASE SUBMIT COMPLETED FIXTURE LEGENDS FOR ALL | | | FIXTURES WHICH ARE TO CONTAIN ALL INFORMATION ON THESE | | | FIXTURES AND WILL NEED TO CORRELATE WITH LIGHTING | | | PERFORMANCE CALCULATIONS FOR COMMON AREAS. | | | PLEASE SEE NUMBER OF LUMINARIES, THE TYPE OF | | | LUMINARIES, THE CONTROL OF LUMINARIES AS STATED ON THE | | | ENERGY CALCULATIONS DO NOT CORRELATE WITH THE PLANS AS | | | SUBMITTED. | | | PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE | | | CALCULATIONS PLEASE KNOW WHEN THE ENERGY CALCULATIONS | | | ARE CORRECTED AND SUBMITTED THE OWNER AGENT IS REQUIRED | | | TO BE SIGNED ON EACH. 13-103.1.1.1 | | | PLEASE SEE THE SHEET 3 FOR CERTIFICATIONS FROM ALL | | | DESIGNER(S) IS THE SHEET WHICH IS REQUIRED TO BE | | | SIGNED, DATED AND SEALED. | | | 13-415.1.AB.1.1, 13-415.1.C, 13-415.2. | | | | | | 6) NOTE: PLEASE SEE 13-413.1.ABC.1 OF THE FBC CHAPTER | | | 13. PLEASE SUBMIT WORST CASE SCENARIO FOR VOLTAGE DROP | | | ON FEEDERS AND BRANCH CIRCUITS. | | | | | | 7) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL | | | EGRESS PATHS FROM UNITS WHICH ARE BEING NOTED ON PLANS | | | AS FUTURE DWELLING UNITS UPSTAIRS. | | | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS. | | | PLEASE SUBMIT AND INDICATE LEVELS UNDER NORMAL AND | | | EMERGENCY. | | | PLEASE SEE THERE IS NOT LIGHTING SHOWNFOR STAIRS | | | PLEASE SEE 700.12F, 700.16 | | | | | | PLEASE SEE NOT #5 ABOVE WITH RESPECT TO THE TYPE OF | | | FIXTURES AND THE FIXTURE LEGEND TO BE COMPLETED. | | | | | | 8) NOTE: PLEASE SEE AS PLANS ARE INCOMPLETE FOR ANY | | | NOTES ON FUTURE UPSTAIRS UNITS ETC, THE ADDITIONAL | | | SERVICE AS SHOWN ON PLANS AND RISER AS FUTURE IS NOT | | | GRANTED AT THIS TIME. | | | PLEASE COMPLETE PLANS WITH THE FUTURE INFORMATION AND | | | INFORMATION TO DETERMINE WHETHER OR NOT THE ADDITIONAL | | | SERVICE AS SHOWN MAY BE GRANTED. AT THIS TIME THIS IS | | | NOT PERMITTED AS SHOWN ON PLANS AND RISER. | | | 230.2, 230.70, 220, ETC. | | | | | | 9) NOTE: PLEASE VERIFY IF A CT WILL BE ON RISER FOR THE | | | LINE SIDE OF THE 800A MDP. | | | FBC 106.3.5.1.2 (FPL REQUIRED?) | | | | | | 10) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM NOTES | | | *STRUCTURAL STEEL*WHICH IS OK AND REQUIRED IF PRESENT | | | PER 250.50 HOWEVER PLEASE CLARIFY IF THIS IS MEANT TO | | | BE THE *FOOTER STEEL* ? | | | | | | 11) NOTE: PLEASE KNOW IF THERE IS ANY FIRE SPRINKLER OR | | | FIRE ALARM PLANS WHICH MAY BE REQUIRED UNDER A SEPARATE | | | PERMIT THE BASE BUILDING PLANS SHALL INDICATE THE | | | MINIMUM LEVELS AND LOCATIONS PER FBC 11-4.28.1, .2 AND | | | .3(4). | | | PLEASE DO NOT QUOTE THE CODE IN LIEU OF SHOWING | | | REQUIRED INFORMATION. | | | | | | 12) NOTE: PLEASE SUBMIT/INDICATE ALL OF THE REQUIRED | | | AIC RATINGS FOR SERVICE EQUIPMENT/MAINS AND BRANCH | | | BREAKERS. | | | 110.9. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 13) NOTE: PLEASE SUBMIT WIND LOAD ENGINEERING FOR SITE | | | LIGHT POLES.PLEASE KNOW THESE WILL BE REVIEWED BY | | | BUILDING REVIEWER AND WILL BE REQUIRED TO MEET THE FBC | | | 140MPH MIN FOR 3-SEC GUST, 120 SUSTAINED OR ABOVE. FBC | | | 106.1.2 | | | | | | | | | | | | *** PLEASE KNOW AS THERE ARE SEVERAL DESIGN CHANGES | | | REQUIRED AND THERE ARE NUMEROUS ITEMS ON PLANS WHICH | | | ARE NOT COMPLETE THERE MAY VERY WELL BE NEW COMMENT SON | | | THE FOLLOWING REVIEW. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
P |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-05-15 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-05-15 |
Time |
14:36 |
Sent To |
B |
|
| Notes |
| 2008-05-15 14:41:56 | PASSED, WITH FOLLOWING PROVISO: | | | PLEASE MAKE SUREYOU CORRECT ITEM #1 & ITEM#3 OF | | | MOCK-ROOS FOLLOWING LETTER | | | RASIK CHOKSHI 805-6723 | | | | | | MARTIN PILOTE, P.E. | | | GLOBE ENGINEERING, INC. | | | N. LAUDERDALE, FL | | | | | | HI MARTIN: | | | | | | THE FOLLOWING LETTER IS FROM OUR CONSULTANT MOCK-ROOS. | | | THEY MADE SOME MINOR COMMENTS ON YOUR WATER QUALITY | | | CALCULATIONS.THEREFORE, WE ASK YOU TO INCORPORATE | | | THEIR ITEM #1 & ITEM # 3 STATED IN MOCK ROOS'S | | | FOLLOWING LETTER FOR YOUR WATER CALCULATION PACKAGE AND | | | YOUR DRAWINGS. HOWEVER, WE HAVE PROVISIONALLY APPROVED | | | YOUR PLANS THAT YOU WILL CORRECT THE STORM WATER | | | CALCULATIONS AND DRAWINGS SUGGESTED BY MOCK-ROOS AS | | | SOON AS POSSIBLE. | | | THANKS, | | | | | | RASIK | | | | | | MAY 6, 2008 | | | MR. EMERY