Plan Review Details - Permit 07060486
Plan Review Stops For Permit 07060486
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By dpalmer Date 2008-01-10 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2008-01-10 Time 12:57 Sent To FIRE
Notes
2008-01-10 12:58:12SENT TO FIRE FOR STAMPS AS PREVIOUSLY NOTED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-06 Cont ID  
Sent By dpalmer Date 2007-12-06 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2007-12-06 Time 16:36 Sent To FIRE
Notes
2007-12-06 16:37:08** DENIED 4TH REVIEW **
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE ONLY THE ONE ELECTRICAL SHEET WAS
 STAMPED BY THE BASE BUILDING ENGINEERING FIRM. ALL
 SHEETS ARE REQUIRED TO BE STAMPED.
 THIS WAS ON PREVIOUS REVIEW COMMENTS.
 FS 471.
 FBC 106.3.5.1.2, 110.1.2, 106.1.2 ETC FOR
 COORDINATION.
  
 2) NOTE: PLEASE SEE THE FEE ASSESSED FOR COMMENCIGN
 WORK WITHOUT PERMITS IS REQUIRED TO BE PAID BEFORE
 PERMIT CAN BE ISSUED. THE BALANCE IS $10, 500.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-27 Cont ID  
Sent By dpalmer Date 2007-10-27 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 09:02 Sent To FIRE
Notes
2007-10-27 09:29:00** DENIED **
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH
 REQUIRES THE BASE BUIDLING ENGINEER OF RECORD TO REVIEW
 AND SHOP DRAWING REVIEW STAMP. THE STAMP ON PLANS IS
 NOT FROM TH BASE BUILDING ENGINEER OF RECORD.
 THIS BUILDING IS COVERED AND UNDER THE RESPONSIBLITY OF
 THE BASE BUIDLING ENGINEER UNTIL CERTIFICATE OF
 OCCUPANCY IS ISSUED FOR THE BUILDING.
 FS 471.
 ** PLEASE ADDRESS.
  
 2) NOTE: PLEASE SEE THE BASE PERMIT FEES AS NOTED ON
 PREVIOUS REVIEW ALSO STILL NEEDS TO BE PAIDS. THE
 SYSTEM STILL INDICATES A BALANCE OWED.
 108.1, 108.3
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-14 Cont ID  
Sent By dpalmer Date 2007-08-14 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2007-08-14 Time 10:12 Sent To FIRE
Notes
2007-08-14 12:52:16 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW COMMENT.
  
  
 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 PLEASE BE SURE THE FOLLOWING CURRENT CODES ADOPTED BY
 THE STATE ARE ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE).
  
 2) NOTE:OWES FEES FOR VALUE BEING INCREASED BY
 CONTRACTOR.
 FBC 108.3
  
  
 3) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW. NO DETAILS FOR LISTED PENETRATIONS PROVIDED
 ALONG WITH CABLING INFORMATION.
 FBC
 PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE INSTALLED
 FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE METHOD OF
 INSTALLATION OF THESE CABLES.
 PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS
 MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC.
 PLEASE SEE CHAPTER 8 NEC.
  
 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE BASE
 BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER OF
 RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED BY
 THE BASE BUILDING DESIGNER OF RECORD.
 FS 471
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By dpalmer Date 2007-06-25 Time 08:03 Rev Time 0.00
Received By dpalmer Date 2007-06-25 Time 07:04 Sent To FIRE
Notes
2007-06-25 08:03:37 
  
 *** UNSAT ***
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CURRENT CODES
 ADOPTED BY THE STATE ARE ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE).
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK
 SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT, AND
 WIRING, DESIGN COST ETC. THIS IS EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. PLEASE SEE THE VALUE AS
 STATED ON PERMIT APPLICATION IS EXTREMELY LOW. A VALUE
 MAY BE ASSESSED BY THIS OFFICE USING GUIDES ADOPTED
 INTO THE FBC 108.3
  
 3) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH
 ARE NOT SHOWN ON SYMBOL LEGEND AND DEVICES CAN NOT BE
 REVIEWED AT THIS TIME.
 FBC 106.1.2
  
 4) NOTE: PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE
 INSTALLED FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE
 METHOD OF INSTALLATION OF THESE CABLES.
 PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS
 MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC.
 PLEASE SEE CHAPTER 8 NEC.
  
 5) NOTE: PLEASE SEE THE CAMERA WHICH IS BEING SHOWN ON
 THE SEPARATE PROPERTY (ELEVATOR TOWER) IS NOT PERMITTED
 AS SYSTEMS CROSSING OVER THE PROPERTY LINE.
  
