Plan Review Details - Permit 07060491
Plan Review Stops For Permit 07060491
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By mjacobs Date 2007-11-08 Time 10:47 Rev Time 0.00
Received By mjacobs Date 2007-10-31 Time 18:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-28 Cont ID  
Sent By mjacobs Date 2007-09-28 Time 10:13 Rev Time 0.00
Received By mjacobs Date 2007-09-27 Time 10:45 Sent To  
Notes
2007-09-28 10:17:43BUILDING PLAN REVIEW
 PERMIT: 07060491
 ADD: 1554 PBL BLVD.
 CONT: GREAT DANE PETROLEUM CONTRACTORS
 TEL: (954)792-1334
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION. SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIRE-MESH, FIBER MESHES OR IF STEEL REBAR WILL BE
 USED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
 ***FBC 1805.2 FOOTINGS ARE REQUIRED TO EXTEND BELOW THE
 GROUND SURFACE A MINIMUM OF 12 INCHES.**
  
 3)2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS,
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT,
 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES
 IN TERMS OF PSF.
 ***THE STRUCTURE AND GENERATOR WILL BE USED DURING
 EMERGENCY SITUATIONS. THEREFORE, THE STRUCTURE SHALL BE
 A CATEGORY IV WITH A WIND FACTOR OF 1.15. SEE FBC TABLE
 1604.5.
  
 4)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By mjacobs Date 2007-07-12 Time 07:42 Rev Time 0.00
Received By mjacobs Date 2007-07-11 Time 18:24 Sent To  
Notes
2007-07-11 19:01:12BUILDING PLAN REVIEW
 PERMIT: 07060491
 ADD: 1554 PBL BLVD.
 CONT: GREAT DANE PETROLEUM CONTRACTORS
 TEL: (954)792-1334
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BE USED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 3)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 SITE WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST AND DESIGN FEES EXCLUDING LAND VALUE. OUR
 VALUATION REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-21 Cont ID  
Sent By dpalmer Date 2007-11-21 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2007-11-21 Time 10:08 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 12:18 Sent To  
Notes
2007-11-09 12:18:42** DENIED **
  
  
 1) NOTE:PLEASE SEE NOTES FROM PREVIOUS REVIEW(S)
 WHICH STATES LETTER NEEDS TO STATE THE CONNECTION,
 ENERGIZING OF GENERATOR AND DISCONNECT AND RE-CONNECT
 TO UTILITY NORMAL POWER WILL BE DONE ONLY BY QUALIFIED
 PERSONNEL.
 NEC 100, 702.6
 PLEASE KNOW THE SAME LETTER AS PREVIOUSLY SUBMITTED WAS
 NOT CHANGED AND AS STATED ON REVIEW OF 9/16/07 LETTER
 NEEDS TO BE CORRECTLY NOTARIZED ALSO.
  
 ELECTRICAL PLANS ARE STAMPED AS OK, ONCE LETTER IS
 SUBMITTED AND ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-16 Cont ID  
Sent By dpalmer Date 2007-09-16 Time 11:19 Rev Time 0.00
Received By dpalmer Date 2007-09-16 Time 10:41 Sent To  
Notes
2007-09-16 11:20:432007-09-16 11:20:43
  
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SUBMIT AN ORIGINAL LETTER FROM AN
 OFFICER OF THE COMPANY WHICH WOULD BE FROM EXXON?S
 CORPORATE DIVISION WHICH STATES THE ENERGIZING,
 DE-ENERGIZING AND START UP OF THIS UNIT WILL ONLY BE
 PERFORMED BY QUALIFIED PERSONNEL. THE LETTER AS
 SUBMITTED FROM EXXON?S PROJECT MANAGER IS NOT AS NEEDED
 FROM THIS DEPARTMENT
 702.6 EXCEPTION.
 THIS LETTER IS TO BE NOTARIZED AND ORIGINAL WHICH WILL
 BE PLACED IN FILE FOR ANY FUTURE REFERENCE.
 THIS LETTER NEEDED HAS BEEN CONFIRMED WITH THE
 BUILDING OFFICIAL AND ASSISTANT BUILDING OFFICIAL
 THROUGH CITY LAW DEPARTMENT.
  
 * KEYED INTERLOCKS WITH MULTIPLE KEYS AVAILABLE AND
 INSTALLED WILL NOT PREVENT INADVERTENT CONNECTION OF
 THE UTILITY AND EMERGENCY BACK UP SOURCE OF POWER AT
 THE SAME TIME*
  
 2) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WHICH MAY
 BE FORTHCOMING FOR THE STRUCTURAL DESIGN OF FOOTING FOR
 THE NEW WALL.
 THIS IS OF CONCERN AS THE FOOTER FOR THE 9FT PLUS WALL
 IS BEING SHOWN AS 8 INCHES BY 8 INCHES AS A THICKENED
 EDGE SLAB.
  