FABIAN | | | CITY OF WEST PALM BEACH | | | ENGINEERING PROJECT COORDINATOR | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH, FL 33407 | | | REF. NO. W7700.16 | | | SUBJECT: FOREST POINT DRAINAGE REVIEW | | | DEAR EMERY: | | | WE HAVE COMPLETED OUR REVIEW OF THE PLANS AND | | | CALCULATIONS PROVIDED FOR THE ABOVE REFERENCED | | | PROJECT. OUR OBSERVATIONS ARE AS FOLLOWS: | | | 1. THE PROPOSED EXFILTRATION TRENCH DETAIL SPECIFIES | | | ONLY 12 INCHES OF BACKFILL OVER THE TRENCH, RATHER | | | THAN THE 18 INCHES THAT IS SPECIFIED BY THE SFWMD | | | TYPICAL EXFILTRATION TRENCH DETAIL. | | | 2. NO GEOTECHNICAL REPORT WAS PROVIDED TO SUBSTANTIATE | | | THE HYDRAULIC CONDUCTIVITY (K VALUE) OR THE | | | GROUND WATER TABLE LEVEL. HOWEVER, THE K VALUE APPEARS | | | TO BE CONSERVATIVE. | | | 3. THE CALCULATIONS INDICATE THAT THE PROPOSED SITE | | | PROVIDES STORAGE FOR UP TO THE 10-YEAR/1-DAY | | | RAINFALL EVENT. HOWEVER, THIS CALCULATION IS BASED ON | | | AN EFFECTIVE HEAD VALUE OF 10.2? (INLET GRATE | | | ELEVATION LESS THE GROUND WATER ELEVATION). IT IS MORE | | | CONVENTIONALLY ACCEPTED THAT THIS VALUE | | | SHOULD BE THE INLET GRATE ELEVATION LESS THE BOTTOM OF | | | THE TRENCH, 16.25? ? 9.75 = 6.5?. USING THE | | | LOWER VALUE, THE PROPOSED VOLUME OF THE TRENCH IS | | | SUFFICIENT FOR THE 5-YEAR/1-HOUR, WHICH IS THE | | | SFWMD CRITERION FOR PARKING AREAS, AND IT IS ALSO | | | ENOUGH STORAGE VOLUME TO PROVIDE FOR THE | | | RUNOFF FROM THE 5-YEAR/1-DAY; HOWEVER, IT IS NOT ENOUGH | | | FOR THE 10-YEAR/1-DAY EVENT RUNOFF. ANY | | | RUNOFF IN EXCESS OF THE 5-YEAR/1-DAY WILL LEAVE THE | | | SITE. THE PLANS DO NOT INDICATE THE OFF-SITE FLOW | | | PATTERN AND IT IS UNKNOWN IF THE DISCHARGE FLOWS TO THE | | | CITY?S SYSTEM OR THAT OF FDOT. | | | ALL THINGS CONSIDERED, THE PROPOSED DRAINAGE MEETS | | | SFWMD WATER QUALITY CRITERIA, PROVIDES THE | | | MINIMUM LEVEL OF PARKING PROTECTION AND WILL BE AN | | | IMPROVEMENT OVER THE EXISTING CONDITIONS. WE | | | RECOMMEND THAT THE CITY CONTINUE TO PROCESS THE | | | PROPOSED SITE APPLICATION. | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT 683-3113, | | | EXTENSION 231. | | | SINCERELY, | | | MOCK, ROOS & ASSOCIATES, INC. | | | ALAN D. WERTEPNY, P.E. | | | AC:JEH SENIOR PROJECT MANAGER |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
F |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-04-04 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-04-04 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2008-04-04 14:32:00 | *****FAILED****** | | | | | | 1. PLEASE PROVIDE A COPYOF GEO-TECH REPORT AND A | | | LATESTEST COPY OF STORM STORM WATER QUALITY | | | CALCULATIONSTOMR. BRAMLEY100045TH STREET | | | ENGINEERINGFOR THEIR REVIEW.STORM WATER QUALITY | | | CALS MUST BE APPROVED FROM 45TH STREET BEFORE WE ISSUE | | | PERMIT. | | | | | | 2. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET ( EMERY FABIAN ), UTILITY DEPT BEFORE WE | | | APPROVE. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-02-25 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-02-25 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2008-02-25 15:39:13 | ****FAILED***** | | | | | | PLEASE RESPOND REV 2, 10/19/07 COMMENTS TO EXPEDITE | | | PERMIT PROCESS | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-10-19 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-10-19 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2007-10-19 14:03:02 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. FIRST FLOOR ELEVATION=18', PLEASE SHOW IN YOUR WATER | | | QUALITY CALS. THAT YOU CONSIDEREDCENTER LINE OF ROAD | | | (CROWN OF THE ROAD), FLOOD ZONE AREA, & 5,10, 25, 100 | | | YEAR FLOOD CRITERIATO DETERMINE THE FIRST FLOOR | | | ELEVATION. FLOOR ELEVATION SHUOLD BE HIGHER THAN CROWN | | | OF THE ROAD BY 1', PLEASE SHOW ALL THESE IN CALS & | | | DRAWINGS. | | | 3. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST | | | MATCH WITH AREAS USED IN STORM WATER QUALITY | | | CALCULATIONS. | | | 4. ALSO PLEASE SHOW ALL STORM WATER CATCH BASINS | | | NEAREST AROUND YOUR SITE. | | | 5. PLEASE PROVIDE A COPY OF NPBID PERMIT, OR SFWMD | | | PERMIT OR ENVOROMENTAL RESOURCE PERMIT , A COPY OF | | | GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM | | | WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH | | | STREET. STORM WATER QUALITY CALS MUST BE APPROVED FROM | | | 45TH STREET BEFORE WE ISSUE PERMIT. | | | 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-07-12 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-07-12 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2007-07-12 11:31:26 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER , | | | ITS ENCLOSURE & THEIR DETAILS PER CITY OF WPB, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS. | | | PLEASE SHOW IN YOUR STORM WATER QUALITY CALS. | | | 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST | | | MATCH WITH AREAS USED IN STORM WATER QUALITY | | | CALCULATIONS. | | | 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM | | | WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL | | | STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION | | | TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS | | | WITH 100% FILL OF STORM WATER ELEVATION IF YOU HAVE IT? | | | PLEASE TELL US WHERE THE STORM WATER GOES IN CITY CANAL | | | OR SFWMD CANAL AFTER CONTROL STRUCTURE? | | | 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND | | | YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE. | | | 7. PLEASE PROVIDE A COPY OF NPBID PERMIT, OR SFWMD | | | PERMIT OR ENVOROMENTAL RESOURCE PERMIT , A COPY OF | | | GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM | | | WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH | | | STREET. | | | 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | | 10. PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS | | | IFTHOSE WERE APPROVED AT 45TH STREET . | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-04-24 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-04-24 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-04-24 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2008-04-24 11:01:36 | STAMPED, SIGNED AND DATED SHEET A-1 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-18 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-18 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2008-03-18 14:24:07 | *****DENIED***** | | | | | | THE FOLLOWINGS COMMENTS (NOT MARKED OK) TAKEN FROM THE | | | PREVIOUS FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1.OK | | | | | | 2.OK | | | | | | 3.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE | | | EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. | | | AS PER WEST PALM BEACH CODE, THE ADDRESS NUMBERS SHALL | | | BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN | | | WIDTH. | | | | | | 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION.ADD TO PROJECT INFORMATION UNDER APPLICABLE | | | CODES (COVER & TITLE SHEET) | | | | | | 5.CONSTRUCTION, ALTERATION, AND DEMOLITION SHALL | | | COMPLY WITH NFPA 241.ADD TO PROJECT INFORMATION UNDER | | | APPLICABLE CODES (COVER & TITLE SHEET) | | | | | | 6.OK | | | | | | 7.MORE INFORMATION WILL BE REQUIRED TO ADDRESS | | | CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF | | | THIS SCOPE OF WORK. | | | | | | 8.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHERS WHICH SATIFIY THE 75' TRAVEL DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | MIKE WENNERGREN,ASSISTANT FIRE MARSHAL | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | FIRE PLAN REVIEW | | | FIRE PREVENTION 561-804-4756 | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-11-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-02 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-02 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2007-11-02 14:02:43 | **DENIED*** | | | | | | TAKEN DIRECTLY FROM FIRST REVIEW: | | | 1) BOUNDARY AND CIVIL DRAWINGS INDICATE NORTH DIXIE | | | HIGHWAY. PLEASE MAKE CORRECTION TO REFLECT SOUTH DIXIE | | | HIGHWAY. | | | | | | 2) IT APPEARS THAT BAY-2 ONLY HAS ONE (1) EXIT. PLEASE | | | VERIFY, AND IF SO DOES SPACE MEET REQUIREMENTS FOR | | | SINGLE EXIT? | | | | | | 3) ADDRESS IS REQUIRED ON BUILDING THAT MEETS THE | | | STANDARDS FOR THE CITY OF WEST PALM BEACH FOR | | | COMMERCIAL BUILDINGS. CITY CODE SEC. 78. | | | | | | 4) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 6) SHEET SP-1 ILLUSTRATES A RESTAURANT. MORE | | | INFORMATION WOULD BE REQUIRED SUCH AS PROPOSED | | | HOOD/SUPPRESSION EQUIPMENT, SEATING LAY OUT, OCCUPANT | | | LOAD ETC. | | | | | | 7) MORE INFORMATION WILL BE REQUIRED TO ADDRESS | | | CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF | | | THIS SCOPE OF WORK. | | | | | | 8) 2A-10B,C RATED FIRE EXTINGUISHERS