Plan Review Details - Permit 07060380
Plan Review Stops For Permit 07060380
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-06-25 Cont ID  
Sent By lursu Date 2007-06-25 Time 09:13 Rev Time 0.00
Received By lursu Date 2007-06-12 Time 12:14 Sent To  
Notes
2007-06-25 09:28:04NEW SITE ADDRESS AS 2112 N JOG RD ,WEST PALM BECAH , FL
 ,33411 HAS BEEN ISSUED FOR THE VACANT PARCEL, PCN =
 74424322080050000.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-06-12 12:14:39THIS LOCATION NEEDS AN ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-05 Cont ID  
Sent By jwitmer Date 2007-11-05 Time 13:38 Rev Time 2.22
Received By jwitmer Date 2007-11-05 Time 13:38 Sent To  
Notes
2007-11-05 14:02:49BUILDING PLAN REVIEW
 PERMIT: 07060380
 ADD: 2112 N JOG RD
 CONT: ALTEK STEEL
 TEL: (561)662-8352
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 2ND REQUEST, 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. NOTE SHEET 3.1 INDICATES THIS BUILDING IS
 DESIGNED TO A TYPE IIAFIRE SPRINKLERED BUILDING. IWHEN
 THE DESIGNER DESIGNS A BUILDING TO A MORE RESTRICTIVE
 TYPE OF CONSTRUCTION THAN REQUIRED
 BY CODE, ALL PORTIONS MUST MEET THIS STANDARD.
 PLEASE SEE TABLE 601 FOOTNOTE (C)(2)(I) REQUIRES THE
 TRUSSES, GIRDERS AND ROOF SHEATHING TO BE FIRE
 RETARDANT TREATED WOOD.
 D) COMPLIED.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.PLANS INDICATE
 A FIRE SPRINKLER SYSTEM IS IN THE DESIGN BUT NO FIRE
 SPRINKLER PLANS WERE SUBMITTED. 106.3.5.1.1(5)
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H )SQ. FT. FOOTPRINT
  
 4)BUILDING PROVISO; 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERMORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER.THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 5)BUILDING PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED
 $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 6) COMPLIED.
  
 7) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL
 BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS
 SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A
 METHOD A CALCULATION MAY BE RESUBMITTED. MINIMUM WALL
 AND ROOF INSULATIONS,ETC.
  
 8) COMPLIED.
  
 9) SHEET 2.1 IT APPEARS THIS BUILDING IS TO BE FILLED
 CELL MASONARY THE END WALLS AND THE REAR WALLS APPEAR
 TO MISSING THE REQUIRED FILLED CELLS?
  
 10) SHEET 2.1 PROVIDES A BEAM SCHEDULE AND SHEET A6.1
 PROVIDES BEAM DETAILS, MISSING A BEAM LAYOUT SHEET?
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG
  
 12) NOTE MIAMI DADE REPORTS THAT DO NOT REFER UNDER
 SUB-HEADING # 3 CALCULATIONS TO BEING TESTED OR IN
 COMPLIANCE WITH THE 2004 FBC NEED TO BE REVIEWED BY AN
 ENGINEER,
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 THE OLDER NOA'S WERE TESTED WITH THE 1.33 STEEL FACTORS
 FOR THE FASTENERS WHICH IS NOT ALLOWED UNDER THE 2004
 FBC.
  
 13) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) YKK STOREFRONT, NEEDS FLORIDA COVERSHEET, SEE OLDER
 REPORT WILL NEED VARIFICATION OF FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. B)
 YKK 20 D NARROW STILE OUTSWING DOOR, OLDER REPORT WILL
 NEED VARIFICATION OF THE FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. C)
 MISSING THE REAR DOORS, HOLLOW METAL DOORS
 D) STORM SHUTTERS SEE COMMENTS BELOW FOR STORM
 SHUTTERS
 E) ROOFING ASSEMBLIES
 E1) MODIFIED, MISSING FLORIDA REPORT, SUBSYSTEMS TO BE
 USED IS NOT HIGHLIGHTED, SEE LIMITATION 7 OR 9!
 E2) MONIER TILE, MISSING FLORIDA COVER SHEET, INDICATE
 ON SHEET 4 OR 5 WHICH TYPE OF FASTENING SYSTEM TO BE
 USED.
 F) TRUSS ANCHORS
 G) WALL LOUVERS
  