 3) NOTE: PLEASE SEE THE MAINS AND MEANS OF DISCONNECT
 FOR THE SERVICE AND GENERATOR ARE NOW BEING SHOWN
 INSIDE A BLOCK WALL ENCLOSURE.
 HOW WILL THE FIRE DEPARTMENT OR EMERGENCY PERSONNEL
 HAVE ACCESS TO THIS EQUIPMENT?
 PLEASE SEE 110.26 FOR THE CLEAR AND UNOBSTRUCTED PATH
 REQUIRED FOR THIS AREA. THE CLEARANCE IS BEING SHOWN AS
 6FT TO THE WALL; PLEASE PROVIDE A MORE DETAILED LAYOUT
 FOR CLEAR SPACE, ACCESS, AND MEETING 110.26.
 THIS WILL BE FORWARDED TO THE FIRE MARSHAL ALSO. IT MAY
 BE A KNOX BOX WHICH WILL BE REQUIRED.
 230.70, 230.71, 230.76, 230.79 ETC.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By dpalmer Date 2007-06-28 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2007-06-28 Time 15:25 Sent To I
Notes
2007-06-28 16:28:49 
  
 *** UNSAT ***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND
 ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70(SHOWS A 2000 EDITION?)
  
 ** PLEASE SEE COMMENTS FROM FIRE AND OTHER TRADES FOR
 OTHER CODES REFERENCED.
  
 2) NOTE: PLEASE SEE THE PERMIT APPLICATION AS SUBMITTED
 NEEDS TO CONTAIN THE SIGNATURES OF THE QUALIFIER OR
 AUTHORIZED AGENT FOR THE ELECTRICAL CONTRACTOR. PLEASE
 SEE THESE ALL APPEAR TO BE THE SAME SIGNATURE FROM THE
 SAME PERSON.
 PLEASE SEE THE NOTARY STATEMENT NEEDS TO BE FILLED OUT
 CORRECTLY. PLEASE SUBMIT SIGNATURE VERIFICATION LETTERS
 ORIGINAL AND NOTARIZED CORRECTLY UNDER FS 117.05.
 ** PLEASE KNOW THE PERMIT APPLICATION AS SUBMITTED WILL
 BE RETAINED BY THIS OFFICE.
  
 3) NOTE: PLEASE SEE THE VALUE AS STATED ON APPLICATION
 IS EXTREMELY LOW. PLEASE KNOW THE VALUE IS REQUIRED TO
 BE FOR ALL LABOR, EQUIPMENT, CONSTRUCTION, MATERIALS,
 DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. FBC 108.3
 ** PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE
 IF AN APPROPRIATE VALUE IS NOT ADJUSTED.
  
 4) NOTE: PLEASE KNOW THE EXISTING MTS AS STATED ON
 PLANS MUST COMPLY WITH NEC 702.6. PLEASE KNOW THAT
 THERE IS KEYED INTERLOCK EQUIPMENT WHICH DOES NOT MEET
 THE NEC FOR INADVERTENT CONNECTION.
 PLEASE KNOW MANY OF THESE DEVICES CONTAIN MULTIPLE KEYS
 WHICH PERMIT THE DEVICES FROM BOTH POWER SOURCES BEING
 TURNED ON AT THE SAME TIME.
 PLEASE SUBMIT SPECS FOR EQUIPMENT TO BE SURE TO SUBMIT
 THE SPECS FOR THE MTS TO VERIFY THIS IS NOT EQUIPMENT
 AS STATED.
  
 5) NOTE: PLEASE SEE RISER WHICH INDICATES ONLY ONE SET
 OF CONDUCTORS RATED FOR 310AMPS FROM THE GENERATOR WHEN
 THE BREAKER ON THE GENERATOR IS 600AMPS.
 PLEASE SEE 240.4, 310.16 AND 445.13
  
 6) NOTE: PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS
 NEED TO INDICATE THE OVER CURRENT PROTECTION OF THE
 BREAKER TO COORDINATION WITH THE RISER. PLEASE ALSO BE
 SURE THE SPECS/CUT SHEETS ALSO INDICATE THE MINIMUM
 CLEARANCES FOR THE GENERATOR UNIT FROM ALL EQUIPMENT,
 VENTS ETC.
 PLEASE SEE THIS UNIT BEING DIESEL WILL REQUIRED A
 MINIMUM OF 10FT FROM ANY OPENINGS INTO THE STRUCTURE.
 PLEASE SEE MECHANICAL REVIEW FOR THIS.
 FBC 106.1.2 FOR COORDINATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-28 15:25:02PLANS REMOVED FROM INCOMING AND IN ELEC FOR REVIEW.
 PLANS ROUTED BACK TO INCOMING ONCE REVIEW IS DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-12 Cont ID  
Sent By mawillia Date 2007-11-12 Time 14:18 Rev Time 0.00
Received By mawillia Date 2007-11-12 Time 14:08 Sent To  
Notes
2007-11-12 14:18:19*****APPROVED*****
  
  
 PLAN SHEET G-2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By mawillia Date 2007-10-10 Time 13:06 Rev Time 0.00
Received By mawillia Date 2007-10-10 Time 12:51 Sent To  
Notes
2007-10-10 13:05:33*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;HOWEVER THE APPROPIATE SHEET(S) TO BE
 FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 23:03 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 22:50 Sent To  
Notes
2007-07-26 23:03:08*****DENIED*****
  
  
 1.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA
 704 LABELS WILL BE REQUIRED.
  