REQUIRED TO MEET | | | MINIMUM 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | IT WOULD BE HELPFUL TO INCLUDE A RESPONSE LETTER | | | INDICATING HOW AND WHERE ON PLANS COMMENTS HAVE BEEN | | | ADDRESSED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-31 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-31 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2007-07-31 15:55:22 | ***DENIED*** | | | | | | 1) BOUNDARY AND CIVIL DRAWINGS INDICATE NORTH DIXIE | | | HIGHWAY. PLEASE MAKE CORRECTION TO REFLECT SOUTH DIXIE | | | HIGHWAY. | | | | | | 2) IT APPEARS THAT BAY-2 ONLY HAS ONE (1) EXIT. PLEASE | | | VERIFY, AND IF SO DOES SPACE MEET REQUIREMENTS FOR | | | SINGLE EXIT? | | | | | | 3) ADDRESS IS REQUIRED ON BUILDING THAT MEETS THE | | | STANDARDS FOR THE CITY OF WEST PALM BEACH FOR | | | COMMERCIAL BUILDINGS. CITY CODE SEC. 78. | | | | | | 4) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 6) SHEET SP-1 ILLUSTRATES A RESTAURANT. MORE | | | INFORMATION WOULD BE REQUIRED SUCH AS PROPOSED | | | HOOD/SUPPRESSION EQUIPMENT, SEATING LAY OUT, OCCUPANT | | | LOAD ETC. | | | | | | 7) MORE INFORMATION WILL BE REQUIRED TO ADDRESS | | | CONCERNS REGARDING SECOND FLOOR USE PROPOSAL IF PART OF | | | THIS SCOPE OF WORK. | | | | | | 8) 2A-10B,C RATED FIRE EXTINGUISHERS REQUIRED TO MEET | | | MINIMUM 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-29 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-29 |
Time |
09:51 |
Sent To |
ENG |
|
| Notes |
| 2008-04-29 09:52:48 | TO "RCHOKSHI" DESK/RESUB--PLANS ONLY NEED ENG PER | | | "LMARTINEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-04-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-03 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-03 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2008-04-03 09:51:25 | TO "COMM" BD#40 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-01 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-01 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2008-02-01 08:38:41 | TO "COMM" BD#29/PLANS ON RACK--LARGE FOLDED PLANS AND | | | PAPERWORK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-11 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-11 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2007-10-02 14:11:52 | TO "COMM" BD#37 | | 2007-09-11 11:32:44 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-31 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-06-19 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2007-07-02 08:31:56 | TO "COMM" BD#54 | | 2007-06-19 09:22:47 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-04-23 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-04-23 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-26 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-26 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2008-02-26 17:47:44 | REVIEW #: 3RD | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | COMMENTS 1 AND 2: ASSUMPTIONS SHALL BE MADE AND | | | APPENDED TO THE ENERGY CALCULATIONS IN ACCORDANCE WITH | | | FBC 13-101.1.6. ASSUMPTIONS REGARDING OCCUPANT LOAD AND | | | VENTILATION REQUIREMENTS NEED TO BE INCLUDED, SINCE | | | THAT INFORMATION IS REQUIRED TO PERFORM COOLING LOAD | | | CALCULATIONS IN ACCORDANCE WITH FBC 13-407.1.ABC.1. | | | ASSUMPTIONS REGARDING THE SIZE OF THE EQUIPMENT | | | INCLUDED IN THE ENERGY CALCULATIONS SHALL BE BASED ON | | | THESE CALCULATIONS. MAKE SURE ALL ASSUMPTIONS AND | | | COOLING LOAD CALCULATIONS ARE APPENDED TO THE ENERGY | | | CALCULATIONS IN ACCORDANCE WITH THESE SECTIONS. | | | | | | 3. PG A-1 IS STILL CALLING FOR R-30 BATTS ABOVE A GRID | | | CEILING WHILE A-2 CALLS FOR SPRAY FOAM INSULATION ON | | | UNDERSIDE OF DECK. ADDITIONALLY, ON PAGES A-2 AND A-5 | | | THE PLANS CALL FOR R-75 INSULATION. PLEASE COORDINATE | | | PLANS AND SHOW WHICH METHOD IS TO BE USED. | | | | | | 4. PLEASE PROVIDE THE COMPONENTS OF THE EXTERIOR BLOCK | | | WALL ASSEMBLY WITH THEIR RESPECTIVE R-VALUES IN ORDER | | | TO COME TO A TOTAL OF R-12.5. FBC 13-403.2.AB. | | | | | | 5. OK | | | | | | 6. THE ?PRODUCT APPROVAL? FOR THE A/C STAND INCLUDED IN | | | THE BINDER ONLY HAS A COPY OF THE SEARCH SCREEN FROM | | | THE DCA WEBSITE STAMPED AND REVIEWED BY THE DESIGNER. A | | | COMPLETE PRODUCT APPROVAL WITH DETAILED INSTALLATION | | | INSTRUCTIONS SHALL BE PROVIDED AND THE ACTUAL PRODUCT | | | APPROVAL SHALL BE APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD IN ACCORDANCE WITH FBC 106.4. | | | | | | 7. OK | | | | | | 8. