Plan Review Details - Permit 07060316
Plan Review Stops For Permit 07060316
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-21 Cont ID  
Sent By lmartine Date 2008-05-21 Time 10:48 Rev Time 0.00
Received By lmartine Date 2008-05-21 Time 10:48 Sent To  
Notes
2008-05-21 10:51:50REVISION FOR CHANGE OF FASTENERS, 7/8 TO 5/8 INCH

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-12 Cont ID  
Sent By jwitmer Date 2007-12-12 Time 11:33 Rev Time 0.77
Received By jwitmer Date 2007-12-12 Time 11:33 Sent To  
Notes
2007-12-12 11:34:27GENERATOR & CONCRETE PAD

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By jwitmer Date 2007-11-19 Time 11:46 Rev Time 1.22
Received By jwitmer Date 2007-11-19 Time 11:46 Sent To  
Notes
2007-11-19 12:14:52530 HIBISCUS, GENERATOR
 2ND REVIEW
 BUILDING PLAN REVIEW
 PERMIT: 07060316
 ADD: 530 HIBISCUS ST.
 CONT: TERRY"S ELECTRICAL
 TEL: (561)689-4182
 DATE: 11-19,2007
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 REVIEW
 ACTION: DENIED
  
 COMMENT# 5 FROM THE PREVIOUS REVIEW, DEALS WITH
 GENERATOR SLAB & ANCHOR REQUIREMENTS.
 THE RESPONSE SHEET INDICATES TO SEE SHEET IN THE BASE
 BUILDING PLAN, AND A PHOTO COPY IS SUPPLIED IN THE
 BINDER SEE TAB# 2. NOTE THIS IS A STAND ALONE PERMIT
 AND ALL BACKUP DOCUMENTS PERTAINING TO THIS PERMIT WILL
 NEED TO MEET ALL STATE STATUTES IN REGARDS TO 471
 ENGINEERING LICENSURE REQUIREMENTS. IF THE SHEET S5.03
 IS TO BE REISSUED IT MUST MEET THE LICENSING
 REQUIREMENTS FOR ENGINEERS.
  
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),PLUS PROVIDE
 PLANS WITH THE INFORMATION DEPICTING HOLD DOWN
 BRACKETS, TYPE OF FASTENER, AND THE MINIMUM EDGE
 DISTANCE THE DEVICE REQUIRES WITHOUT LOAD REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE SLAB, THICKNESS,
 WIDTH AND LENGTH, IF WIRE MESH, FIBER MESH OR IF STEEL
 REBAR WILL BE USED.THE NEW SLAB AND HOLD DOWN
 DETAILS: 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By jwitmer Date 2007-07-17 Time 16:31 Rev Time 0.77
Received By jwitmer Date 2007-07-16 Time 22:17 Sent To  
Notes
2007-07-17 16:45:34BUILDING PLAN REVIEW
 PERMIT: 07060316
 ADD: 525 OKEECHOBEE BLVD
 CONT: TERRY"S ELECTRICAL
 TEL: (561)689-4182
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLEASE PROVIDE A SITE PLAN WHERE THESE GENERATORS
 WILL BE INSTALLED. I BELIEVE FROM THE BASE BUILDING
 PLAN THAT THERE IS AN EASEMENT AND THAT THESE
 GENERATORS WILL ACTUALLY BE PLACED
 ON THE SAME LOT AS THE "B" BLOCK PARKING GARAGE ALONG
 WITH THE NEW ELEVATOR TOWER. PLEASE SUBMIT SITE PLAN IF
 CORRECTIONS NEED TO BE MADE TO THE PERMIT APPLICATION
 ADDRESS AND PCN PLEASE DO SO. PLEASE NOTE THE CORRECT
 ADDRESS TO THE SITE PLAN HEADER !
  
 4) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY 3)-
 WIND EXPOSURE
  
 5) ) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE
 PROVIDE SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS
 WITH THE INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE
 OF FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION. SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 10:08 Sent To PC
Notes
2008-06-16 10:09:10UL REPORTS FOR THE ADDITION OF BI-FUEL ASSEMBLY TO
 UNIT.
 UL REPORT FOR EXHAUST PANEL
 UL REPORT FOR NREAKER ENCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 14:42 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 14:42 Sent To  
Notes
2007-11-09 14:43:40** OWES BALANCE FOR 4X FEE OF $150.00.
  