 14) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. FBC 1606.1.4.FL BLD
 CODE 2004 SECTION 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES:
 1(B) A COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TOPALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By jwitmer Date 2007-07-19 Time 21:24 Rev Time 1.22
Received By jwitmer Date 2007-07-19 Time 21:07 Sent To  
Notes
2007-07-19 22:35:16BUILDING PLAN REVIEW
 PERMIT: 07060380
 ADD: 2112 N JOG RD
 CONT: ALTEK STEEL
 TEL: (561)662-8352
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.EVEN SHELL BUILDINGS!
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H )SQ. FT. FOOTPRINT
  
 4)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERMORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER.THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 5)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED
 $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 6) SHEET 5.1 INDICATES ROOF DRAINS BUT THERE ARE NO
 SECONDARY OREMERGENCY OVERFLOWS, ALSO PLAN INDICATES
 DOWN SPOUT BUT ON SHEET 4.1 THERE IS NO DOWNSPOUT OR
 RAIN LEADERS SHOWN.
 1503.4.1 GUTTERS.
 GUTTERS AND LEADERS PLACED ON THE OUTSIDE OF BUILDINGS,
 OTHER THAN GROUP R-3 AS APPLICABLE IN SECTION 101.2 ,
 PRIVATE GARAGES AND BUILDINGS OF TYPE V CONSTRUCTION,
 SHALL BE OF NONCOMBUSTIBLE MATERIAL OR A MINIMUM OF
 SCHEDULE 40 PLASTIC PIPE.
  
 1503.4.3 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL
 BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS
 SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A
 METHOD A CALCULATION MAY BE RESUBMITTED. MINIMUM WALL
 AND ROOF INSULATIONS,ETC.
  
 8) DISCREPANCY BETWEEN THE LIFE SAFETY PLAN AND SHEET
 3.1, MISSING THE REAR DOORS?
  
 9) SHEET 2.1 IT APPEARS THIS BUILDING IS TO BE FILLED
 CELL MASONARY THE END WALLS AND THE REAR WALLS APPEAR
 TO MISSING THE REQUIRED FILLED CELLS?
  
 10) SHEET 2.1 PROVIDES A BEAM SCHEDULE AND SHEET A6.1
 PROVIDES BEAM DETAILS, MISSING A BEAM LAYOUT SHEET?
  
 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG
  
 12) NOTE MIAMI DADE REPORTS THAT DO NOT REFER UNDER
 SUB-HEADING # 3 CALCULATIONS TO BEING TESTED OR IN
 COMPLIANCE WITH THE 2004 FBC NEED TO BE REVIEWED BY AN
 ENGINEER,
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 THE OLDER NOA'S WERE TESTED WITH THE 1.33 STEEL FACTORS
 FOR THE FASTENERS WHICH IS NOT ALLOWED UNDER THE 2004
 FBC.
  
 13) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) YKK STOREFRONT, NEEDS FLORIDA COVERSHEET, SEE OLDER
 REPORT WILL NEED VARIFICATION OF FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. B)
 YKK 20 D NARROW STILE OUTSWING DOOR, OLDER REPORT WILL
 NEED VARIFICATION OF THE FASTENERS OR TAKE THE
 REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. C)
 MISSING THE REAR DOORS, HOLLOW METAL DOORS
 D) STORM SHUTTERS SEE COMMENTS BELOW FOR STORM
 SHUTTERS
 E) FOOFING ASSEMBLIES
 E1) MODIFIED, MISSING FLORIDA REPORT, SUBSYSTEMS TO BE
 USED IS NOT HIGHLIGHTED, SEE LIMITATION 7 OR 9! E2)
 MONIER TILE, MISSING FLORIDA COVER SHEET, INDICATE ON
 SHEET 4 OR 5 WHICH TYPE OF FASTENING SYSTEM TO BE
 USED.
  
