Plan Review Details - Permit 07060376
Plan Review Stops For Permit 07060376
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-07-11 Cont ID  
Sent By jgomez Date 2007-07-11 Time 12:41 Rev Time 0.00
Received By jgomez Date 2007-07-11 Time 12:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 09:15 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 09:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By btrobaug Date 2007-06-20 Time 17:33 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 16:52 Sent To M
Notes
2007-06-20 17:29:43 
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} IF A SERVICE CHANGE IS TO BE PART OF THE ELECTRICAL
 PERMIT, PROVIDE A RISER DIAGRAM PER 215.5.
  
 2}THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3.
 FBC.
  
 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.408.4 CIRCUIT DIRECTORY OR CIRCUIT
 IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 10:54 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 10:54 Sent To E
Notes
2007-07-16 10:55:09TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By jgomez Date 2007-07-11 Time 12:52 Rev Time 0.00
Received By jgomez Date 2007-06-14 Time 09:48 Sent To  
Notes
2007-06-14 09:48:23TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-21 Cont ID  
Sent By tgordon Date 2007-06-21 Time 08:30 Rev Time 0.20
Received By tgordon Date 2007-06-21 Time 08:30 Sent To P
Notes
2007-06-21 08:30:49NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-05 Cont ID  
Sent By jleech Date 2007-07-05 Time 08:32 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 08:32 Sent To B
Notes
2007-07-05 08:32:44NO PLUMBING SHOWN ON PLANS.