| Plan Review Stops For Permit 07060481 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2007-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-10 |
Time |
10:31 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-10 |
Time |
10:31 |
Sent To |
PC |
|
| Notes |
| 2007-07-10 10:34:59 | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | | INGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 2,000 CUBIC FEET REQUIRED. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|