 14) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. FBC 1606.1.4.FL BLD
 CODE 2004 SECTION 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES:
 1(B) A COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TOPALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-30 Cont ID  
Sent By dpalmer Date 2007-10-30 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2007-10-30 Time 12:07 Sent To  
Notes
2007-10-30 13:45:09 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE IN
 NEED OF ADDRESSING ALONG WITH NEW COMMENT AS NEW
 INFORMATION IS ONLY NOW BEING SUBMITTED FOR REVIEW.
  
  
  
 1) NOTE: PLEASE KNOW AS PER FS 481.229, PLANS AND
 DOCUMENTS MAY NOT BE DONE BY A *DESIGNER* WHO IS NOT
 LICENSED UNDER FS 481 OR 471.
 PLEASE SEE THIS ALSO INCLUDES DESIGNS FOR ENERGY
 CALCULATIONS.
 PLEASE CONTACT THE BOARD OF ARCHITECTS PROSECUTING
 ATTORNEY MR. DAVID MINACCI FOR ANY QUESTIONS REGARDING
 THIS.
 BY REVISING A TITLE BLOCK DOES NOT ALLEVIATE OR CHANGE
 THE STATUTES WHICH IS IN EFFECT.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED
 ENERGY CALCULATIONS AS REQUIRED PER 13-101.1.6 HOWEVER
 AS CALCULATIONS HAS NOW BEEN SUBMITTED AND THEY DO NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE LIGHTING ON PLANS NEEDS TO BE SPECIFIC
 AND THE ASSUMED ALLOWANCES FOR INTERIOR LIGHTING NEEDS
 TO BE FIGURED.
 PLEASE SEE THE CALCULATIONS ALSO DO NOT INCLUDE ANY
 EXTERIOR LIGHTING WHICH IS NOT POSSIBLE WHEN THE PLANS
 DO HAVE AND CONTAIN EXTERIOR LIGHTING.
 PLEASE SEE ONLY ONE COPY OF CALCULATIONS WERE SUBMITTED
 WHEN TWO SIGNED, DATED AND SEALED SETS ARE REQUIRED.
 PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED.
 PLEASE SEE NOTES ABOVE IN NOTE #1.
  
 3) NOTE: PLEASE SEE PROVIDE THE SPECIFIC INFORMATION ON
 THE FIXTURES WHICH ARE BEING INSTALLED. PLANS MENTIONS
 THESE ARE TO BE SELECTED BY THE OWNER HOWEVER THESE IS
 REQUIRED AT THIS TIME.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE MENTIONED
 ELECTRICAL LIGHTING CONTROLS FOR INTERIOR LIGHTING. THE
 RESPONSE MENTIONS THIS WILL BE DONE HOWEVER COULD NOT
 LOCATE ANY CONTROL DEVICES.
 FBC 13-415.1.ABC.1.1, 13-415.1.ABC.1.2.
  
 ** PLEASE SEE ANY POSSIBLE CODES FROM OTHER REVIEWER(S)
 WHICH MAY BE REQUESTED.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By dpalmer Date 2007-06-26 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2007-06-26 Time 18:19 Sent To  
Notes
2007-06-26 18:48:47 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 STATED ON ARCHITECTURAL SHEETS ALSO. MOST ARE ALREADY
 STATED ON THE E-1 SHEET.
 PLEASE SEE PLANS MENTIONS THE *PALM BEACH COUNTY
 AMENDMENTS* AND THIS PROJECT IS LOCATED IN THE CITY OF
 WEST PALM BEACH.
 PLEASE ADJUST.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 ** PLEASE SEE ANY POSSIBLE CODES FROM OTHER REVIEWER(S)
 WHICH MAY BE REQUESTED.
  
