Plan Review Details - Permit 07060281
Plan Review Stops For Permit 07060281
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-10 Cont ID  
Sent By lmartine Date 2007-10-10 Time 17:14 Rev Time 0.00
Received By lmartine Date 2007-10-10 Time 17:14 Sent To  
Notes
2007-10-10 17:32:18ELEVATION CERTIFICATE REQUIRED BEFORE FINAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-01 Cont ID  
Sent By rmcdouga Date 2007-10-01 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2007-10-01 Time 07:17 Sent To  
Notes
2007-10-01 07:18:432004 FBC W/2007 AMENDMENTS
  
 DENIED BY BUILDING
  
 1) A FLORIDA LICENSED BUILDING OR GENERAL CONTRACTOR
 WILL BE REQUIRED TO APPLY FOR THE PERMIT FOR THE
 STRUCTURE TO ENCLOSE THE AIR COMPRESSOR EQUIPMENT.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED FOR THE STRUCTURE.
  
 3) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, AN
 ELEVATION CERTIFICATE WILL BE REQUIRED. SPECIFY THE TOP
 OF SLAB ELEVATION ON THE PLANS.
  
 4) THE PLANS SPECIFY THAT THE SLAB IS EXISTING AND WAS
 PERMITTED UNDER PERMIT # 06030729. I WAS UNABLE TO
 LOCATE THE PLANS FOR THIS SLAB ON THE APPROVED PLANS
 FOR THIS PERMIT OR ON THE PLANS FOR THE FOUNDATION #
 05110729. PLEASE SUBMIT A COPY OF THE CITY APPROVED
 PLANS FOR THIS SLAB.
  
 5) SHEET 1 SPECIFIES THE EXISTING SLAB TO BE 12" THICK
 AND SHEET A-2.00 INDICATES THAT IT IS 16" THICK. PLEASE
 COORDINATE THE PLANS.
  
 6) SPECIFY THE CONSTRUCTION TYPE AND OCCUPANCY OF THE
 STRUCTURE ON THE PLANS. NOTE: THE BUILDING THAT IT IS
 SERVICING IS TYPE II-B SPRINKLERED AND THE OCCUPANCY IS
 F-1. SEE FBC 602.1 AND FBC 302.
  
 7) THE SLAB PLAN ST-3 INSERT ON SHEET A-2.0 SHOWS THE
 SLAB LEVEL WITH THE EXISTING GRADE AND THE ELEVATIONS
 SHOW THE SLAB ABOVE GRADE. PLEASE SPECIFY THE DISTANCE
 FROM FINISH GRADE TO THE TOP OF THE SLAB AND THE
 DISTANCE FROM GRADE TO THE BOTTOM OF THE FOOTING. SEE
 FBC 1805.2.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE ITEMS REQUIRED BY
 FAC RULE 9B-72 WHICH INCLUDES ROOFING, LOUVERS, WALL
 PANELS, DOORS, ETC.
  
 9) SHOW COMPLIANCE WITH FBC 503.1.3 BUILDINGS ON THE
 SAME LOT. SPECIFY IF THE NEW STRUCTURE IS TO BE
 REGULATED AS A SEPARATE BUILDING OR CONSIDERED AS A
 PORTION OF EXISTING BUILDING. IF TWO SEPARATE BUILDINGS
 THREE HOUR FIRE SEPARATION IS REQUIRED PER FBC TABLE
 602. IF ONE BUILDING SHOW CALCULATIONS FOR AREA
 INCREASES FOR SPRINKLERS AND FRONTAGE AS ALLOWED BY FBC
 506. NOTE: OPTION 2 WILL REQUIRE THE NEW STRUCTURE TO
 BE FIRE SPRINKLERED.
  
 10) NOTE: THE ELECTRICAL CODE REQUIRES THE FOOTING
 STEEL TO BE BONDED.
  
 11) ADDITIONAL FEES WILL BE REQUIRED. THE PERMIT FEES
 BASED ON THE VALUE OF THE STRUCTURE, RADON FEES AND
 COUNTY IMPACT FEES.
  
 12) THE INTERNAL PRESSURE COEFFICIENT SPECIFIED IS FOR
 AN ENCLOSED BUILDING. THIS BUILDING APPEARS TO BE
 EITHER OPEN. PLEASE SEE THE DEFINITIONS FOR OPEN AND
 PARTIALLY ENCLOSED BUILDINGS IN FBC 1609.2. SPECIFY ON
 THE PLANS WHETHER THE BUILDING IS DESIGNED AS OPEN,
 ENCLOSED OR PARTIALLY ENCLOSED AND AMEND THE COMPONENT
 AND CLADDING PRESSURES ACCORDINGLY.
  
 13) ADDITIONAL COMMENTS MAY RESULT BASED ON HOW THESE
 COMMENTS ARE ADDRESSED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By rmcdouga Date 2007-07-11 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2007-07-11 Time 15:59 Sent To Z
Notes
2007-07-11 16:19:30(PLAN REVIEW ONLY) DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE. THE
 EQUIPMENT PAD IS REQUIRED TO BE AT 7.5' ABOVE BFE.
  
