Plan Review Details - Permit 07060380
| Plan Review Stops For Permit 07060380 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2007-06-25 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-06-25 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-06-12 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2007-06-25 09:28:04 | NEW SITE ADDRESS AS 2112 N JOG RD ,WEST PALM BECAH , FL | | | ,33411 HAS BEEN ISSUED FOR THE VACANT PARCEL, PCN = | | | 74424322080050000. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] | | 2007-06-12 12:14:39 | THIS LOCATION NEEDS AN ADDRESS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-05 |
Time |
13:38 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-11-05 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2007-11-05 14:02:49 | BUILDING PLAN REVIEW | | | PERMIT: 07060380 | | | ADD: 2112 N JOG RD | | | CONT: ALTEK STEEL | | | TEL: (561)662-8352 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) 2ND REQUEST, 110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR | | | CERTIFICATE OF OCCUPANCY: | | | A) COMPLIED. | | | B) COMPLIED. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. NOTE SHEET 3.1 INDICATES THIS BUILDING IS | | | DESIGNED TO A TYPE IIAFIRE SPRINKLERED BUILDING. IWHEN | | | THE DESIGNER DESIGNS A BUILDING TO A MORE RESTRICTIVE | | | TYPE OF CONSTRUCTION THAN REQUIRED | | | BY CODE, ALL PORTIONS MUST MEET THIS STANDARD. | | | PLEASE SEE TABLE 601 FOOTNOTE (C)(2)(I) REQUIRES THE | | | TRUSSES, GIRDERS AND ROOF SHEATHING TO BE FIRE | | | RETARDANT TREATED WOOD. | | | D) COMPLIED. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) | | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED.PLANS INDICATE | | | A FIRE SPRINKLER SYSTEM IS IN THE DESIGN BUT NO FIRE | | | SPRINKLER PLANS WERE SUBMITTED. 106.3.5.1.1(5) | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | H )SQ. FT. FOOTPRINT | | | | | | 4)BUILDING PROVISO; 109.3.10* IMPACT OF CONSTRUCTION. | | | ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL | | | BE PERMORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT | | | THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT | | | TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER | | | TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY | | | OWNER.THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL | | | OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS | | | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, | | | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | | FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED | | | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE | | | FINAL INSPECTION. | | | | | | 5)BUILDING PROVISO:109.3.10.1 HURRICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW | | | CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO | | | REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND | | | DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION | | | SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE | | | DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND | | | DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR | | | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS | | | WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED | | | $500.00. IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT | | | TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 6) COMPLIED. | | | | | | 7) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL | | | BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS | | | SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C. | | | ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A | | | METHOD A CALCULATION MAY BE RESUBMITTED. MINIMUM WALL | | | AND ROOF INSULATIONS,ETC. | | | | | | 