 WORK CONTINUED AFTER STOP WORK WAS GIVEN. PER PHIL
 PETTY AND JAKE LEAHY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By dpalmer Date 2007-06-26 Time 18:13 Rev Time 0.00
Received By dpalmer Date 2007-06-26 Time 17:31 Sent To  
Notes
2007-06-26 18:13:38 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT AS STATED ON PREVIOUS PHONE
 CALLS, THIS SEPARATE PERMIT WAS REQUIRED AS THE
 GENERATORS WERE LOCATED ON A DIFFERENT PARCEL AND LEGAL
 PROPERTY.
 PLEASE SEE HOWEVER THE PERMIT WAS APPLIED FOR UNDER THE
 SAME ADDRESS OF THE OFFICE TOWER WHICH IS INCORRECT.
 PLEASE OBTAIN THE CORRECT PARCEL AND ADJUST PLANS WHICH
 ARE TO BE SUBMITTED.
 AS ONLY A LEGAL EASEMENT WAS ISSUED, THIS IS STILL
 LOCATED ON A SEPARATE PCN.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE NO SITE/SURVEY PLANS WERE SUBMITTED
 FOR LOCATION UNDER THIS LEGAL RECORDED PERMIT.
 REVIEW FOR CLEARANCES, LOCATIONS ETC CAN NOT BE DONE AT
 THIS TIME.
 110.26.
 FBC 106.1.2
  
 3) NOTE: PLEASE SUBMIT THE ELECTRICAL PLANS FOR THE
 GENERATOR AND ITS LOCATION ALONG WITH THE REVISED
 ELECTRICAL RISER FOR THE BASE OFFICE BUILDING IN WHICH
 IT FEEDS.
 PLEASE SEE THE NOTES UNDER THE BASE BUILDING ON THE
 LAST SUBMITTED REVISED ELECTRICAL AS THE PLANS NEED TO
 REFLECT CHANGES AND CORRECTIONS FOR THE INCREASED
 UNITS.
 PLEASE ALSO SEE NOTES WITH RESPECT TO THE MODIFICATIONS
 OF THE GENERATOR. IF THIS UNIT IS STILL GOING TO BE
 BI-FUEL AND ANY MODIFICATIONS TO THIS UNIT MAY VERY
 WELL VOID ANY OF THE CERTIFICATIONS OF THE GENERATOR.
 PLEASE KNOW AS THESE ARE PART OF LEGALLY REQUIRED AND
 EMERGENCY LIFE SAFETY SYSTEMS IN THE OFFICE BUILDING
 ANY MODIFICATIONS TO CERTIFIED OR LISTED EQUIPMENT IS
 NOT PERMITTED.
 110.3, 215.5, 90.7, 700, 701 ETC.
 REVISE SERVICE.
  
 4) NOTE: PLEASE BE SURE ALL MANUFACTURES SPECS/CUT
 SHEETS ARE SUBMITTED. PLEASE SEE COMMENTS FROM OTHER
 TRADES FOR FUEL TANKS ETC.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL CONTRACTOR DID NOT
 SIGN ON THE ELECTRICAL LINE FOR THE GEN-ELEC PERMIT.
 PLEASE DO SO.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-05 Cont ID  
Sent By mawillia Date 2007-12-05 Time 15:54 Rev Time 0.00
Received By mawillia Date 2007-12-05 Time 15:18 Sent To  
Notes
2007-12-05 15:50:49*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED: PLAN SHEET E0.01GE STAMPED, INITIALED,
 AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 23:38 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 23:11 Sent To  
Notes
2007-07-26 23:38:09*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 110.
  
 3.PROVIDE A SITE PLAN SHOWING PROPER SETBACKS TO
 PROPERTY LINES, BUILDING OPENINGS OF AT LEAST 10 FEET
 DISTANCE, AND ANY MEANS OF EGRESS IN REGARDS TO FUEL
 EXHAUSTING.
  
 4.ABOVE GROUNDFUEL TANKS SHALL BE PERMITTED TO BE
 INSTALLED THAT MEET THE REQUIREMENTS OF NFPA 30.NFPA
 704 LABELS WILL BE REQUIRED.
  
 5.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 6.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 7.THE INSTALLATION AND/OR SCOPE OF WORK SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF.
  
 8.HOW WILL THE ABOVE GROUND FUEL TANK BE PROTECTED
 FROM VEHICULAR/COLLISION DAMAGE?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By kstevens Date 2007-12-28 Time 16:08 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 16:08 Sent To  
Notes
2007-12-28 16:09:41 
  
  
  
  
 REVISION OK
  
 SEPARATE GAS PERMIT REQUIRED.
  