 3) SUBMIT DETAILS FOR THE CONCRETE EQUIPMENT PAD AND
 SPECIFY HOW THE EQUIPMENT WILL BE ATTACHED TO RESIST
 WINDLOADS. SEE FBC 106.1.2* AND 1609.1.3.
  
 4) SPECIFY THE APPLICABLE WIND DESIGN DATA ON THE
 PLANS. SEE FBC 1603.1.4.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-09 Cont ID  
Sent By btrobaug Date 2007-10-09 Time 12:26 Rev Time 0.00
Received By btrobaug Date 2007-10-09 Time 11:43 Sent To B
Notes
2007-10-09 12:29:19 
  
 PROVISO
  
 PROVIDEIDENTIFICATIONPER 225.37, 2005 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By btrobaug Date 2007-09-25 Time 10:35 Rev Time 0.00
Received By btrobaug Date 2007-09-25 Time 10:24 Sent To  
Notes
2007-09-25 10:35:31 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PANEL DESIGNATIONS AND CIRCUIT NUMBERS GIVEN FOR
 THE EQUIPMENT ARE INCORRECT PER PERMITTED SET OF PLANS.
 THE GEAR SHOWN FEEDING THE COMPRESSERS ARE NOT ON THIS
 BUILDING. SEE 230.3
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By btrobaug Date 2007-06-13 Time 16:01 Rev Time 0.50
Received By btrobaug Date 2007-06-13 Time 15:39 Sent To  
Notes
2007-06-13 16:01:45 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PANEL DESIGNATIONS AND CIRCUIT NUMBERS GIVEN FOR
 THE EQUIPMENT ARE INCORRECT PER PERMITTED SET OF
 PLANS.
  
 2} SPECIFY COPPER OR ALUMINUM CONDUCTORSON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-02 Cont ID  
Sent By mawillia Date 2007-10-02 Time 16:53 Rev Time 0.00
Received By mawillia Date 2007-10-02 Time 16:22 Sent To  
Notes
2007-10-02 16:28:07*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ACKNOWLEDGED;HOWEVER THE CAPITALIZED GUIDES
 FOLLOWING THE COMMENTS WILL ENHANCE FIRE REVIEW
 APPROVAL.
  
  
  
 2.THE PRE-INSTALLATION OPERATIONS SHALL NOT INTERFERE
 OR HINDER EMERGENCY RESPONSE ACCESS TO THE SAID
 PROPERTY/BUILDING OR VICINITY THEREOF.ADD THIS
 COMMENT TO THE GENERAL NOTES ON SHEET 1
  
 3.THE PROPOSED EQUIPMENT APPEARS TO BE LOCATED
 BETWEEN TWO EXIT DOORS.PLEASE PROVIDE THE DISTANCE OF
 THE EQUIPMENT TO THESE OPENINGS (EXIT DOORS).YOUR
 RESPONSE OF "THE PAD IS SET TO THE SIDE OF EACH DOOR BY
 6 INCHES"IS ACKNOWLEDGED;CAN THIS BE SHOWN ON AN
 APPROPIATE LAYOUT OR DETAIL
  
 4.HOW WILL THE SAFETY OF PERSON(S) EXITING THROUGH
 THESE DOORS BE IMPACTED BY THE INSTALLATION OF THIS NEW
 EQUIPMENT.RESPONSE 4 ACKNOWLEDGED;ADD THIS RESPONSE
 TO THE GENERAL NOTES ON SHEET 1
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHEREON THE PLAN EACH ITEM WAS
 ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 17:04 Rev Time 0.00
Received By mawillia Date 2007-07-23 Time 16:37 Sent To  
Notes
2007-07-23 17:01:44*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED,
  
 2.THE PRE-INSTALLATION OPERATIONS SHALL NOT INTERFERE
 OR HINDER EMERGENCY RESPONSE ACCESS TO THE SAID
 PROPERTY/BUILDING OR VICINITY THEREOF.
  
 3.THE PROPOSED EQUIPMENT APPEARS TO BE LOCATED
 BETWEEN TWO EXIT DOORS.PLEASE PROVIDE THE DISTANCE OF
 THE EQUIPMENT TO THESE OPENINGS (EXIT DOORS)
  
 4.HOW WILL THE SAFETY OF PERSON(S) EXITING THROUGH
 THESE DOORS BE IMPACTED BY THE INSTALLATION OF THIS NEW
 EQUIPMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHEREON THE PLAN EACH ITEM WAS
 ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 11:53 Sent To  
Notes
2007-09-24 08:34:41TO "COMM" BD#20
2007-08-31 11:54:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 16:37 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 09:56 Sent To  
Notes
2007-06-12 09:56:31TO "TGORDON" DESK/PER "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-05 Cont ID  
Sent By rregueir Date 2007-10-05 Time 17:07 Rev Time 0.00
Received By rregueir Date 2007-10-05 Time 17:01 Sent To  
Notes
2007-10-05 17:06:59***********PROVISO**************
  
