Plan Review Details - Permit 07060304
Plan Review Stops For Permit 07060304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By mjacobs Date 2007-08-29 Time 09:27 Rev Time 0.00
Received By mjacobs Date 2007-08-29 Time 12:50 Sent To  
Notes
2007-09-04 09:27:13 
 BUILDING PLAN REVIEW
 PERMIT: 07060304
 ADD: 477 S.ROSEMARY AVE.
 CONT: OCEAN DRIVE BUILDING CORP.
 TEL: (561)833-3900
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE DRAWINGS PROVIDED DO NOT INDICATE CLEARLY THE
 SCOPE OF WORK.PROVIDE TWO COMPLETE SETS OF DRAWINGS
 WITH THE EXISTING FLOOR PLAN AND THE PROSOSED FLOOR
 PLAN.PAGE 1 OF 6 SHOWS TWO SEPERATE UNITS. PROVIDE
 SIMILAR DRAWINGS SHOWING HOW THE TWO UNITS WILL BECOME
 ONE. THE PLANS PROVIDED SHOWS ONLY ONE UNIT WITH A
 CASED OPENING. THE TOTAL FLOOR PLAN SHALL BE SHOWN.
 FBC. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE SECTION
 106.3.5)
  
 NEW***
  
 1)A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 A)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 B)UNITS 207 AND 209 APPEARS TO BE RESIDENTIAL UNITS.
 IF THESE UNITA ARE NOW BEING CHANGED AT BUSINESS, THE
 CHANGE OF OCCUPANCY OR USE BOX SHALL BE CHECKED ON THE
 APPLICATION.
  
 C) PROVIDE A LIFESAFETY PLAN SHOWING THE EGRESS PATH
 AND TRAVEL DISTANCE. FBC. (BUILDING) 1013.
  
 D) 1006.3.1. EXIT SIGNS:EXIT SIGNS SHALL BE MARKED BY
 AN APPROVED SIGN READILY VISIBLE FROM ANY DIRECTION OF
 EXIT ACCESS. EVERY EXIT SIGN SHALL BE SUITABLE
 ILLUMINATED BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE VISIBLE IN BOTH
 THE NORMAL & EMERGENCY LIGHTING.
  
 E)FBC. (BUILDING) 11-4.3.4 IF DOORWAYS HAVE TWO
 INDEPENDENTLY OPERATED DOORLEAVES, THEN ONE
 LEAF SHALL BE AT LEAST 32 INCHES. THE DOUBLE DOORS
 LEADING TO THE INTERIOR DESIGNER SPACE SHALL MEET THIS
 REQUIREMENT.
  
 F)SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR. 11-4.24.3 KNEE
 CLEARANCE THAT IS AT LEAST 27" HIGH 30" WIDE, AND 19"
 DEEP SHALL BE PROVIDED UNDERNEATH SINKS. 11-4.24.5
 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 G) INDICATE THE INTERIOR WALL AND CEILING FINISH IN
 ACCORDANCE WITH FBC.TABLE 803.5.
  
 H)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 I)INDICATE CLEARLY THE TYPE OF BUSINESS AND THE USE
 OF EACH ROOM OR AREA ON THE PLANS. PROVIDE A WALL
 LEGEND AND SHOW WHERE EACH TYPE OF WALL WILL BE
 INSTALLED ON THE FLOOR PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By mjacobs Date 2007-06-21 Time 12:14 Rev Time 0.00
Received By mjacobs Date 2007-06-21 Time 08:54 Sent To  
Notes
2007-06-21 12:14:02BUILDING PLAN REVIEW
 PERMIT: 07060304
 ADD: 477 S.ROSEMARY AVE.
 CONT: OCEAN DRIVE BUILDING CORP.
 TEL: (561)833-3900
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE DRAWINGS PROVIDED DO NOT INDICATE CLEARLY THE
 SCOPE OF WORK.PROVIDE TWO COMPLETE SETS OF DRAWINGS
 WITH THE EXISTING FLOOR PLAN AND THE PROSOSED FLOOR
 PLAN.PAGE 1 OF 6 SHOWS TWO SEPERATE UNITS. PROVIDE A
 SIMILAR DRAWINGS SHOWING HOW THE TWO UNITS WILL BECOME
 ONE. THE PLANS PROVIDED SHOWS ONLY ONE UNIT WITH A
 CASED OPENING. THE TOTAL FLOOR PLAN SHALL BE SHOWN.
 FBC. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL ( SEE SECTION
 106.3.5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-22 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 17:32 Rev Time 0.00
Received By btrobaug Date 2007-08-22 Time 17:06 Sent To  
Notes
2007-08-22 17:32:20 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE ARE TWO PLANS SUBMITTED ON TWO DIFFERENT
 SHEETS, IT IS UNCLEAR WHICH SET IS INTENDED FOR REVIEW.
 REMOVE THE SET NOT INTENDED FOR REVIEW. SEE COMMENTS
 FROM PREVIOUS REVIEW.
  