 6) NOTE: PLEASE PROVIDE INFORMATION FOR ACCESS AND
 EGRESS CONTROLS AND FAIL-SAFE OPERATIONS SO THAT IN THE
 EVENT OF A POWER FAILURE EGRESS IN NOT IMPEDED IN ANY
 FASHION.
 PLEASE ALSOSEE NOTES FROM THE FIRE MARSHAL'S OFFICE
 WITH RESPECT TO LOCKING ARRANGEMENTS AND FURTHER
 DETAILS ON PLANS FOR CARD ACCESS, PUSH BUTTONEGRESS
 ETC WHICH WILL AFFECT THESE PLANS.
 PLEASE SEE NFPA-101CHAPTER 7:PLEASE SEE 7.2.1.5,
 7.2.1.6., 7.2.1.9 ONLY TO MENTION A FEW.
  
 7) NOTE: PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE
 BASE BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER
 OF RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED
 BY THE BASE BUILDING DESIGNER OF RECORD.
 FS 471
  
 8) NOTE: PLEASE SUBMIT THREE SETS OF COMPLETE PLANS AND
 SPECS AS THIS IS A THRESHOLD PROJECT.
 FBC106.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-25 07:05:21RECEIVED 6/22

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-17 Time 12:13 Rev Time 0.00
Received By mawillia Date 2008-01-17 Time 11:55 Sent To  
Notes
2008-01-17 12:10:19*****APPROVED*****
  
  
 PLAN SHEET 1 (OF 8) STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-02 Cont ID  
Sent By mawillia Date 2008-01-02 Time 11:41 Rev Time 0.00
Received By mawillia Date 2008-01-02 Time 10:53 Sent To  
Notes
2008-01-02 11:41:15*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ACKNOWLEDGED;HOWEVER THE APPROPIATE PLAN
 SHEET(S) TO BE FIRE-STAMPED WHEN ELECTRICAL'S COMMENT #
 1 HAS BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-11-15 Cont ID  
Sent By mwennerg Date 2007-11-15 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2007-11-15 Time 15:03 Sent To  
Notes
2007-11-15 15:13:00***DENIED***
  
 1) OK, PLEASE CLARIFY IF OPTION A OR B WILL BE PROVIDED
 WITH REGARDS TO NFPA 101, SEC.7.2.1.6.2 (1).
  
 2) REQUIRED EXIT DOORS NEED TO BE IDENTIFIED WITH
 REGARDS TO MEANS OF EGRESS TO DETERMINE COMPLIANCE WITH
 REFERENCED SECTION IN COMMENT #1.
  
 3) OK, EQUIPMENT TO BE INSPECTED, TESTED AND APPROVED
 BY THIS OFFICE PRIOR TO FINAL INSPECTION.
  
 4) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-03 Cont ID  
Sent By mawillia Date 2007-10-03 Time 13:58 Rev Time 0.00
Received By mawillia Date 2007-10-03 Time 12:30 Sent To  
Notes
2007-10-03 13:57:51*****UNSAT*****
  
 OLD COMMENT
  
 1.DOORS IN A MEANS OF EGRESS SHALL BE PERMITTED TO BE
 EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101
 (2003 EDITION) 7.2.1.6.2 ARE MET.PLEASE PROVIDE
 INFORMATION DETAILING HOW THIS IS ACCOMPLISHED.PLEASE
 INDICATE WHICH ONE(S) OF THE CRITERIA WILL BE
 FOLLOWED.
  
 NEW COMMENTS
  
 2.SHOW THE LOCATION OF THE EXIT LIGHTS.
  
 3.PLEASE EXPLAIN THE RATIONALE FOR CARD READERS ON
 ELEVATORS AS SHOWN ON SHEET 1.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 15:45 Rev Time 0.00
Received By mawillia Date 2007-07-11 Time 14:51 Sent To  
Notes
2007-07-11 15:45:42*****UNSAT*****
  
  
 1.DOORS IN A MEANS OF EGRESS SHALL BE PERMITTED TO BE
 EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101
 (2003 EDITION) 7.2.1.6.2 ARE MET.PLEASE PROVIDE
 INFORMATION DETAILING HOW THIS IS ACCOMPLISHED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-10 Cont ID  
Sent By dpalmer Date 2008-01-10 Time 08:34 Rev Time 0.00
Received By dpalmer Date 2008-01-10 Time 08:34 Sent To E
Notes
2008-01-10 08:34:54TO DVP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 11:41 Sent To FIRE
Notes
2007-12-06 11:41:46TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 09:57 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 09:57 Sent To E
Notes
2007-10-26 09:57:29TO "DPALME" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 13:33 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 13:33 Sent To E
Notes
2007-08-13 13:34:15TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 14:51 Rev Time 0.00
Received By mawillia Date 2007-06-15 Time 14:44 Sent To  
Notes
2007-06-15 14:44:30TO "E" BOX