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-03 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-03 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2007-11-03 15:47:59 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | COMMENTS 1 THROUGH 8: NONE OF THE PREVIOUS MECHANICAL | | | REVIEW COMMENTS WERE ADDRESSED EITHER IN WRITING OR IN | | | THE SUPPORTING DOCUMENTATION/PLANS. SEE ATTACHED COPY | | | OF PREVIOUS REVIEW COMMENTS AND ADDRESS EACH OF THEM | | | ACCORDINGLY PRIOR TO RESUBMITTAL. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-17 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-16 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2007-07-17 11:23:30 | --------------DENIED--------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO INFORMATION WAS PROVIDED REGARDING VENTILATION | | | REQUIREMENTS. PLEASE PROVIDE OCCUPANCY CLASSIFICATION, | | | OCCUPANT LOAD AND OUTDOOR AIR CALCULATIONS BASED ON | | | FBC,M 403.3. | | | | | | 2. NO INFORMATION WAS INCLUDED IN ENERGY CALCULATIONS | | | FOR AIR CONDITIONING OR OTHER FEATURES OF THE SPACE. | | | NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO | | | DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS | | | AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY | | | WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE | | | CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL | | | ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL | | | LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE | | | LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO | | | THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS | | | COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL | | | CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S) | | | USING METHODS A, B OR C SHALL BE SUBMITTED WHEN | | | COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS | | | PERMITTED. FBC 13-101.1.6 | | | | | | 3. PG A-1: NOTE #1 INDICATES R-30 INSULATION IS TO BE | | | PROVIDED LATER ABOVE A FUTURE DROP CEILING. ROOF | | | INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED | | | CEILING WITH REMOVABLE PANELS PER FBC 13-404.1.ABC.1. | | | | | | 4. PG A-1: NOTE #3 INDICATES R-5 INSULATION ON EXTERIOR | | | MASONRY WALLS, BUT ENERGY CALCULATIONS SHOW R-12.5. | | | PLEASE COORDINATE PLANS WITH INFORMATION USED IN THE | | | INPUT DATA REPORT. FBC 13-403.2.AB | | | | | | 5. PLEASE INCLUDE EXTERIOR DOOR INFORMAION ON ENERGY | | | CALCULATIONS/ INPUT DATA REPORT. FBC 13-403.2.AB | | | | | | 6. PG A-2 SUPPORT DETAIL: PRE-ENGINEERED A/C STANDS ARE | | | STRUCTURAL COMPONENTS AS DEFINED IN FAC RULE 9B-72 AND | | | AS SUCH ARE SUBJECT TO THE FLORIDA PRODUCT APPROVAL | | | SYSTEM. PLEASE PROVIDE NOA WITH INSTALLATION DETAILS. | | | ALSO, DRAWING REFERS TO A DETAIL ON PAGE M-2, BUT THERE | | | IS NO PG M-2 PROVIDED. PLEASE CLARIFY. FBC 106.1.1 | | | | | | 7. M-1: OUTSIDE AIR OPENINGS IN THE EXTERIOR WALLS | | | SHALL BE LOCATED A MINIMUM OF 10' FROM ANY HAZARDOUS | | | CONTAMINANT SUCH AS STREETS, ALLEYS, PARKING LOTS AND | | | LOADING DOCKS PER FBC,M 401.5.1. | | | | | | 8. M-1: WALL LEGEND ON A-1 SHOWS EXTERIOR BLOCK WALLS | | | TO BE 1-HOUR RATED. HOW ARE OUTDOOR AIR AND EXHAUST | | | OPENINGS TO BE PROTECTED IN ACCORDANCE WITH FBC,M | | | 401.6? | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-03-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-14 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-14 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-03 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-03 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2007-11-03 10:33:20 | DENIED | | | REFERENCE: FBC-2004 W/2006 AMENDMENTS | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND | | | FLOOR PIPING**** | | | | | | ****FROM PREVIOUS REVIEW. COMMENT NUMBER SHALL BE THE | | | SAME TO AVOID CONFUSION: | | | | | | 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED. | | | SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE | | | FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED | | | SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR | | | REVIEW. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC. | | | TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT | | | REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR | | | WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE | | | WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING | | | FOR REVIEW. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE | | | TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.-- | | | THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS | | | THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT. | | | PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER | | | INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC | | | 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS | | | SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2. ****NO | | | RESPONSE, NOT ADDRESSED. NOW SHT IR-1 ADDED AND THE | | | SAME COMMENT APPLIES. | | | | | | 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER | | | WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1. ****NO | | | RESPONSE, NOT ADDRESSED. | | | | | | 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE | | | BUILDING. 106.3.5.1.1(2). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER | | | TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE | | | TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA | | | OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN | | | THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA | | | BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE | | | SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE | | | GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1& | | | 106.1.2. | | | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE SUBMITTED. | | | THE SQUARE FOOTAGE BEING DRAINED BY EACH DOWNSPOUT CAN | | | NOT BE DETERMINED UNTIL THE HIGH POINT IS ESTABLISHED. | | | IT APPEARS THAT THE SQUARE FOOTAGE DRAINING INTO EACH | | | DOWNSPOUT WILL BE DIFFERENT BECAUSE OF THE FACT THAT | | | THE DOWNSPOUTS ARE NOT EVENLY SPACED THROUGH THE | | | GUTTER. | | | | | | 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION | | | 106.1.1. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 8. N/A | | | | | | 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON | | | THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE | | | INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN. | | | SHOW ALL DOWNSPOUTS. SECTION 106.1.1. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 10. OK | | | 11. OK | | | | | | **********NEW COMMENTS********** | | | | | | 1B. SHT P-3 THE RISER DIAGRAM FOR UNIT/BAY-1 NOW | | | INDICATES A GREASE INTERCEPTOR. THIS DOES NOT REFLECT | | | THE FLOOR PLAN. SECTION 106.1.1. THE GREASE INTERCEPTOR | | | IS NOT APPROVED FOR INSIDE THE BUILDING AND SHALL BE | | | LOCATED OUTSIDE THE BUILDING. ALSO A NOTE ON THE RISER | | | DIAGRAM STATES "TERMINATE AND CAP ABOVE THE CEILING FOR | | | FUTURE USE". WILL THERE BE A RESTAURANT ON THE SECOND | | | FLOOR? PLEASE CLARIFY. | | | | | | 2B. ALL GREASE INTERCEPTORS SHALL BE SIZED BY THE | | | UTILITY DEPT., INDUSTRIAL PRE-TREATMENT, ENVIRONMENTAL | | | COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561) | | | 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS, | | | (561) 822-2284, E-MAIL [email protected]. THERE FAX | | | NUMBER IS (561) 822-2287. A WRITTEN DETERMINATION FROM | | | ENVIRONMENTAL COMPLIANCE WILL BE SUBMITTED WITH THE | | | PLANS WHEN RESUBMITTING FOR REVIEW OF BLDG PERMIT. | | | | | | 3B. NO VENTING FOR THE FIRST FLOOR IS INDICATED ON THE | | | SANITARY RISER DIAGRAMS. PLEASE INDICATE HOW THE TENANT | | | BUILD-OUTS WILL BE VENTED. SECTION 901.2.1. | | | | | | 4B. SHT P-3 RISERS 4 & 5 DO NOT REFLECT THE FLOOR PLAN. | | | RISER 4 INDICATES AN OFFSET AT THE TOP OF THE STACK | | | THAT IS NOT INDICATED ON THE FLOOR PLAN, AND ON RISER 5 | | | AN OFFSET IS REQUIRED TO REFLECT THE FLOOR PLAN. TO | | | CLEAR UP THE CONFUSION INDICATE THE RISER NUMBERS ON | | | THE FLOOR PLANS OF THE FIRST AND SECOND FLOORS SHTS P-1 | | | & P-2. RISERS START OFF RISER 1 ON THE LEFT AND | | | CONTINUE TO RISER 5 ON THE RIGHT. PLEASE | | | CLARIFY.SECTION 106.1.1. | | | | | | 5B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A | | | NOTICE ONLY AT THIS TIME. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE, NOT ADDRESSED. BY NOT ADDRESSING THE | | | COMMENTS WITH A WRITTEN RESPONSE, REVIEW TIME TAKES | | | LONGER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-16 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-07-14 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2007-07-16 12:23:34 | DENIED | | | REFERENCE: FBC-2004 W/2006 AMENDMENTS | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****SUBMITTED & REVIEWED AS SHELL ONLY WITH FUTURE 2ND | | | FLOOR PIPING**** | | | | | | 1. SURVEY SHEET 1 OF 1 SHALL BE SIGNED, SEALED & DATED. | | | SECTION 106.1.--THE LICENSE STATUS AS SHOWN ON THE | | | FLORIDA STATE DBPR WEBSITE IS DELINQUENT. (SEE ATTACHED | | | SHEET). PLEASE UPDATE STATUS PRIOR TO RESUBMITTING FOR | | | REVIEW. | | | | | | 2. ALL SHEETS WITH SOUTHEAST ARCHITECT SERVICES INC. | | | TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT | | | REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR | | | WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE | | | WEBSITE AND/OR THE TITLE BLOCK PRIOR TO RESUBMITTING | | | FOR REVIEW. | | | | | | 3. SHTS L-1 & L-2THE FIRM ADDRESS IS REQUIRED IN THE | | | TITLE BLOCK PER FAC 61G1-16.004(1) & FS 481.2055.-- | | | THE ORIGINAL LEGAL SIGNATURE IS REQUIRED. IT APPEARS | | | THAT INITIALS HAVE BEEN USED TO SIGN THE DOCUMENT. | | | PLEASE SUBMIT A SIGNED, SEALED, DATED, NOTORIZED LETTER | | | INDICATING YOUR LEGAL SIGNATURE FOR OUR FILES. FAC | | | 61G1-16.003, 61G1-16.004(5) & FS 481.2055.--SHEETS | | | SHALL BE SEALED PER SECTION 106.1.1 & 106.1.2. | | | | | | 4. PLANS SHALL INDICATE ALL CODES ADOPTED AND UNDER | | | WHICH THE PLANS WERE DESIGNED. SECTION 106.1.1. | | | | | | 5. PLEASE INDICATE THE PROPOSED OCCUPANCY OF THE | | | BUILDING. 106.3.5.1.1(2). | | | | | | 6. SHT A-2 SUBMIT CALCULATIONS FOR THE GUTTERS PER | | | TABLE 1106.6 & DOWNSPOUTS PER TABLE 1106.2. SHOW THE | | | TOTAL SQUARE FOOTAGE AREA OF THE ROOF AND SHOW 1/2 AREA | | | OF ALL VERTICAL WALLS INCLUDING PARAPETS INCLUDED IN | | | THE CALCULATIONS.--SHOW THE TOTAL SQUARE FOOT AREA | | | BEING DRAINED BY EACH DOWNSPOUT.--INDICATE THE | | | SLOPE OF EACH GUTTER AND INDICATE THE HIGH POINT OF THE | | | GUTTER SLOPING TO THE DOWNSPOUTS.SECTIONS 106.1.1& | | | 106.1.2. | | | | | | 7. SHT A-2 INDICATE THE SLOPE OF THE MAIN ROOF. SECTION | | | 106.1.1. | | | | | | 8. SHT A-3 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON | | | THE ROOF PLAN. PLEASE CORRELATE. SECTION 106.1.1.-- | | | NO DOWNSPOUTS ARE INDICATED ON THE ELEVATION. PLEASE | | | SHOW THE LOCATION OF EACH DOWNSPOUT. SECTION 106.1.1. | | | SHOW THE SIZE OF THE GUTTER AND THE DOWNSPOUTS. TABLES | | | 1106.6 & 1106.2. | | | | | | 9. SHT A-4 GUTTERS DO NOT REFLECT THE GUTTERS SHOWN ON | | | THE ROOF PLAN. NO DOWNSPOUTS SHOWN. PLEASE CORRELATE | | | INFORMATION SHOWN ON THE ELEVATION AND THE ROOF PLAN. | | | SHOW ALL DOWNSPOUTS. SECTION 106.1.1. | | | | | | 10. SHT P-3 THE SANT RISER TO UNIT #1 SHOWS 2" TO ONE | | | LAV, BUT THE FLOOR PLAN SHOWS 3".--RISER TO UNIT | | | #3 SHOWS 3" TO LAVS AND 3" TO ONE LAV BUT SHOWS 2" ON | | | THE FLOOR PLANS. --RISER TO UNIT #4 SHOWS 2" TO THE | | | W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS SHOWN | | | ON THE FLOOR PLAN. - 3" IS SHOWN TO TWO LAVS BUT SHOWN | | | AS 2" ON THE FLOOR PLAN.--RISER TO UNIT #5 SHOWS 2" | | | TO THE W/M. 3" IS REQUIRED PER SECTION 406.3 AND 3" IS | | | SHOWN ON THE FLOOR PLAN. PLEASE CORRELAT INFORMATION | | | BETWEEN THE FLOOR PLAN AND THE RISER DIAGRAMS. | | | | | | 11. SHT P-3 BAY 1 WATER RISER. PLEASE SHOW ALL PIPE | | | SIZES.--BAY 2 WATER RISER IS SHOWN AS 1-1/4" | | | METER/BACKFLOW BUT FLOOR PLAN SHOWS 2" METER/BACKFLOW. | | | PLEASE CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND | | | THE RISER DIAGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-04-10 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-04-09 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2008-04-10 11:13:41 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. | | | | | | PROVISO SHEET SP-1 SHALL GOVERN FOR BENCH AND PLANTER | | | LAYOUT. | | | | | | PROVISO SHEET A-1 SHALL GOVERN FOR BENCH | | | LAYOUT/ORIENTATION. | | | | | | A SIGN PERMIT SHALL BE SUBMITTED FOR ALL SIGNS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-02-06 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-02-06 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2008-02-06 15:35:27 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. | | | | | | PROVISO SHEET SP-1 SHALL GOVERN FOR BENCH AND PLANTER | | | LAYOUT. | | | | | | PROVISO SHEET A-1 SHALL GOVERN FOR BENCH | | | LAYOUT/ORIENTATION. | | | | | | A