 2) NOTE: PLEASE KNOW THAT THE SPACE EVEN AS A SHELL
 WILL BE REQUIRED TO CONTAIN INTERIOR LIGHTING FOR
 INGRESS/EGRESS IN SPACE. THESE MAY BE CONTROLLED BY OS
 DEVICES OR MANUAL SWITCHES AS ENTRANCE/EXIT LOCATIONS.
  
 PLEASE SEE THIS WILL ALSO BE REQUIRED BY THE FIRE
 MARSHAL'S OFFICE.
 NFPA-101 7.8. THE EMERGENCY BATTERY BACK UP LIGHTS
 SHOWN ON PLANS ARE OK FOR LOSS OF POWER.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUIRED
 FOR NEW BUILDINGS.
 PLEASE SEE METHOD FOR SHELL SPACES. 13-415.1.AB.1.1,
 13-415.2
  
 4) NOTE: PLEASE LABEL MAINS PER 230.2E : EXAMPLE, MAIN
 1OF3, MAIN 2 OF 3 ETC.
  
 5) NOTE:PLEASE SEE THAT NOW THAT AN ADDRESS HAS BEEN
 ASSIGNED. PLEASE BE SURE TO REVISE THE TITLE BLOCKS FOR
 NEW ADDRESS WHICH WAS ASSIGNED AS 2112 N. JOG RD. **
 PLEASE BE SURE TO ALSO REVISE THE PERMIT APPLICATION. A
 NEW PERMIT APPLICATION WILL BE ATTACHED TO NOTES FOR
 CONVENIENCE AS THERE ARE SEVERAL ITEMS ON PERMIT
 APPLICATION WHICH ARE NOT VISIBLE.
 FAC 61G1-16.004, 61G15-23.002
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-11-01 Cont ID  
Sent By rchokshi Date 2007-11-01 Time 14:20 Rev Time 0.00
Received By rchokshi Date 2007-11-01 Time 13:32 Sent To  
Notes
2007-11-01 14:20:38***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1.PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE AND THEIR DETAILSPER CITY OF WPB,
 LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 PERYOUR RESPONSE OF 8/8/07, SITE PLAN SHEET 1.1 OR
 2 OF 9 DO NOT SHOW NEITHER LOCATION NOR DETAILS OF
 DUMPSTER.
 2.MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 YOURRESPONSE OF 8/8/07WAS: "THE SITE AREAS
 .....ARE CORRECT...." .OUR RESPONSE TO YOU:INFACT
 AREA SHOWN ON SITE PLAN SHEET 1.1NOT CONSISTENT WITH
 POST DEVELOPMENT SITE AREAS SHOWN ON SHEET 1 OF 2.FOR
 EXAMPLE ON SITE PLAN SHEET 1.1 TOTAL AREA 75503 SQ FT,
 AND PERVIOUS AREA 5616 SQ FT WHILEYOU HAVE SHOWN ON
 CALCULATION SHEET 1 OF 2TOTAL SITE AREA 17189 SQ FT
 AND PERVIOUS AREA 6870 SQ FTAND SO FORTH INCONSISTENT
 IN IMPERVIOUS AREA ALSO.
 3. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER CATCH
 BASINS DRAINS AROUND YOUR SITE
 4.THESTORM STORM WATER QUALITY CALCULATIONS MUST BE
 APPROVED FROM 1000 45TH STREET, ENGINEERING,BEFORE WE
 ISSUE A PERMIT.
 5. PER CITY ORDINANCE NO. 4060-07,PLEASE SHOW ON
 DRAWINGS THE POLLUTION PREVENTION SILT AROUND THE SITE
 & CATCH BASINS DURING CONSTRUCTION AND DURING ALL
 DEMOLITION.HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER
 FDEP TO STOP DUST & PARTICLES.
 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE ISSUE A
 PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By rchokshi Date 2007-07-12 Time 13:32 Rev Time 0.00
Received By rchokshi Date 2007-07-12 Time 13:21 Sent To  
Notes
2007-07-12 13:32:21***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE AND THEIR DETAILSPER CITY OF WPB,
 LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 PLEASE SHOW IN YOUR STORM WATER QUALITY CALS.
 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, DO YOU HAVE DRY/WET POND?
 IF YOU DO,PLEASE SHOW DRY DETENTION/WET DETENTION
 AREAS WITH 100% FILL OF STORM WATER ELEVATION. WHERE
 THE STORM WATER GOES AFTER BLEEDING, IN CITY CANAL, OR
 SFWMD CANAL??
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE.
 7. PLEASE PROVIDE A COPY OF NPBID PERMIT,, AND A
 LATESTEST COPY OF STORM STORM WATER QUALITY
 CALCULATIONS SHOWING THE WORST CRITERIA TO CALCULATE
 QUALITY CALSTHAT YOU PROVIDED AT 45TH STREET.
 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 SILT AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS
 THAT WERE APPROVED AT 45TH STREET.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-07 Cont ID  
Sent By mawillia Date 2007-11-07 Time 17:36 Rev Time 0.00
Received By mawillia Date 2007-11-07 Time 17:00 Sent To  
Notes
2007-11-07 17:35:52*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 02.ALL FIRE LINES/FIRE HYDRANT(S) TO BE INSTALLED AND
 IN WORKING CONDITION BEFORE, DURING, AND AFTER BUILDING
 CONSTRUCTION.SHOW THE LOCATION OF THE NEAREST FIRE
 HYDRANT(S) TO THE PROPOSED STRUCTURE
  
