Plan Review Details - Permit 07060415
Plan Review Stops For Permit 07060415
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-15 Cont ID  
Sent By shill Date 2007-09-15 Time 10:08 Rev Time 0.00
Received By shill Date 2007-09-15 Time 10:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-10 Cont ID  
Sent By shill Date 2007-09-10 Time 10:15 Rev Time 0.00
Received By shill Date 2007-09-10 Time 10:15 Sent To  
Notes
2007-09-10 10:18:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 2.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025.
  
 HILLMAN ENGINEERING IS A PHOTOCOPY.MUST BE ORIGINAL.
  
 3.)PLEASE PROVIDE TWO COLLATED IDENTICAL SETS FOR
 PERMIT ISSUANCE.OLD SHEETS SHOULD BE SEPARATE AND
 MARKED "VOID".
  
  
  
 3RD REVIEW - ONLY ONE ORIGINAL WAS PROVIDED.TWO
 IDENTICAL COLLATED SETS (TWO ORIGINAL SETS OF
 ENGINEERING) REQUIRED FOR PERMIT ISSUANCE.
  
 PLEASE PUT TOGETHER TWO IDENTICAL COLLATED SETS FOR
 PERMIT ISSUANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By shill Date 2007-08-30 Time 10:56 Rev Time 0.00
Received By shill Date 2007-08-30 Time 10:56 Sent To  
Notes
2007-08-30 10:58:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025.
  
 HILLMAN ENGINEERING IS A PHOTOCOPY.MUST BE ORIGINAL.
  
  
 NEW COMMENT:
  
 PLEASE PROVIDE TWO COLLATED IDENTICAL SETS FOR PERMIT
 ISSUANCE.OLD SHEETS SHOULD BE SEPARATE AND MARKED
 "VOID".
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 16:54 Rev Time 0.00
Received By shill Date 2007-07-26 Time 16:54 Sent To E
Notes
2007-07-26 17:05:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.THE
 ENGINEER'S CALCULATIONS STATES "SEE ATTACYHED MOUNTING
 DETAILS . . . " BUT NOTHING WAS ATTACHED.
  
 2.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025.
  
 3.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO
 BE ON EACH SHEET.
  
 4.)CALCULATIONS ARE TO BE SIGNED, SEALED AND DATED ON
 EACH SHEET UNLESS AN INDEX SHEET (IN COMPLIANCE WITH
 FAC61G15-23) IS USED, FAC61G15-23.002.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-19 Cont ID  
Sent By btrobaug Date 2009-03-19 Time 08:07 Rev Time 0.00
Received By btrobaug Date 2009-03-19 Time 08:06 Sent To PC
Notes
2009-03-19 08:07:39 
  
  
 REVISION FOR RELOCATION ONLY./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-27 Cont ID  
Sent By btrobaug Date 2008-08-27 Time 13:26 Rev Time 0.00
Received By btrobaug Date 2008-08-27 Time 13:22 Sent To M
Notes
2008-08-27 13:26:25 
  