SIGN PERMIT SHALL BE SUBMITTED FOR ALL SIGNS. | | | | | 2008-02-06 08:45:36 | IN ZONING FOR REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-09-26 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-09-20 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2007-09-26 12:27:00 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. THE LANDSCAPE PLANS SHOW A LARGER NUMBER OF TREES TO | | | BE REMOVED THAN THE NUMBER STATED ON THE TREE | | | ALTERATION PERMIT APPLICATION.PLEASE SUBMIT TWO (2) | | | COPIES OF A REVISED LANDSCAPE PLAN AND TREE SURVEY, AS | | | WELL AS A STATEMENT EXPLAINING THE ADDITIONAL TREES TO | | | BE REMOVED, TO AMEND YOUR TREE ALTERATION PERMIT | | | APPLICATION.PLEASE NOTE THAT APPROVAL OF THE TREE | | | ALTERATION PERMIT IS REQUIRED PRIOR TO BUILDING PERMIT | | | APPROVAL. | | | | | | 2. SURVEY STILL SHOWS NORTH DIXIE HIGHWAY INSTEAD OF | | | SOUTH DIXIE HIGHWAY.PLEASE NOTE THAT ALL COPIES OF | | | THE SURVEY SHALL BE SIGNED AND SEALED.IN ADDITION, | | | PLEASE NOTE THAT THE STORMWATER PREVENTION PLAN, SHEET | | | C2 OF 4, ALSO READS NORTH DIXIE HIGHWAY. | | | | | | 3. STAFF'S COMMENTS AT THE AUGUST 20, 2007 MEETING WERE | | | TO COME UP WITH ALTERNATIVES TO ADJUST THE SLABS OF THE | | | FUTURE BALCONIES SO THAT THEY MAY BE MORE IN CHARACTER | | | WITH THE PROPORTION OF PHASE I. | | | A. ONE OF THE SUGGESTIONS MADE BY STAFF WAS TO REDUCE | | | THE THICKNESS OF THE FACIA CONCEALING THE SLABS. | | | HOWEVER, THE PLANS SUBMITTED ONLY SHOW THE THICKNESS | | | REDUCED ON TWO (2) OF THE SLABS.THERE SHOULD BE A | | | CONSISTENCY THROUGHOUT THE BUILDING.IF THE THICKNESS | | | OF THE THIRD SLAB CAN NOT BE REDUCED DUE TO STRUCTURAL | | | PURPOSES, THEN THE REMAINING SLABS SHOULD REMAIN THE | | | SAME. | | | B. THE SECOND SUGGESTION MADE BY STAFF WAS TO INSTALL | | | LIGHTING FIXTURES UNDERNEATH THE SLABS.PLEASE PROVIDE | | | DETAILS AND A CROSS-SECTION OF THE LIGHT FIXTURES | | | LOCATED UNDERNEATH THE SLABS.AS MENTIONED IN THE | | | MEETING, THERE SHOULD BE ENOUGH FACIA DEPTH TO CONCEAL | | | THE LIGHTING FIXTURE BELOW THE SLAB AND BEHIND THE BEAM | | | SO THAT IT WILL NOT BE VISIBLE. | | | | | | 4. PLEASE NOTE THAT THERE APPEARS TO BE SOME | | | DISCREPANCY BETWEEN THE PLANS (I.E. NAME OF SOUTH DIXIE | | | HIGHWAY, AND LAYOUT OF THE BENCH AT THE NORTHWEST | | | CORNER OF THE SITE).PLEASE ENSURE THAT ALL PLANS SHOW | | | THE SAME CONDITIONS. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-06-29 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-06-26 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2007-06-29 14:06:13 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. PROVIDE COPY OF THE APPROVAL LETTER FROM PALM TRAN | | | FOR THE NEW BUS STOP LOCATION. | | | | | | 2. PROPOSED BUS STOP LOCATION SHALL BE SHOWN ON THE | | | LANDSCAPE PLAN. | | | | | | 3. PROVIDE A COPY OF FDOT APPROVAL FOR THE REMOVAL OF | | | THE EXISTING CURB CUTS ON SOUTH DIXIE HIGHWAY. | | | | | | 4. PROVIDE A COPY OF THE APPROVED PLANS/LETTER FOR THE | | | TREES THAT ARE TO BE REMOVED AND/OR RELOCATED. | | | | | | 5. SURVEY AND PLANS SHALL BE CORRECTED TO SHOW SOUTH | | | DIXIE HIGHWAY INSTEAD OF NORTH DIXIE HIGHWAY. | | | | | | 6. THE PROPOSED BUILDING SQUARE FOOTAGE ON THE | | | PHOTOMETRIC PLAN DOES NOT MATCH THE PROPOSED BUILDING | | | SQUARE FOOTAGE ON THE SITE PLAN AND FLOOR PLAN.ALL | | | PLANS SHALL SHOW THE SAME DATA.PROVIDE CORRECT | | | BUILDING SQUARE FOOTAGE ON THE PHOTOMETRIC PLAN. | | | | | | 7. HANDICAP SYMBOL SHALL BE PAINTED IN WHITE. | | | | | | 8. FLOOR PLAN (SHEET A-1) SHOWS TWO (2) COLUMNS ALONG | | | THE SIGHT LINE, WHICH ARE NOT SHOWN ON ANY OF THE OTHER | | | PLANS.PLEASE CLARIFY THE PRESENCE OF THE NEW COLUMNS. | | | IN THE EVENT THAT THE COLUMNS ARE FOR STRUCTURAL | | | SUPPORT PURPOSES, STAFF RECOMMENDS USING ALTERNATIVE | | | DESIGN OPTIONS SO THAT THEY MAY NOT TAKE AWAY FROM THE | | | VISUAL EMPHASIS AND INTEREST TO THE MAIN ENTRANCE. | | | | | | 9. PLEASE CONTACT THE PLANNING AND ZONING DEPARTMENT TO | | | DISCUSS DESIGN OPTIONS FOR THE BALCONY SLABS AND | | | PARAPET. | | | | | | 10.ALL SIGNS SHALL BE APPROVED ON A SEPARATE | | | PERMIT. | | | | | | 11.PLEASE PROVIDE ONE OF THE FOLLOWING. | | | A. AN IRRIGATION PLAN TO BE INCLUDED WITH THIS | | | PERMIT APPLICATION; OR | | | B. AN IRRIGATION PLAN UNDER A SEPARATE | | | PERMIT. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
|