 09.THE PROJECT DATA ON SHEET 3.1 STATES THAT THERE
 ARE FOUR (4) EXITS, WHEREAS THE LIFE SAFETY SUMMARY ON
 SHEET 7.1 LISTS TWO (2) EXIT DOORS.PLEASE INCLUDE THE
 ACTUAL NUMBER OF EXITS IN THE PROJECT DATA (SHEET 3.1)
 AND LIFE SAFETY SUMMARY (SHEET 7.1) AS ILLUSTRATED ON
 SHEET 7.1
  
 10.IT IS STATED THAT THE BUILDING WILL BE
 SPRINKLERED.IN THE EVENT OF A FIRE, HOW AND WHERE
 WILL WATER BE INTRODUCED INTO THE BUILDING?S
  
 11.AS IT RELATES TO THIS SPRINKLERED BUILDING, HOW
 WILL NOTIFICATION FOR EMERGENCY RESPONSE BE
 ACCOMPLISHED IN THE ACTIVATION OF THE SPRINKLER
 SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE(ON THE PLAN) EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 13:26 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 11:54 Sent To  
Notes
2007-07-26 13:25:52*****DENIED*****
  
  
 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 02.ALL FIRE LINES/FIRE HYDRANT(S) TO BE INSTALLED AND
 IN WORKING CONDITION BEFORE, DURING, AND AFTER BUILDING
 CONSTRUCTION.
  
 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES,
 ETC).
  
 06.ON THE APPROPIATE EXTERIOR ELEVATION, POSTS THE
 NUMERICAL ADDRESS TO BE VISIBLE FROM NORTH JOG ROAD. AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION AT THE MAIN
 ENTRANCE, SHOW/DISPLAY THE DISTINGUISHABLE SUITE
 NUMBER.AS PER WEST PALM BEACH CODE, THE UNIT NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.IF THE SUITE/UNIT HAS AN EXTERIOR DOOR, AN
 UNIT NUMBER SHALL ALSO BE POSTED.
  
 08.ON SHEET 7.1, NO EXIT DOORS ARE SHOWN ON THE WEST
 ELEVATION;HOWEVER, ON SHEET 4.1, DOORS ARE SHOWN ON
 THIS ELEVATION.PLEASE EXPLAIN.
  
 09.THE PROJECT DATA ON SHEET 3.1 STATES THAT THERE
 ARE FOUR (4) EXITS, WHEREAS THE LIFE SAFETY SUMMARY ON
 SHEET 7.1 LISTS TWO (2) EXIT DOORS.PLEASE EXPLAIN.
  