  
 PROVISO
  
 NFPA-37-4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND
 THEIR WEATHERPROOF HOUSINGS IF PROVIDED, THAT ARE
 INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 1.5 M (5
 FT) FROM OPENINGS IN WALLS AND AT LEAST 1.5 M (5 FT)
 FROM STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE THE FOLLOWING
 CONDITIONS EXIST:
 (1) THE ADJACENT WALL OF THE STRUCTURE HAS A FIRE
 RESISTANCE RATING OF AT LEAST 1 HOUR.
 (2) THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-07-26 Cont ID  
Sent By btrobaug Date 2007-07-26 Time 17:12 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 13:44 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-08-29 Cont ID  
Sent By mperson Date 2007-08-29 Time 14:55 Rev Time 0.00
Received By mperson Date 2007-08-29 Time 14:55 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By mperson Date 2007-07-10 Time 08:05 Rev Time 0.45
Received By mperson Date 2007-07-10 Time 08:05 Sent To B
Notes
2007-07-10 08:10:53DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
 NOTE: FAILED ZONING 6/15/07.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 NOTE: SIGNATURE IS CUT OFF ON THE GAS FLOOR PLAN.
 PLEASE CORRECT ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-03-12 Cont ID  
Sent By adarroug Date 2009-03-12 Time 12:14 Rev Time 0.00
Received By adarroug Date 2009-03-12 Time 12:14 Sent To E
Notes
2009-03-12 12:14:32TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-12 Cont ID  
Sent By btrobaug Date 2008-08-27 Time 13:27 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 15:35 Sent To Z
Notes
2008-08-12 15:36:35TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 12:07 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 12:07 Sent To B
Notes
2007-09-11 12:07:53TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 08:39 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 08:39 Sent To B
Notes
2007-09-06 08:40:18TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 13:52 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 13:52 Sent To Z
Notes
2007-08-22 13:52:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-07-26 Time 13:50 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 10:55 Sent To  
Notes
2007-06-15 10:55:09TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 14:41 Rev Time 0.30
Received By tgordon Date 2008-08-27 Time 14:41 Sent To  
Notes
2008-08-27 15:02:27REVISION TO SITE LOCATION
 *** PROVISO ***
 1) COMPLY WITH GENERAC INSTALLATION INSTRUCTIONS AND
 NFPA 37.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-29 Cont ID  
Sent By tgordon Date 2007-08-29 Time 16:32 Rev Time 0.20
Received By tgordon Date 2007-08-29 Time 16:32 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By tgordon Date 2007-06-20 Time 11:13 Rev Time 0.20
Received By tgordon Date 2007-06-20 Time 11:13 Sent To E
Notes
2007-06-20 11:14:49*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-08-27 Cont ID  
Sent By lfranco Date 2008-08-27 Time 10:15 Rev Time 0.00
Received By lfranco Date 2008-08-27 Time 10:14 Sent To E
Notes
2008-08-27 10:31:23PLANNING AND ZONING: **** PASSED WITH PROVISO ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO THE IBIS RESIDENTIAL PLANNED DEVELOPMENT
 (RPD) REGULATIONS, THE REQUIRED SIDE SETBACK FOR A ZERO
 LOT LINE (ZLL) RESIDENCE IS EIGHT (8) FEET; AND
 PURSUANT TO THE ZONING CODE, SECTION 94-305(B)(4),
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR (4)
 FEET INTO A SETBACK.
  
 THEREFORE, THE GENERATOR?S EDGE SHALL BE A MINIMUM OF
 FOUR (4) FEET FROM THE SIDE PROPERTY LINE.THE PLANS
 SHOW THE GENERATOR AT 42 INCHES FROM THE PROPERTY LINE,
 WHICH IS NOT COMPLYING.IF YOU RESUBMIT FOR OTHER
 FAILED DISCIPLINES, REVISE DRAWINGS ACCORDINGLY TO MEET
 THE REQUIREMENTS.OTHERWISE, ASSURE AT INSTALLATION
 THAT THE LOCATION OF THE GENERATOR WILL MEET SIDE
 SETBACK/INCLUDING ENCROACHMENT REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-23 Cont ID  
Sent By choops Date 2007-08-23 Time 13:34 Rev Time 0.00
Received By choops Date 2007-08-23 Time 13:34 Sent To M
Notes
2007-08-23 13:35:20SENT TO MP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By choops Date 2007-06-15 Time 13:31 Rev Time 0.00
Received By choops Date 2007-06-15 Time 13:31 Sent To E
Notes
2007-06-15 13:37:50***FAILED***
  
  
 1)PLEASE INCLUDE MORE LEGIBLE SETBACK DIMENSIONS TO
 PROPERTY LINES ON THE SURVEYS.NOTE:GENERATOR MUST
 BE A MINIMUM OF 3.5' FROM SIDE PROPERTY LINE,AS PER
 THE CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-305(B)(4) :
  
 (4)MECHANICAL EQUIPMENT.MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK...
  
 (THE REQUIRED SIDE SETBACK FOR THE RESIDENCE IS 7.5'
 ... THEREFORE YOU MAY ENCROACH 4' INTO THAT ... LEAVING
 YOU WITH A SIDE SETBACK OF 3.5' TO THE GENERATOR'S
 EDGE.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720