 WELDED PIPE REQUIRES WELDING CERTIFICATIONS AND
 WELDING PROCEDURES AT THE TIME OF APPLICATION.THE
 WELDS WILL HAVE THREESEPARATE INSPECTIONS. THE FIRST
 WILL BE THE TACK UP, THE SECOND WILL BE THE ROOT PASS,
 AND THE THIRD WILL BE THE FINAL PASSES WITH PRESSURE
 TEST.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 14:24 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 14:24 Sent To  
Notes
2007-12-04 15:34:31 
  
  
  
 SEPARATE GAS PERMIT REQUIRED.
  
 WELDED PIPE REQUIRES WELDING CERTIFICATIONS AND
 WELDING PROCEDURES AT THE TIME OF APPLICATION.THE
 WELDS WILL HAVE THREESEPARATE INSPECTIONS. THE FIRST
 WILL BE THE TACK UP, THE SECOND WILL BE THE ROOT PASS,
 AND THE THIRD WILL BE THE FINAL PASSES WITH PRESSURE
 TEST.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 09:04 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 09:04 Sent To  
Notes
2007-07-14 09:20:35DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SUBMIT A SURVEY/SITE PLAN SHOWING THE MEASUREMENTS
 FROM ALL PROPERTY LINES, STRUCTURES, OPENINGS IN
 STRUCTURES AND SHOWING COMPLIANCE WITH MANUF.
 INSTALLATION CLEARANCE REQUIREMENTS. SECTION 106.1.2.
  
 2. UPON REVIEW OF "BILL OF MATERIAL" FROM CUMMINGS
 POWER GENERATION A BIFUEL VALVE IS INDICATED. AS SUCH
 PLEASE SEE REQUIREMENTS FOR FUEL GAS.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. NO BTU LOAD IS
 INDICATED IN THE MANUF. SPECIFICATION SHEETS FOR THE
 GENERATORS. SUBMIT INFORMATION SHOWING MAXIMUM BTU LOAD
 AT 100%.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 3. SEPARATE GAS PERMIT REQUIRED.
  
 4. SEE COMMENT #1 FROM ELECTRICAL REVIEW AND COMMENT #3
 FROM THE MECHANICAL REVIEW. THIS ISSUE TO BE ADDRESSED
 PRIOR TO PERMIT ISSUANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 12:27 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 12:27 Sent To E
Notes
2008-06-02 12:27:47TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 10:12 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 10:12 Sent To Z
Notes
2008-05-12 10:13:19TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:24 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:24 Sent To  
Notes
2007-12-21 16:25:11TO RON REGUEIRO

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 13:57 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 13:57 Sent To P
Notes
2007-12-14 13:57:41TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 13:22 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 13:22 Sent To  
Notes
2007-12-07 15:52:43APPL. ON HOLD PER ADRIANNA MCKENZIE(FEES WERE NOT PAID
2007-12-07 13:27:00TO "COMM" BD#13--BINDERS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 14:50 Sent To  
Notes
2007-11-26 13:31:17TO "COMM" BD#37
2007-10-23 14:50:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 23:11 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 08:43 Sent To  
Notes
2007-06-26 08:59:44TO "COMM" BD#41
2007-06-12 08:43:40WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-07 Cont ID  
Sent By rregueir Date 2008-01-07 Time 08:40 Rev Time 0.00
Received By rregueir Date 2008-01-05 Time 15:02 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-11 Cont ID  
Sent By rregueir Date 2007-12-11 Time 15:41 Rev Time 0.00
Received By rregueir Date 2007-12-11 Time 15:38 Sent To B
Notes
2007-12-11 15:41:31****************PROVISO****************
 SITE PLAN GSP-1 WITH DERM APPROVAL STAMP ARE REVISION
 2, WITH ONLY 2 COPIES PROVIDED AND THEY ARE NOT SIGNED
 AND SEALED. PROVIDE 3 COPIES OF GSP-1, REV.3 ALSO WITH
 DERM STAMP TO BE SUBMITTED AS A REVISION IF BUILDING
 PLAN REVIEW PASSES AND PERMIT IS ISSUED. OTHERWISE,
 PROVIDE PLANS AS REQUESTED AT TIME OF RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By rregueir Date 2007-11-20 Time 16:39 Rev Time 0.00
Received By rregueir Date 2007-11-20 Time 16:31 Sent To  
Notes
2007-11-20 16:38:52REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. THIS PERMIT WILL NOT BE ISSUED PRIOR TO RECEIPT OF
 PLANS WHICH AHVE BEEN REVIEWED AND APPROVED BY PALM
 BEACH COUNTY DERM. UNTIL THIS PART OF THE PROCESS IS
 COMPLETE, IT IS UNKNOWN AS TO WHETHER THE PROPOSED
 LOCATION IS ACCEPTABLE UNDER DERM REGULATIONS.
 THEREFORE, THE PERMIT WILL NOT BE ISUUED PRIOR TO DERM
 APPROVAL.
  