8) COMPLIED. | | | | | | 9) SHEET 2.1 IT APPEARS THIS BUILDING IS TO BE FILLED | | | CELL MASONARY THE END WALLS AND THE REAR WALLS APPEAR | | | TO MISSING THE REQUIRED FILLED CELLS? | | | | | | 10) SHEET 2.1 PROVIDES A BEAM SCHEDULE AND SHEET A6.1 | | | PROVIDES BEAM DETAILS, MISSING A BEAM LAYOUT SHEET? | | | | | | 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE | | | PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN | | | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC | | | FORM PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG | | | | | | 12) NOTE MIAMI DADE REPORTS THAT DO NOT REFER UNDER | | | SUB-HEADING # 3 CALCULATIONS TO BEING TESTED OR IN | | | COMPLIANCE WITH THE 2004 FBC NEED TO BE REVIEWED BY AN | | | ENGINEER, | | | 1605.3.1.1 LOAD REDUCTION. | | | 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT | | | OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE | | | EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN | | | SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD | | | LOAD AND ANY OF THE VARIABLE LOADS. | | | 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE | | | MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED | | | STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD | | | COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD | | | INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER | | | 23 . | | | THE OLDER NOA'S WERE TESTED WITH THE 1.33 STEEL FACTORS | | | FOR THE FASTENERS WHICH IS NOT ALLOWED UNDER THE 2004 | | | FBC. | | | | | | 13) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) YKK STOREFRONT, NEEDS FLORIDA COVERSHEET, SEE OLDER | | | REPORT WILL NEED VARIFICATION OF FASTENERS OR TAKE THE | | | REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. B) | | | YKK 20 D NARROW STILE OUTSWING DOOR, OLDER REPORT WILL | | | NEED VARIFICATION OF THE FASTENERS OR TAKE THE | | | REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. C) | | | MISSING THE REAR DOORS, HOLLOW METAL DOORS | | | D) STORM SHUTTERS SEE COMMENTS BELOW FOR STORM | | | SHUTTERS | | | E) ROOFING ASSEMBLIES | | | E1) MODIFIED, MISSING FLORIDA REPORT, SUBSYSTEMS TO BE | | | USED IS NOT HIGHLIGHTED, SEE LIMITATION 7 OR 9! | | | E2) MONIER TILE, MISSING FLORIDA COVER SHEET, INDICATE | | | ON SHEET 4 OR 5 WHICH TYPE OF FASTENING SYSTEM TO BE | | | USED. | | | F) TRUSS ANCHORS | | | G) WALL LOUVERS | | | | | | 14) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION | | | WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. FBC 1606.1.4.FL BLD | | | CODE 2004 SECTION 103.6, 1606.1.4, 1707.4 & 3401.7.2.4. | | | PROCEDURES: | | | 1(B) A COMPLETE INSTALLATION SCHEDULE SUMMARIZING & | | | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT | | | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT | | | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | | | | 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TOPALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE | | | CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-19 |
Time |
21:24 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-07-19 |
Time |
21:07 |
Sent To |
|
|
| Notes |
| 2007-07-19 22:35:16 | BUILDING PLAN REVIEW | | | PERMIT: 07060380 | | | ADD: 2112 N JOG RD | | | CONT: ALTEK STEEL | | | TEL: (561)662-8352 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3.EVEN SHELL BUILDINGS! | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) | | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT | | | H )SQ. FT. FOOTPRINT | | | | | | 4)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERMORMED IN A | | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS | | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER.THIS | | | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, | | | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS | | | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, | | | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | | FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED | | | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE | | | FINAL INSPECTION. | | | | | | 5)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE | | | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED | | | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. | | | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH | | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE | | | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN | | | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH | | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY | | | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE | | | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 | | | HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED | | | $500.00. IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT | | | TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 6) SHEET 5.1 INDICATES ROOF DRAINS BUT THERE ARE NO | | | SECONDARY OREMERGENCY OVERFLOWS, ALSO PLAN INDICATES | | | DOWN SPOUT BUT ON SHEET 4.1 THERE IS NO DOWNSPOUT OR | | | RAIN LEADERS SHOWN. | | | 1503.4.1 GUTTERS. | | | GUTTERS AND LEADERS PLACED ON THE OUTSIDE OF BUILDINGS, | | | OTHER THAN GROUP R-3 AS APPLICABLE IN SECTION 101.2 , | | | PRIVATE GARAGES AND BUILDINGS OF TYPE V CONSTRUCTION, | | | SHALL BE OF NONCOMBUSTIBLE MATERIAL OR A MINIMUM OF | | | SCHEDULE 40 PLASTIC PIPE. | | | | | | 1503.4.3 OVERFLOW SCUPPERS. | | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT | | | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR | | | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 | | | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND | | | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED | | | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET | | | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN | | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. | | | | | | 1503.6 PROTECTION AGAINST DECAY AND TERMITES. | | | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT | | | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, | | | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR | | | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON | | | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) | | | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON | | | A ROOF ABOVE ANOTHER ROOF. | | | | | | 7) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL | | | BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS | | | SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C. | | | ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN, A | | | METHOD A CALCULATION MAY BE RESUBMITTED. MINIMUM WALL | | | AND ROOF INSULATIONS,ETC. | | | | | | 8) DISCREPANCY BETWEEN THE LIFE SAFETY PLAN AND SHEET | | | 3.1, MISSING THE REAR DOORS? | | | | | | 9) SHEET 2.1 IT APPEARS THIS BUILDING IS TO BE FILLED | | | CELL MASONARY THE END WALLS AND THE REAR WALLS APPEAR | | | TO MISSING THE REQUIRED FILLED CELLS? | | | | | | 10) SHEET 2.1 PROVIDES A BEAM SCHEDULE AND SHEET A6.1 | | | PROVIDES BEAM DETAILS, MISSING A BEAM LAYOUT SHEET? | | | | | | 11)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE | | | PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN | | | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC | | | FORM PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG | | | | | | 12) NOTE MIAMI DADE REPORTS THAT DO NOT REFER UNDER | | | SUB-HEADING # 3 CALCULATIONS TO BEING TESTED OR IN | | | COMPLIANCE WITH THE 2004 FBC NEED TO BE REVIEWED BY AN | | | ENGINEER, | | | 1605.3.1.1 LOAD REDUCTION. | | | 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT | | | OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE | | | EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN | | | SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD | | | LOAD AND ANY OF THE VARIABLE LOADS. | | | 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE | | | MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED | | | STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD | | | COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD | | | INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER | | | 23 . | | | THE OLDER NOA'S WERE TESTED WITH THE 1.33 STEEL FACTORS | | | FOR THE FASTENERS WHICH IS NOT ALLOWED UNDER THE 2004 | | | FBC. | | | | | | 13) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) YKK STOREFRONT, NEEDS FLORIDA COVERSHEET, SEE OLDER | | | REPORT WILL NEED VARIFICATION OF FASTENERS OR TAKE THE | | | REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. B) | | | YKK 20 D NARROW STILE OUTSWING DOOR, OLDER REPORT WILL | | | NEED VARIFICATION OF THE FASTENERS OR TAKE THE | | | REDUCTION, 1605.3.1.1. ONLY ONE REPORT SUBMITTED. C) | | | MISSING THE REAR DOORS, HOLLOW METAL DOORS | | | D) STORM SHUTTERS SEE COMMENTS BELOW FOR STORM | | | SHUTTERS | | | E) FOOFING ASSEMBLIES | | | E1) MODIFIED, MISSING FLORIDA REPORT, SUBSYSTEMS TO BE | | | USED IS NOT HIGHLIGHTED, SEE LIMITATION 7 OR 9! E2) | | | MONIER TILE, MISSING FLORIDA COVER SHEET, INDICATE ON | | | SHEET 4 OR 5 WHICH TYPE OF FASTENING SYSTEM TO BE | | | USED. | | | | | | 14) STORM SHUTTERS: PROVIDE STORM PANEL INFORMATION | | | WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. FBC 1606.1.4.FL BLD | | | CODE 2004 SECTION 103.6, 1606.1.4, 1707.4 & 3401.7.2.4. | | | PROCEDURES: | | | 1(B) A COMPLETE INSTALLATION SCHEDULE SUMMARIZING & | | | IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT | | | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT | | | APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | | | | 15)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TOPALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-30 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-30 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2007-10-30 13:45:09 | | | | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE IN | | | NEED OF ADDRESSING ALONG WITH NEW COMMENT AS NEW | | | INFORMATION IS ONLY NOW BEING SUBMITTED FOR REVIEW. | | | | | | | | | | | | 1) NOTE: PLEASE KNOW AS PER FS 481.229, PLANS AND | | | DOCUMENTS MAY NOT BE DONE BY A *DESIGNER* WHO IS NOT | | | LICENSED UNDER FS 481 OR 471. | | | PLEASE SEE THIS ALSO INCLUDES DESIGNS FOR ENERGY | | | CALCULATIONS. | | | PLEASE CONTACT THE BOARD OF ARCHITECTS PROSECUTING | | | ATTORNEY MR. DAVID MINACCI FOR ANY QUESTIONS REGARDING | | | THIS. | | | BY REVISING A TITLE BLOCK DOES NOT ALLEVIATE OR CHANGE | | | THE STATUTES WHICH IS IN EFFECT. | | | | | | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED | | | ENERGY CALCULATIONS AS REQUIRED PER 13-101.1.6 HOWEVER | | | AS CALCULATIONS HAS NOW BEEN SUBMITTED AND THEY DO NOT | | | CORRELATE WITH PLANS. | | | PLEASE SEE THE LIGHTING ON PLANS NEEDS TO BE SPECIFIC | | | AND THE ASSUMED ALLOWANCES FOR INTERIOR LIGHTING NEEDS | | | TO BE FIGURED. | | | PLEASE SEE THE CALCULATIONS ALSO DO NOT INCLUDE ANY | | | EXTERIOR LIGHTING WHICH IS NOT POSSIBLE WHEN THE PLANS | | | DO HAVE AND CONTAIN EXTERIOR LIGHTING. | | | PLEASE SEE ONLY ONE COPY OF CALCULATIONS WERE SUBMITTED | | | WHEN TWO SIGNED, DATED AND SEALED SETS ARE REQUIRED. | | | PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED. | | | PLEASE SEE NOTES ABOVE IN NOTE #1. | | | | | | 3) NOTE: PLEASE SEE PROVIDE THE SPECIFIC INFORMATION ON | | | THE FIXTURES WHICH ARE BEING INSTALLED. PLANS MENTIONS | | | THESE ARE TO BE SELECTED BY THE OWNER HOWEVER THESE IS | | | REQUIRED AT THIS TIME. | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE MENTIONED | | | ELECTRICAL LIGHTING CONTROLS FOR INTERIOR LIGHTING. THE | | | RESPONSE MENTIONS THIS WILL BE DONE HOWEVER COULD NOT | | | LOCATE ANY CONTROL DEVICES. | | | FBC 13-415.1.ABC.1.1, 13-415.1.ABC.1.2. | | | | | | ** PLEASE SEE ANY POSSIBLE CODES FROM OTHER REVIEWER(S) | | | WHICH MAY BE REQUESTED. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-26 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-26 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2007-06-26 18:48:47 | | | | | | | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE | | | STATED ON ARCHITECTURAL SHEETS ALSO. MOST ARE ALREADY | | | STATED ON THE E-1 SHEET. | | | PLEASE SEE PLANS MENTIONS THE *PALM BEACH COUNTY | | | AMENDMENTS* AND THIS PROJECT IS LOCATED IN THE CITY OF | | | WEST PALM BEACH. | | | PLEASE ADJUST. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | ** PLEASE SEE ANY POSSIBLE CODES FROM OTHER REVIEWER(S) | | | WHICH MAY BE REQUESTED. | | | | | | 2) NOTE: PLEASE KNOW THAT THE SPACE EVEN AS A SHELL | | | WILL BE REQUIRED TO CONTAIN INTERIOR LIGHTING FOR | | | INGRESS/EGRESS IN SPACE. THESE MAY BE CONTROLLED BY OS | | | DEVICES OR MANUAL SWITCHES AS ENTRANCE/EXIT LOCATIONS. | | | | | | PLEASE SEE THIS WILL ALSO BE REQUIRED BY THE FIRE | | | MARSHAL'S OFFICE. | | | NFPA-101 7.8. THE EMERGENCY BATTERY BACK UP LIGHTS | | | SHOWN ON PLANS ARE OK FOR LOSS OF POWER. | | | | | | 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUIRED | | | FOR NEW BUILDINGS. | | | PLEASE SEE METHOD FOR SHELL SPACES. 13-415.1.AB.1.1, | | | 13-415.2 | | | | | | 4) NOTE: PLEASE LABEL MAINS PER 230.2E : EXAMPLE, MAIN | | | 1OF3, MAIN 2 OF 3 ETC. | | | | | | 5) NOTE:PLEASE SEE THAT NOW THAT AN ADDRESS HAS BEEN | | | ASSIGNED. PLEASE BE SURE TO REVISE THE TITLE BLOCKS FOR | | | NEW ADDRESS WHICH WAS ASSIGNED AS 2112 N. JOG RD. ** | | | PLEASE BE SURE TO ALSO REVISE THE PERMIT APPLICATION. A | | | NEW PERMIT APPLICATION WILL BE ATTACHED TO NOTES FOR | | | CONVENIENCE AS THERE ARE SEVERAL ITEMS ON PERMIT | | | APPLICATION WHICH ARE NOT VISIBLE. | | | FAC 61G1-16.004, 61G15-23.002 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-11-01 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-11-01 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2007-11-01 14:20:38 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1.PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER & | | | ITS ENCLOSURE AND THEIR DETAILSPER CITY OF WPB, | | | LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | PERYOUR RESPONSE OF 8/8/07, SITE PLAN SHEET 1.1 OR | | | 2 OF 9 DO NOT SHOW NEITHER LOCATION NOR DETAILS OF | | | DUMPSTER. | | | 2.MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST | | | MATCH WITH AREAS USED IN STORM WATER QUALITY | | | CALCULATIONS. | | | YOURRESPONSE OF 8/8/07WAS: "THE SITE AREAS | | | .....ARE CORRECT...." .OUR RESPONSE TO YOU:INFACT | | | AREA SHOWN ON SITE PLAN SHEET 1.1NOT CONSISTENT WITH | | | POST DEVELOPMENT SITE AREAS SHOWN ON SHEET 1 OF 2.FOR | | | EXAMPLE ON SITE PLAN SHEET 1.1 TOTAL AREA 75503 SQ FT, | | | AND PERVIOUS AREA 5616 SQ FT WHILEYOU HAVE SHOWN ON | | | CALCULATION SHEET 1 OF 2TOTAL SITE AREA 17189 SQ FT | | | AND PERVIOUS AREA 6870 SQ FTAND SO FORTH INCONSISTENT | | | IN IMPERVIOUS AREA ALSO. | | | 3. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER CATCH | | | BASINS DRAINS AROUND YOUR SITE | | | 4.THESTORM STORM WATER QUALITY CALCULATIONS MUST BE | | | APPROVED FROM 1000 45TH STREET, ENGINEERING,BEFORE WE | | | ISSUE A PERMIT. | | | 5. PER CITY ORDINANCE NO. 4060-07,PLEASE SHOW ON | | | DRAWINGS THE POLLUTION PREVENTION SILT AROUND THE SITE | | | & CATCH BASINS DURING CONSTRUCTION AND DURING ALL | | | DEMOLITION.HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER | | | FDEP TO STOP DUST & PARTICLES. | | | 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE ISSUE A | | | PERMIT. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-07-12 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-07-12 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2007-07-12 13:32:21 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER & | | | ITS ENCLOSURE AND THEIR DETAILSPER CITY OF WPB, | | | LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS. | | | PLEASE SHOW IN YOUR STORM WATER QUALITY CALS. | | | 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST | | | MATCH WITH AREAS USED IN STORM WATER QUALITY | | | CALCULATIONS. | | | 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM | | | WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL | | | STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, DO YOU HAVE DRY/WET POND? | | | IF YOU DO,PLEASE SHOW DRY DETENTION/WET DETENTION | | | AREAS WITH 100% FILL OF STORM WATER ELEVATION. WHERE | | | THE STORM WATER GOES AFTER BLEEDING, IN CITY CANAL, OR | | | SFWMD CANAL?? | | | 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND | | | YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE. | | | 7. PLEASE PROVIDE A COPY OF NPBID PERMIT,, AND A | | | LATESTEST COPY OF STORM STORM WATER QUALITY | | | CALCULATIONS SHOWING THE WORST CRITERIA TO CALCULATE | | | QUALITY CALSTHAT YOU PROVIDED AT 45TH STREET. | | | 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | SILT AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE | | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & | | | PARTICLES. | | | 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | | 10. PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS | | | THAT WERE APPROVED AT 45TH STREET. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-07 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-07 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2007-11-07 17:35:52 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 02.ALL FIRE LINES/FIRE HYDRANT(S) TO BE INSTALLED AND | | | IN WORKING CONDITION BEFORE, DURING, AND AFTER BUILDING | | | CONSTRUCTION.SHOW THE LOCATION OF THE NEAREST FIRE | | | HYDRANT(S) TO THE PROPOSED STRUCTURE | | | | | | 09.THE PROJECT DATA ON SHEET 3.1 STATES THAT THERE | | | ARE FOUR (4) EXITS, WHEREAS THE LIFE SAFETY SUMMARY ON | | | SHEET 7.1 LISTS TWO (2) EXIT DOORS.PLEASE INCLUDE THE | | | ACTUAL NUMBER OF EXITS IN THE PROJECT DATA (SHEET 3.1) | | | AND LIFE SAFETY SUMMARY (SHEET 7.1) AS ILLUSTRATED ON | | | SHEET 7.1 | | | | | | 10.IT IS STATED THAT THE BUILDING WILL BE | | | SPRINKLERED.IN THE EVENT OF A FIRE, HOW AND WHERE | | | WILL WATER BE INTRODUCED INTO THE BUILDING?S | | | | | | 11.AS IT RELATES TO THIS SPRINKLERED BUILDING, HOW | | | WILL NOTIFICATION FOR EMERGENCY RESPONSE BE | | | ACCOMPLISHED IN THE ACTIVATION OF THE SPRINKLER | | | SYSTEM? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE(ON THE PLAN) EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-26 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-26 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2007-07-26 13:25:52 | *****DENIED***** | | | | | | | | | 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 02.ALL FIRE LINES/FIRE HYDRANT(S) TO BE INSTALLED AND | | | IN WORKING CONDITION BEFORE, DURING, AND AFTER BUILDING | | | CONSTRUCTION. | | | | | | 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 05.