 2.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 3.INCLUDE IN THE NOTES ON G-1 THAT NFPA 101, LIFE
 SAFETY CODE, 2003 EDITION SHALL BE REFERENCED.
  
 4.PROVIDE MANUFACTURE SPEC SHEETS FOR THE GENERATOR
 AND ASSOCIATED EQUIPMENT.
  
 5.THE INSTALLATION AND/OR SCOPE OF WORK SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF.
  
 6.ILLUSTRATE DISTANCES TO OPENINGS AND ANY MEANS OF
 EGRESS IN REGARDS TO FUEL EXHAUST.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By rregueir Date 2007-11-19 Time 14:36 Rev Time 0.00
Received By rregueir Date 2007-11-19 Time 14:34 Sent To PC
Notes
2007-11-19 14:36:22ONE SET OF PREVIOUSLY SUBMITTED PLANS TO BE RETAINED IN
 PERMIT RECORDS FOR PBC DERM APROVAL STAMP. SECOND SET
 RETURNED TO CONTRACTOR FOR FIELD PERMIT SET.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By rregueir Date 2007-10-05 Time 16:08 Rev Time 0.00
Received By rregueir Date 2007-10-05 Time 16:08 Sent To  
Notes
2007-10-05 16:09:40REVIEW #:2
 ACTION: DENIED
  
 PLANS AS RESUBMITTED ARE NOT APPROVED BY PALM BEACH
 COUNTY DERM. PLEASE BE SURE PLANS, WHEN RESUBMITTED,
 HAVE PBC DERM APPROVAL ON THEM
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2007-07-17 Cont ID  
Sent By rregueir Date 2007-07-17 Time 17:23 Rev Time 0.00
Received By rregueir Date 2007-07-17 Time 16:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 17:54 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 17:54 Sent To  
Notes
2007-07-14 17:54:34GENERATOR IS INDICATED AS A DIESEL GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 16:09 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 16:09 Sent To  
Notes
2007-11-08 13:37:19TO "COMM" BD#21
2007-10-18 16:10:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 13:27 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 13:27 Sent To  
Notes
2007-08-27 13:28:22WAITING FOR "COMM" BD--NEW SHEETS(ALL TRADES)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 22:50 Rev Time 0.00
Received By mawillia Date 2007-06-15 Time 16:40 Sent To  
Notes
2007-06-29 11:05:42TO "COMM" BD#14
2007-06-15 16:47:40WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-05 Cont ID  
Sent By rregueir Date 2007-10-05 Time 16:07 Rev Time 0.00
Received By rregueir Date 2007-10-05 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By rregueir Date 2007-07-17 Time 17:26 Rev Time 0.00
Received By rregueir Date 2007-07-17 Time 17:23 Sent To  
Notes
2007-07-17 17:26:23--------------DENIED-----------------
  
 1. WHAT IS THE DISTANCE BETWEEN THE PROPOSED WALL AND
 THE EXISTING CONDENSER? PLEASE VERIFY THAT CLEARANCE
 WILL BE MAINTAINED PER ITS ORIGINAL LISTING AND THAT
 MINIMUM SERVICE CLEARANCE IS MAINTAINED. FBC 106.1.1
  
 2. PLEASE SHOW GENERATOR EXHAUST DISCHARGE LOCATION TO
 BE AT LEAST 10 FEET FROM ANY OPENINGS INTO THE BUILDING
 SUCH AS DOORS, WINDOWS, SOFFIT VENTS AND AIR INTAKES.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By kdfreema Date 2007-11-08 Time 08:46 Rev Time 0.00
Received By kdfreema Date 2007-11-08 Time 08:46 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By kdfreema Date 2007-10-04 Time 09:02 Rev Time 0.00
Received By kdfreema Date 2007-09-17 Time 14:07 Sent To  
Notes
2007-09-17 14:07:49A MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO BE
 SUBMITTED AS A RESULT IN THE CHANGES IN THE
 CONFIGURATION OF THE GENERATOR MADE IN THIS
 RESUBMITTAL.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-07-19 Cont ID  
Sent By kdfreema Date 2007-07-19 Time 16:38 Rev Time 0.00
Received By kdfreema Date 2007-07-19 Time 16:38 Sent To  
Notes
***NONE***