 2} THE APPLICATIION HAS BEEN PARTIALLY "WHITED OUT",
 FILL OUT A NEW APPLICATION. 106.1.3 FBC.
  
 3} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By btrobaug Date 2007-06-20 Time 10:19 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 09:58 Sent To  
Notes
2007-06-20 10:15:03 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES SO THAT COMPLIANCE WITH CALCULATIONS FOR
 220.14(I) MAY BE REVIEWED.
  
 2} PROVIDE AMPERAGE RATINGS FOR EXISTING PANELS. BOTH
 PANELS ON SHEET 1/6 ARE DESIGNATED "D". REDESIGNATE FOR
 CIRCUIT CLARITY.
  
 3} SUBMIT A PANEL SCHEDULES PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 4} PROVIDE A CALCULATION FOR THE TRACK LIGHTING PER
 220.43(B).
  
 5} 2} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS.
  
 6} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  
 7} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-08-27 Time 14:21 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 13:18 Sent To  
Notes
2007-08-27 13:15:16*****UNSAT*****
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 CLEAR, CONCISE, AND CONSISTENT PLANS HAVE BEEN
 SUBMITTED.
  
  
 01.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE REMOVAL AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER WITH
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES).
  
 05.INDICATE IF THE EXISTING BUILDING OR PORTION
 THEREOF REPRESENTS A CHANGE OF OCCUPANCY TO A BUSINESS
 OCCUPANCY.IF SO, THE LIFE SAFETY REQUIREMENTS FOR A
 NEW BUSINESS OCCUPANCY SHALL APPLY.
  
 06.PLEASE PROVIDE THE OCCUPANT LOAD AS IN THE NUMBER
 OF PERSONS FOR WHOM MEANS OF EGRESS AND OTHER
 PROVISIONS ARE REQUIRED.
  
 07.DOORS COMPLYING WITH NFPA 101, 7.2.1 SHALL BE
 PERMITTED.
  
 08.PLEASE PROVIDE TRAVEL DISTANCE TO EXIT(S).
  
 09.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S).
  
 10.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A OR CLASS B IN EXITS AND IN EXIT ACCESS
 CORRIDORS, CLASS A, CLASS B, OR CLASS C IN ALL OTHER
 AREAS.BE SPECIFIC
  
 11.SEPARATE PLANS AND PERMIT SHALL BE PROVIDED IF THE
 FIRE SPRINKLER OR FIRE ALARM IS MODIFIED AS A RESULT OF
 THE SCOPE OF WORK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By mawillia Date 2007-06-23 Time 21:16 Rev Time 0.00
Received By mawillia Date 2007-06-23 Time 20:26 Sent To  
Notes
2007-06-23 21:16:16*****DENIED*****
  
  
 01.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE REMOVAL AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER WITH
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES).
  
 05.INDICATE IF THE EXISTING BUILDING OR PORTION
 THEREOF REPRESENTS A CHANGE OF OCCUPANCY TO A BUSINESS
 OCCUPANCY.IF SO, THE LIFE SAFETY REQUIREMENTS FOR A
 NEW BUSINESS OCCUPANCY SHALL APPLY.
  
 06.PLEASE PROVIDE THE OCCUPANT LOAD AS IN THE NUMBER
 OF PERSONS FOR WHOM MEANS OF EGRESS AND OTHER
 PROVISIONS ARE REQUIRED.
  
 07.DOORS COMPLYING WITH NFPA 101, 7.2.1 SHALL BE
 PERMITTED.
  
 08.PLEASE PROVIDE TRAVEL DISTANCE TO EXIT(S).
  
 09.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S).
  