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY | | | OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES, | | | ETC). | | | | | | 06.ON THE APPROPIATE EXTERIOR ELEVATION, POSTS THE | | | NUMERICAL ADDRESS TO BE VISIBLE FROM NORTH JOG ROAD. AS | | | PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS | | | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | | | | | 07.ON THE APPROPIATE EXTERIOR ELEVATION AT THE MAIN | | | ENTRANCE, SHOW/DISPLAY THE DISTINGUISHABLE SUITE | | | NUMBER.AS PER WEST PALM BEACH CODE, THE UNIT NUMBERS | | | SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1" | | | IN WIDTH.IF THE SUITE/UNIT HAS AN EXTERIOR DOOR, AN | | | UNIT NUMBER SHALL ALSO BE POSTED. | | | | | | 08.ON SHEET 7.1, NO EXIT DOORS ARE SHOWN ON THE WEST | | | ELEVATION;HOWEVER, ON SHEET 4.1, DOORS ARE SHOWN ON | | | THIS ELEVATION.PLEASE EXPLAIN. | | | | | | 09.THE PROJECT DATA ON SHEET 3.1 STATES THAT THERE | | | ARE FOUR (4) EXITS, WHEREAS THE LIFE SAFETY SUMMARY ON | | | SHEET 7.1 LISTS TWO (2) EXIT DOORS.PLEASE EXPLAIN. | | | | | | 10.IT IS STATED THAT THE BUILDING WILL BE | | | SPRINKLERED.IN THE EVENT OF A FIRE, HOW AND WHERE | | | WILL WATER BE INTRODUCED INTO THE BUILDING? | | | | | | 11.AS IT RELATES TO THIS SPRINKLERED BUILDING, HOW | | | WILL NOTIFICATION FOR EMERGENCY RESPONSE BE | | | ACCOMPLISHED IN THE ACTIVATION OF THE SPRINKLER | | | SYSTEM? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE(ON THE PLAN) EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-10 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-10 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2007-10-29 08:34:01 | TO "COMM" BD#20 | | 2007-10-10 16:10:24 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-26 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-13 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2007-06-26 09:20:10 | TO "COMM" BD#11 | | 2007-06-13 16:56:12 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-17 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-17 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2007-11-17 13:51:36 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. ENERGY CALCULATIONS: | | | A) PROJECT SUMMARY STATES THIS IS A NEW FINISHED | | | BUILDING, BUT PLANS INDICATES THIS IS A SHELL BUILDING. | | | PLEASE COORDINATE PLANS AND CALCULATIONS. | | | B) ENERGY CALCULATIONS ARE TO BE CERTIFIED BY THE | | | OWNER, PROJECT ARCHITECT (REGISTERED IN THE STATE OF | | | FLORIDA), OR OTHER OFFICIALLY DESIGNATED AGENT ALLOWED | | | IN SECTION 103.2 IN ACCORDANCE WITH FBC 13-103.1 | | | C)MANUAL J INCLUDED WITH ENERGY CALCULATIONS INDICATE | | | BARE CONCRETE BLOCK WALLS WITH INSULATION VALUE OF | | | R-11. WHAT IS THE BASIS FOR THIS VALUE? MANUAL J ALSO | | | INDICATES A METAL DECK ROOF WITH 3 INCHES OF INSULATION | | | WITH A VALUE OF R-19. WHAT IS THE BASIS FOR THIS | | | VALUE? | | | D) THE VALUES USED IN THE MANUAL J AND THE ENERGY | | | CALCULATIONS SHALL BE SHOWN ON PLANS, IN SUFFICIENT | | | DETAIL, INCLUDING ALL PERTINENT DATA AND FEATURES OF | | | THE BUILDING AND THE EQUIPMENT AND SYSTEMS AS HEREIN | | | GOVERNED INCLUDING, BUT NOT LIMITED TO: DESIGN | | | CRITERIA, EXTERIOR ENVELOPE COMPONENT MATERIALS, | | | U-VALUES OF THE ENVELOPE SYSTEMS, R-VALUES OF | | | INSULATING MATERIALS, SIZE AND TYPE OF APPARATUS AND | | | EQUIPMENT, EQUIPMENT AND SYSTEMS CONTROLS AND OTHER | | | PERTINENT DATA TO INDICATE CONFORMANCE WITH THE | | | REQUIREMENTS OF THIS CODE. FBC 13-103.2 | | | | | | 2. SEE PLUMBING CODE FOR MINIMUM FACILITIES REQUIRED. | | | | | | 3. MANUAL J SHOWS 300 CFM OF VENTILATION AIR FOR EACH | | | SYSTEM. WHAT IS THE BASIS FOR THIS NUMBER? PREVIOUS | | | REVIEW REQUESTED OUTSIDE AIR CALCULATIONS BASED ON | | | FBC,M TABLE 403.3. NONE WERE PROVIDED. OUTSIDE AIR | | | CALCULATIONS SHALL BE BASED ON OCCUPANCY | | | CLASSIFICATION, OCCUPANT LOAD AND CFM/PERSON AS | | | REQUIRED BY TABLE 403.3. SHOE THE MINIMUM REQUIRED | | | OUTSIDE AIR RATE FOR THIS SPACE AND SHOW CORRELATION | | | WITH MANUAL J FOR PROPER SYSTEM SIZING. | | | | | | NEW COMMENT: WALL LOUVERS HAVE BEEN ADDED TO THE | | | DRAWINGS. LOUVERS ARE GOVERNED BY FAC RULE 9B-72 AND AS | | | SUCH, PRODUCT APPROVAL IS REQUIRED. SUBMIT TWO COPIES | | | OF THE PRODUCT APPROVAL FOR THE SPECIFIC BRAND OF | | | LOUVER TO BE USED. FOR MORE INFORMATION ON THE FLORIDA | | | PRODUCT APPROVAL SYSTEM PLEASE VISIT: | | | WWW.FLORIDABUILDING.ORG | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-13 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-13 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2007-07-13 11:18:20 | --------------DENIED------------------ | | | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO MECHANICAL INFORMATION WAS PROVIDED ASIDE FROM | | | THE ROOF PLAN SHOWS 3 RTU'S.PLEASE SEE THE MINIMUM | | | PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS AS | | | REQUIRED BY FBC 106.3.5. | | | | | | 2. FLOOR PLAN SHOWS PROVISIONS FOR TWO TOILET ROOMS. | | | PLEASE SHOW PROVISIONS FOR MECHANICAL EHAUST PER FBC,M | | | TABLE 403.3. | | | | | | 3. PLEASE SHOW OUTDOOR AIR CALCULATINS INCLUDING | | | OCCUPANCY CLASIFICATIONS, OCCUPANT LOAD AND OUTDOOR AIR | | | REQUIRED PER FBC, M 403.3. | | | | | | NOTE: ADDITIONAL COMMENTS ARE POSSIBLE BASED ON NEW | | | INFORMATION WHICH MAY BE PROVIDED FOR NEXT REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-04 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-04 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2007-12-04 16:13:24 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | ******SHELL ONLY****** | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1.OK | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. SHT 5.1 THREE RTU'S ON THE ROOF. PLEASE INDICATE IF | | | THERE WILL BE CONDENSATE DRAINING FROM THESE UNITS. IF | | | SO PLEASE INDICATE METHOD OF DRAINING FROM THE ROOF. | | | ****NO RESPONSE, NOT ADDRESSED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-14 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-07-14 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2007-07-14 13:38:49 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | ******SHELL ONLY****** | | | | | | 1.SHT 3.1 ALTHOUGH THIS IS A SHELL ONLY, NO | | | PROVISIONS ARE INDICATED FOR THE REQUIRED DRINKING | | | FOUNTAIN. SECTION 403.1. PLEASE BE ADVISED THAT A | | | DRINKING FOUNTAIN IS REQUIRED. | | | | | | 2. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE OF | | | THE BUILDING. SECTION 608.13.2. PLEASE INDICATE ON | | | PLANS. | | | | | | 3. SHT 4.1 WEST ELEVATION DOES NOT SHOW DOWNSPOUTS | | | INDICATED ON SHT 5.1 ROOF PLAN. PLEASE CORRELATE | | | INFORMATION FROM ELEVATION AND ROOF PLAN. SECTION | | | 106.1.1. | | | | | | 4. SHT 5.1 SECONDARY ROOF DRAINS OR SCUPPERS SHALL BE | | | PROVIDED WHERE THE ROOF PERIMETER CONSTURCTION EXTENDS | | | ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE | | | ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY | | | REASON/ SECTION 1107.1 PLEASE INDICATE THE LOCATION OF | | | THE SECONDARY ROOF DRAINS/SCUPPERS.--SEPARATE | | | SYSTEMS ARE REQUIRED PER SECTION 1107.2. | | | | | | 5. SHT 5.1 THREE RTU'S ON THE ROOF. PLEASE INDICATE IF | | | THERE WILL BE CONDENSATE DRAINING FROM THESE UNITS. IF | | | SO PLEASE INDICATE METHOD OF DRAINING FROM THE ROOF. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-06-19 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-06-19 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2007-06-19 15:58:57 | NO LANDSCAPE PLAN WAS SUBMITTED, PLEASE MAKE SURE TO | | | INCLUDE IT WHEN YOU RESUBMIT. | | | | | | PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | WITH QUESTIONS. |
|
|
|