 3. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By rregueir Date 2007-07-11 Time 14:17 Rev Time 0.00
Received By rregueir Date 2007-07-10 Time 16:35 Sent To  
Notes
2007-07-11 14:17:23--------------DENIED-----------------
  
 1. PLEASE PROVIDE SITE PLANS SHOWING LOCATION OF
 EQUIPMENT, REQUIRED SETBACKS, EXHAUST TERMINATION
 LOCATIONS, PROTECTION FROM VEHICLE DAMAGE. FBC
 106.1.2.
  
 2. ABOVE GROUND FUEL TANKS OF 550 GALLONS OR MORE
 REQUIRE PALM BEACH COUNTY DERM APPROVAL. FOR ADDITIONAL
 INFORMATION CONTACT DERM AT 561-233-2400 OR
 HTTP://WWW.PBCGOV.COM/ERM
  
 3. IS THE ADDRESS ON THIS PERMIT APPLICATION CORRECT OR
 IS IT LOCATED ON AN EASEMENT ON AN ADJACENT PROPERTY?
 PLEASE PROVIDE THE CORRECT ADDRESS ON THE PERMIT
 APPLICATION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 5 Status N Date 2008-05-15 Cont ID  
Sent By choops Date 2008-05-15 Time 11:50 Rev Time 0.00
Received By ESCHNEID Date 2008-05-15 Time 11:52 Sent To  
Notes
2008-05-15 11:52:02BOLT CHANGE NO ZONING REVIEW REQUIRED.
  
 DISREGARD REVIEW DATED 5/13/2008.

Review Stop Z ZONING
Rev No 4 Status F Date 2008-05-13 Cont ID  
Sent By eschneid Date 2008-05-13 Time 16:46 Rev Time 0.00
Received By eschneid Date 2008-05-13 Time 16:46 Sent To B
Notes
2008-05-13 16:47:51FAILED
  
 1) CITYPLACE STAMP REQUIRED.
  
 2) PROVIDE A COPY OF THE APPROVED GENERATOR LOCATION
 SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-12 Cont ID  
Sent By eschneid Date 2007-12-12 Time 16:59 Rev Time 0.00
Received By eschneid Date 2007-12-12 Time 16:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-29 Cont ID  
Sent By eschneid Date 2007-10-29 Time 18:35 Rev Time 0.00
Received By eschneid Date 2007-10-29 Time 18:35 Sent To  
Notes
2007-10-29 18:48:58FAILED
  
 1) MINOR AMENDMENT APPROVAL REQUIRED FOR GENERATOR
 LOCATION.THIS IS IN CITYPLACE RETAIL SERVICE AREA.
  
 2) WHERE WILL THE DUMPSTERS/COMPACTORS FOR CITYPLACE BE
 RELOCATED TOO?THESE NEED TO BE SHOWN ON THE PLANS.
  
 3) THE TURNING RADIUS/TURN AROUND FOR THE GARBAGE
 TRUCKS AND 18-WHEELERS DELIVERING TO CITYPLACE RETAIL
 SHALL BE SHOWN ON THE PLANS.THE GENERATORS ARE TAKING
 UP A SIGNIFICANT PORTION OF THE SERVICE AREA.
  
 4) CITYPLACE RETAIL STAMP IS REQUIRED ON THE PLANS.
  
 5) WHAT IS THE RELOCATION PLAN FOR THE MANHOLE.IS
 THIS A CITY WATER MAIN? IF SO, THEN THE WPB UTILITIES
 SHALL SIGN-OFF ON THE RELOCATION/BURYING OF THE
 MANHOLE.
  
 6) HOW TALL IS THE GENERATOR?CLEARLY STATE THE
 MAXIMUM HEIGHT.THE NUMBERS IN THE SCHEMATICS ARE
 DIFFICULT TO READ.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By eschneid Date 2007-06-28 Time 13:48 Rev Time 0.00
Received By eschneid Date 2007-06-28 Time 13:48 Sent To  
Notes
2007-06-28 13:50:40FAILED
  
 1) NO SITE PLAN OR SURVEY SUBMITTED TO SHOW WHERE THE
 GENERATORS ARE LOCATED.
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ONCE THE SITE
 PLAN/SURVEY IS SUBMITTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.