 10.IT IS STATED THAT THE BUILDING WILL BE
 SPRINKLERED.IN THE EVENT OF A FIRE, HOW AND WHERE
 WILL WATER BE INTRODUCED INTO THE BUILDING?
  
 11.AS IT RELATES TO THIS SPRINKLERED BUILDING, HOW
 WILL NOTIFICATION FOR EMERGENCY RESPONSE BE
 ACCOMPLISHED IN THE ACTIVATION OF THE SPRINKLER
 SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE(ON THE PLAN) EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 16:10 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 16:10 Sent To  
Notes
2007-10-29 08:34:01TO "COMM" BD#20
2007-10-10 16:10:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 11:54 Rev Time 0.00
Received By mawillia Date 2007-06-13 Time 16:56 Sent To  
Notes
2007-06-26 09:20:10TO "COMM" BD#11
2007-06-13 16:56:12WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-17 Cont ID  
Sent By rregueir Date 2007-11-17 Time 14:34 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 13:32 Sent To  
Notes
2007-11-17 13:51:36REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. ENERGY CALCULATIONS:
 A) PROJECT SUMMARY STATES THIS IS A NEW FINISHED
 BUILDING, BUT PLANS INDICATES THIS IS A SHELL BUILDING.
 PLEASE COORDINATE PLANS AND CALCULATIONS.
 B) ENERGY CALCULATIONS ARE TO BE CERTIFIED BY THE
 OWNER, PROJECT ARCHITECT (REGISTERED IN THE STATE OF
 FLORIDA), OR OTHER OFFICIALLY DESIGNATED AGENT ALLOWED
 IN SECTION 103.2 IN ACCORDANCE WITH FBC 13-103.1
 C)MANUAL J INCLUDED WITH ENERGY CALCULATIONS INDICATE
 BARE CONCRETE BLOCK WALLS WITH INSULATION VALUE OF
 R-11. WHAT IS THE BASIS FOR THIS VALUE? MANUAL J ALSO
 INDICATES A METAL DECK ROOF WITH 3 INCHES OF INSULATION
 WITH A VALUE OF R-19. WHAT IS THE BASIS FOR THIS
 VALUE?
 D) THE VALUES USED IN THE MANUAL J AND THE ENERGY
 CALCULATIONS SHALL BE SHOWN ON PLANS, IN SUFFICIENT
 DETAIL, INCLUDING ALL PERTINENT DATA AND FEATURES OF
 THE BUILDING AND THE EQUIPMENT AND SYSTEMS AS HEREIN
 GOVERNED INCLUDING, BUT NOT LIMITED TO: DESIGN
 CRITERIA, EXTERIOR ENVELOPE COMPONENT MATERIALS,
 U-VALUES OF THE ENVELOPE SYSTEMS, R-VALUES OF
 INSULATING MATERIALS, SIZE AND TYPE OF APPARATUS AND
 EQUIPMENT, EQUIPMENT AND SYSTEMS CONTROLS AND OTHER
 PERTINENT DATA TO INDICATE CONFORMANCE WITH THE
 REQUIREMENTS OF THIS CODE. FBC 13-103.2
  
 2. SEE PLUMBING CODE FOR MINIMUM FACILITIES REQUIRED.
  
 3. MANUAL J SHOWS 300 CFM OF VENTILATION AIR FOR EACH
 SYSTEM. WHAT IS THE BASIS FOR THIS NUMBER? PREVIOUS
 REVIEW REQUESTED OUTSIDE AIR CALCULATIONS BASED ON
 FBC,M TABLE 403.3. NONE WERE PROVIDED. OUTSIDE AIR
 CALCULATIONS SHALL BE BASED ON OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD AND CFM/PERSON AS
 REQUIRED BY TABLE 403.3. SHOE THE MINIMUM REQUIRED
 OUTSIDE AIR RATE FOR THIS SPACE AND SHOW CORRELATION
 WITH MANUAL J FOR PROPER SYSTEM SIZING.
  