 10.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A OR CLASS B IN EXITS AND IN EXIT ACCESS
 CORRIDORS, CLASS A, CLASS B, OR CLASS C IN ALL OTHER
 AREAS.BE SPECIFIC
  
 11.SEPARATE PLANS AND PERMIT SHALL BE PROVIDED IF THE
 FIRE SPRINKLER OR FIRE ALARM IS MODIFIED AS A RESULT OF
 THE SCOPE OF WORK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 09:52 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 09:52 Sent To  
Notes
2007-08-16 09:47:11TO "BOB"#7
2007-08-10 09:52:30WAITING FOR BOB BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 09:43 Rev Time 0.00
Received By tgordon Date 2007-06-12 Time 08:17 Sent To  
Notes
2007-06-12 08:25:13TO "BOB"#11
2007-06-12 08:17:57WAITING FOR"BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-16 Cont ID  
Sent By tgordon Date 2007-08-16 Time 10:41 Rev Time 0.25
Received By tgordon Date 2007-08-16 Time 10:41 Sent To  
Notes
2007-08-16 10:43:13INSTALLING ONE NEW A/C SUPPLY DROP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 09:33 Rev Time 0.25
Received By tgordon Date 2007-06-27 Time 09:33 Sent To  
Notes
2007-06-27 09:40:23*** DENIED ***
 1) PLANS STATE COMBINE TWO EXISTING UNITS. PLANS DO NOT
 SHOW HOW THE TWO UNITS ARE BEING COMBINED THEY ONLY
 SHOW HOW ONE UNIT (#207 ? NOT CERTAIN) IS BEING
 ALTERED. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
 .

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By mperson Date 2007-09-04 Time 08:22 Rev Time 0.00
Received By mperson Date 2007-09-04 Time 08:22 Sent To  
Notes
2007-09-04 09:15:49DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** THIS LOOKS LIKE ONE HALF OF THE 2 UNITS IS
 TURNING INTO A BUSINESS. THIS WOULD REQUIRE THE
 BATHROOM OR BATHROOMS TO BE HANDICAP ACCESSIBLE. SEE
 FBC-2004 EXISTING BUILDING, SECTION 506.1.
 NOTE: THIS COMMENT WAS NOT ADDRESSED ON THE
 RESUBMITTAL. IF THERE IS A CHANGE OF OCCUPANCY PLEASE
 INDICATE THIS ON THE RESUBMITTED PERMIT APPLICATION AS
 SUCH. PLEASE CLARIFY THIS ON THE RESUBMITTAL.
  
 2. **NO** SHOW ELEVATION DETAIL DRAWINGS WITH ALL THE
 REQUIRED MEASURMENTS/ INFORMATION TO COMPLY WITH
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILTY CODE SECTIONS
 11-4.23.1 THRU 11-4.23.9.
 NOTE: IF THERE IS A CHANGE OF OCCUPANCY ALL OF THE
 ABOVE INFORMATION IS REQUIRED. THIS COMMENT WAS NOT
 ADDRESSED ON THE RESUBMITTAL.
  
 3. **NO** ARE THE LAUNDRY FACILITIES BEING REMOVED?
 NOTE: IF SHEET 1 OF 6 IS SUPPOSED TO BE A DEMOLITION
 DRAWING PLEASE INDICATE THE REMOVAL OF THE LAUNDRY
 FACILITIES ON THE RESUBMITTAL.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 4. IF ONE HALF OF THIS UNIT IS TURNING INTO A BUSINESS
 A DRINKING FOUNTAIN IS REQUIRED PER FBC-2004, TABLE
 403.1, AND SHALL BE ADA ACCESSIBLE PER FBC-2004 CHAPTER
 11, SECTION 11-4.15.1 THRU 11-4.15.5 AND SECTION
 11-4.1.3(10) INDIVIDUALS WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By jleech Date 2007-06-26 Time 08:55 Rev Time 0.00
Received By jleech Date 2007-06-26 Time 08:55 Sent To  
Notes
2007-06-26 09:20:18DENIED;
 1. THIS LOOKS LIKE ONE HALF OF THE 2 UNITS IS TURNING
 INTO A BUSINESS. THIS WOULD REQUIRE THE BATHROOM OR
 BATHROOMS TO BE HANDICAP ACCESSIBLE. SEE FBC-2004
 EXISTING BUILDING SECTION 506.1.
 2. SHOW DETAIL DRAWINGS WITH ALL REQUIRED MEASURMENTS
 TO COMPLY WITH 11-4.23.1 THRU 11-4.23.9.
 3. ARE THE LAUNDRY FACILITIES BEING REMOVED?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-16 Cont ID  
Sent By choops Date 2007-08-16 Time 16:00 Rev Time 0.00
Received By choops Date 2007-08-16 Time 16:00 Sent To  
Notes
2007-08-16 16:00:34*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy