| Plan Review Stops For Permit 07060486 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-10 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-10 |
Time |
12:57 |
Sent To |
FIRE |
|
| Notes |
| 2008-01-10 12:58:12 | SENT TO FIRE FOR STAMPS AS PREVIOUSLY NOTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-12-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-06 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-06 |
Time |
16:36 |
Sent To |
FIRE |
|
| Notes |
| 2007-12-06 16:37:08 | ** DENIED 4TH REVIEW ** | | | | | | ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | 1) NOTE: PLEASE SEE ONLY THE ONE ELECTRICAL SHEET WAS | | | STAMPED BY THE BASE BUILDING ENGINEERING FIRM. ALL | | | SHEETS ARE REQUIRED TO BE STAMPED. | | | THIS WAS ON PREVIOUS REVIEW COMMENTS. | | | FS 471. | | | FBC 106.3.5.1.2, 110.1.2, 106.1.2 ETC FOR | | | COORDINATION. | | | | | | 2) NOTE: PLEASE SEE THE FEE ASSESSED FOR COMMENCIGN | | | WORK WITHOUT PERMITS IS REQUIRED TO BE PAID BEFORE | | | PERMIT CAN BE ISSUED. THE BALANCE IS $10, 500. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-10-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-27 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-27 |
Time |
09:02 |
Sent To |
FIRE |
|
| Notes |
| 2007-10-27 09:29:00 | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH | | | REQUIRES THE BASE BUIDLING ENGINEER OF RECORD TO REVIEW | | | AND SHOP DRAWING REVIEW STAMP. THE STAMP ON PLANS IS | | | NOT FROM TH BASE BUILDING ENGINEER OF RECORD. | | | THIS BUILDING IS COVERED AND UNDER THE RESPONSIBLITY OF | | | THE BASE BUIDLING ENGINEER UNTIL CERTIFICATE OF | | | OCCUPANCY IS ISSUED FOR THE BUILDING. | | | FS 471. | | | ** PLEASE ADDRESS. | | | | | | 2) NOTE: PLEASE SEE THE BASE PERMIT FEES AS NOTED ON | | | PREVIOUS REVIEW ALSO STILL NEEDS TO BE PAIDS. THE | | | SYSTEM STILL INDICATES A BALANCE OWED. | | | 108.1, 108.3 | | | | | | ** PLEASE SUBMIT THE ABOVE FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-14 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-14 |
Time |
10:12 |
Sent To |
FIRE |
|
| Notes |
| 2007-08-14 12:52:16 | | | | *** DENIED 2ND REVIEW *** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED ALONG WITH NEW COMMENT. | | | | | | | | | 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. | | | PLEASE BE SURE THE FOLLOWING CURRENT CODES ADOPTED BY | | | THE STATE ARE ON PLANS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 (IF APPLICABLE). | | | | | | 2) NOTE:OWES FEES FOR VALUE BEING INCREASED BY | | | CONTRACTOR. | | | FBC 108.3 | | | | | | | | | 3) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS | | | REVIEW. NO DETAILS FOR LISTED PENETRATIONS PROVIDED | | | ALONG WITH CABLING INFORMATION. | | | FBC | | | PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE INSTALLED | | | FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE METHOD OF | | | INSTALLATION OF THESE CABLES. | | | PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS | | | MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC. | | | PLEASE SEE CHAPTER 8 NEC. | | | | | | 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS | | | REVIEW. | | | PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE BASE | | | BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER OF | | | RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED BY | | | THE BASE BUILDING DESIGNER OF RECORD. | | | FS 471 | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-25 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-25 |
Time |
07:04 |
Sent To |
FIRE |
|
| Notes |
| 2007-06-25 08:03:37 | | | | | | | *** UNSAT *** | | | | | | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING CURRENT CODES | | | ADOPTED BY THE STATE ARE ON PLANS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 (IF APPLICABLE). | | | | | | 2) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK | | | SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT, AND | | | WIRING, DESIGN COST ETC. THIS IS EVEN IF ANY OF THESE | | | ITEMS ARE OWNER SUPPLIED. PLEASE SEE THE VALUE AS | | | STATED ON PERMIT APPLICATION IS EXTREMELY LOW. A VALUE | | | MAY BE ASSESSED BY THIS OFFICE USING GUIDES ADOPTED | | | INTO THE FBC 108.3 | | | | | | 3) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH | | | ARE NOT SHOWN ON SYMBOL LEGEND AND DEVICES CAN NOT BE | | | REVIEWED AT THIS TIME. | | | FBC 106.1.2 | | | | | | 4) NOTE: PLEASE STATE ALL CABLE TYPES WHICH ARE TO BE | | | INSTALLED FOR RATED AREAS/PLENUMS ETC. PLEASE INDICATE | | | METHOD OF INSTALLATION OF THESE CABLES. | | | PLEASE SEE 300.21 AS ANY CONDUIT/WIRING PENETRATIONS | | | MUST INCLUDE THE LISTED DETAIL PER UL/ASTM/ANSI