 NEW COMMENT: WALL LOUVERS HAVE BEEN ADDED TO THE
 DRAWINGS. LOUVERS ARE GOVERNED BY FAC RULE 9B-72 AND AS
 SUCH, PRODUCT APPROVAL IS REQUIRED. SUBMIT TWO COPIES
 OF THE PRODUCT APPROVAL FOR THE SPECIFIC BRAND OF
 LOUVER TO BE USED. FOR MORE INFORMATION ON THE FLORIDA
 PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By rregueir Date 2007-07-13 Time 11:18 Rev Time 0.00
Received By rregueir Date 2007-07-13 Time 09:56 Sent To  
Notes
2007-07-13 11:18:20--------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO MECHANICAL INFORMATION WAS PROVIDED ASIDE FROM
 THE ROOF PLAN SHOWS 3 RTU'S.PLEASE SEE THE MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS AS
 REQUIRED BY FBC 106.3.5.
  
 2. FLOOR PLAN SHOWS PROVISIONS FOR TWO TOILET ROOMS.
 PLEASE SHOW PROVISIONS FOR MECHANICAL EHAUST PER FBC,M
 TABLE 403.3.
  
 3. PLEASE SHOW OUTDOOR AIR CALCULATINS INCLUDING
 OCCUPANCY CLASIFICATIONS, OCCUPANT LOAD AND OUTDOOR AIR
 REQUIRED PER FBC, M 403.3.
  
 NOTE: ADDITIONAL COMMENTS ARE POSSIBLE BASED ON NEW
 INFORMATION WHICH MAY BE PROVIDED FOR NEXT REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 16:12 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 16:12 Sent To  
Notes
2007-12-04 16:13:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ******SHELL ONLY******
  
 ****FROM PREVIOUS REVIEW:
  
 1.OK
 2. OK
 3. OK
 4. OK
  
 5. SHT 5.1 THREE RTU'S ON THE ROOF. PLEASE INDICATE IF
 THERE WILL BE CONDENSATE DRAINING FROM THESE UNITS. IF
 SO PLEASE INDICATE METHOD OF DRAINING FROM THE ROOF.
 ****NO RESPONSE, NOT ADDRESSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 13:17 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 13:17 Sent To  
Notes
2007-07-14 13:38:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ******SHELL ONLY******
  
 1.SHT 3.1 ALTHOUGH THIS IS A SHELL ONLY, NO
 PROVISIONS ARE INDICATED FOR THE REQUIRED DRINKING
 FOUNTAIN. SECTION 403.1. PLEASE BE ADVISED THAT A
 DRINKING FOUNTAIN IS REQUIRED.
  
 2. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE OF
 THE BUILDING. SECTION 608.13.2. PLEASE INDICATE ON
 PLANS.
  
 3. SHT 4.1 WEST ELEVATION DOES NOT SHOW DOWNSPOUTS
 INDICATED ON SHT 5.1 ROOF PLAN. PLEASE CORRELATE
 INFORMATION FROM ELEVATION AND ROOF PLAN. SECTION
 106.1.1.
  
 4. SHT 5.1 SECONDARY ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTURCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON/ SECTION 1107.1 PLEASE INDICATE THE LOCATION OF
 THE SECONDARY ROOF DRAINS/SCUPPERS.--SEPARATE
 SYSTEMS ARE REQUIRED PER SECTION 1107.2.
  
 5. SHT 5.1 THREE RTU'S ON THE ROOF. PLEASE INDICATE IF
 THERE WILL BE CONDENSATE DRAINING FROM THESE UNITS. IF
 SO PLEASE INDICATE METHOD OF DRAINING FROM THE ROOF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By kdfreema Date 2007-06-19 Time 15:57 Rev Time 0.00
Received By kdfreema Date 2007-06-19 Time 15:57 Sent To  
Notes
2007-06-19 15:58:57NO LANDSCAPE PLAN WAS SUBMITTED, PLEASE MAKE SURE TO
 INCLUDE IT WHEN YOU RESUBMIT.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.