 PROVIDE START-UP REPORT FROM INGERSOLL RAND INDICATING
 THE EQUIPMENT IS ADEQUATELY PROTECTED FROM LOCAL
 WEATHER CONDITIONS PRIOR TO FINAL INSPECTION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 14:00 Rev Time 0.45
Received By tgordon Date 2007-09-28 Time 14:00 Sent To  
Notes
2007-09-28 14:12:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 IN FOR PERMIT
 *** DENIED ***
 1)A BUILDING PERMIT WILL BE REQUIRED BE FOR THE
 MECHANICAL PERMIT CAN PASS REVIEW. AS THE COMPRESSORS
 ARE NOT RATED FOR OUTDOOR INSTALLATION AND THE BUILDING
 IS GOING TO MEET THE140 MPH WIND LOAD REQUIREMENT.
  
 2) A BUILDING CONTRACTOR WILL NEED TO APPLY FOR THE
 BUILDING PERMIT AS THE WORK IS NOT IN THE SCOPE OF YOUR
 LICENSE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 11:18 Rev Time 0.30
Received By tgordon Date 2007-06-12 Time 11:18 Sent To E
Notes
2007-06-12 11:29:50FOR PLAN REVIEW ONLY NOT FOR PERMIT AT THIS TIME
 *** DENIED ***
 1) PLEASE SUBMIT MANUFACTURES INFORMATION SHOWING THAT
 THE AIR COMPRESSOR IS DESIGNED FOR OUT-DOOR USE.
  
 2) PLEASE PROVIDE A DETAIL SHOWING HOW THE EQUIPMENT IS
 TO BE ANCHORED FOR WIND LOADS, PER 2004 FBC 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-03 Cont ID  
Sent By mperson Date 2007-10-03 Time 11:27 Rev Time 0.00
Received By mperson Date 2007-10-03 Time 11:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 08:10 Rev Time 0.45
Received By mperson Date 2007-07-02 Time 08:10 Sent To B
Notes
2007-07-02 08:38:48DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 **FOR PLAN REVIEW ONLY NOT FOR PERMIT AT THIS TIME**
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: A COMPLETE ISOMETRIC RISER DIAGRAM WITH PIPE
 SIZES, VALVE LOCATIONS, QUICK-DISCONNETS, AND INCLUDING
 TJE UNDERGROUND PIPING AND CONNECTIONS.
  
 2. NOTE: PLEASE SUBMIT TWO COPIES OF MANUFACTURER
 SPECIFICATIONS/CUT SHEETS THAT SHOW A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) FOR THE
 FOLLOWING. PLEASE PROVIDE MANUFACTURER SHEETS THAT
 EQUIPMENT IS DESIGNED FOR OUTDOOR USE.
 A} INFINITY PIPE (90000 CALIBRATED ALUMINUM
 PIPING) AND FITTINGS (D20, D25, D32, D40MM).
 B} AIR COMPRESSORS.
 C} DRYER.
 D} TANK A & B.
 3. NOTE: PROVIDE A DETAIL INDICATING HOW THE EQUIPMENT
 IS TO BE ANCHORED FOR WIND LOADS PER THE FOLLOWING.
 FBC-2004
 A} SECTION, 1603.1.4 WIND DESIGN DATA.
 B} SECTION, 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIDING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-10 Cont ID  
Sent By jroach Date 2007-10-10 Time 17:36 Rev Time 0.00
Received By jroach Date 2007-10-10 Time 17:36 Sent To  
Notes
2007-10-10 17:37:15REVISION TO CONSTRUCT ENCLOSURE USING CHAIN-LINK WITH
 SLATS.....***PASSED***
  
 PROVISO - CHAIN LINK IS TO BE BLACK PVC COATED!!
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-24 Cont ID  
Sent By jroach Date 2007-09-24 Time 22:56 Rev Time 0.00
Received By jroach Date 2007-09-24 Time 22:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-22 Cont ID  
Sent By jroach Date 2007-07-22 Time 21:11 Rev Time 0.00
Received By jroach Date 2007-07-22 Time 21:11 Sent To I
Notes
2007-07-22 21:13:56***FAILED***
  
 1) MINOR AMENDMENT TO THE RYBOVICH SPENCER COMMERCIAL
 MARINE PLANNED DEVELOPMENT (CMPD) SHALL BE SUBMITTED
 TO, AND APPROVED BY, THE PLANNING AND ZONING DEPARTMENT
 PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 2) MECHANICAL EQUIPMENT SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED.SCREENING SHALL
 CONSIST OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COPMARABLY DURABLE WOOD AND STEEL.WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO (2) FOOT INTERVALS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.