ETC. | | | PLEASE SEE CHAPTER 8 NEC. | | | | | | 5) NOTE: PLEASE SEE THE CAMERA WHICH IS BEING SHOWN ON | | | THE SEPARATE PROPERTY (ELEVATOR TOWER) IS NOT PERMITTED | | | AS SYSTEMS CROSSING OVER THE PROPERTY LINE. | | | | | | 6) NOTE: PLEASE PROVIDE INFORMATION FOR ACCESS AND | | | EGRESS CONTROLS AND FAIL-SAFE OPERATIONS SO THAT IN THE | | | EVENT OF A POWER FAILURE EGRESS IN NOT IMPEDED IN ANY | | | FASHION. | | | PLEASE ALSOSEE NOTES FROM THE FIRE MARSHAL'S OFFICE | | | WITH RESPECT TO LOCKING ARRANGEMENTS AND FURTHER | | | DETAILS ON PLANS FOR CARD ACCESS, PUSH BUTTONEGRESS | | | ETC WHICH WILL AFFECT THESE PLANS. | | | PLEASE SEE NFPA-101CHAPTER 7:PLEASE SEE 7.2.1.5, | | | 7.2.1.6., 7.2.1.9 ONLY TO MENTION A FEW. | | | | | | 7) NOTE: PLEASE KNOW ANY SYSTEMS BEING INSTALLED IN THE | | | BASE BUILDING WHICH IS STILL UNDER THE PRIMARY ENGINEER | | | OF RECORD MUST HAVE PLANS/SHOP DRAWING/SPECS REVIEWED | | | BY THE BASE BUILDING DESIGNER OF RECORD. | | | FS 471 | | | | | | 8) NOTE: PLEASE SUBMIT THREE SETS OF COMPLETE PLANS AND | | | SPECS AS THIS IS A THRESHOLD PROJECT. | | | FBC106.1 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-06-25 07:05:21 | RECEIVED 6/22 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-17 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-17 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2008-01-17 12:10:19 | *****APPROVED***** | | | | | | | | | PLAN SHEET 1 (OF 8) STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-01-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-02 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-02 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2008-01-02 11:41:15 | *****PROVISO***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ACKNOWLEDGED;HOWEVER THE APPROPIATE PLAN | | | SHEET(S) TO BE FIRE-STAMPED WHEN ELECTRICAL'S COMMENT # | | | 1 HAS BEEN ADDRESSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-15 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-15 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2007-11-15 15:13:00 | ***DENIED*** | | | | | | 1) OK, PLEASE CLARIFY IF OPTION A OR B WILL BE PROVIDED | | | WITH REGARDS TO NFPA 101, SEC.7.2.1.6.2 (1). | | | | | | 2) REQUIRED EXIT DOORS NEED TO BE IDENTIFIED WITH | | | REGARDS TO MEANS OF EGRESS TO DETERMINE COMPLIANCE WITH | | | REFERENCED SECTION IN COMMENT #1. | | | | | | 3) OK, EQUIPMENT TO BE INSPECTED, TESTED AND APPROVED | | | BY THIS OFFICE PRIOR TO FINAL INSPECTION. | | | | | | 4) OK | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-03 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-03 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2007-10-03 13:57:51 | *****UNSAT***** | | | | | | OLD COMMENT | | | | | | 1.DOORS IN A MEANS OF EGRESS SHALL BE PERMITTED TO BE | | | EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101 | | | (2003 EDITION) 7.2.1.6.2 ARE MET.PLEASE PROVIDE | | | INFORMATION DETAILING HOW THIS IS ACCOMPLISHED.PLEASE | | | INDICATE WHICH ONE(S) OF THE CRITERIA WILL BE | | | FOLLOWED. | | | | | | NEW COMMENTS | | | | | | 2.SHOW THE LOCATION OF THE EXIT LIGHTS. | | | | | | 3.PLEASE EXPLAIN THE RATIONALE FOR CARD READERS ON | | | ELEVATORS AS SHOWN ON SHEET 1. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-11 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-11 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2007-07-11 15:45:42 | *****UNSAT***** | | | | | | | | | 1.DOORS IN A MEANS OF EGRESS SHALL BE PERMITTED TO BE | | | EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101 | | | (2003 EDITION) 7.2.1.6.2 ARE MET.PLEASE PROVIDE | | | INFORMATION DETAILING HOW THIS IS ACCOMPLISHED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-10 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-10 |
Time |
08:34 |
Sent To |
E |
|
| Notes |
| 2008-01-10 08:34:54 | TO DVP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-12-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-06 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-06 |
Time |
11:41 |
Sent To |
FIRE |
|
| Notes |
| 2007-12-06 11:41:46 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-26 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-26 |
Time |
09:57 |
Sent To |
E |
|
| Notes |
| 2007-10-26 09:57:29 | TO "DPALME" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-13 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-13 |
Time |
13:33 |
Sent To |
E |
|
| Notes |
| 2007-08-13 13:34:15 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-11 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-15 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2007-06-15 14:44:30 | TO "E" BOX |
|
|