Plan Review Details - Permit 07060276
Plan Review Stops For Permit 07060276
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By jwitmer Date 2007-07-17 Time 15:54 Rev Time 0.75
Received By jwitmer Date 2007-07-16 Time 22:17 Sent To  
Notes
2007-07-17 16:21:19BUILDING PLAN REVIEW
 PERMIT: 07060276
 ADD: 1700 PALM BEACH LAKES BLVD
 CONT: ALL-PRO ELECTRICAL
 TEL: (561)239-3097
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
  
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED INDICATE THEY WERE PRODUCED BY KAMM
 CONSULTING ENGINEERING, THEY APPEAR TO BE COPIES,
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 4) THE VALUE OF THE PERMIT IS LOW, THE TOTAL JOB COST
 ARE TO INCLUDE THEOWNER BAUGHTGENERATOR. IF THE
 VALUE IS NOT DECLARED THE CITY WILL USE MARSHALL &
 SWIFT TO ESTAMATE THE VALUES AND THE PERMIT FEES WILL
 BE ADJUSTED ACCORDINGLY. 108.3 FLB ADMINISTRATIVE
 CODE.
  
 5) PLEASE PROVIDE A SITE PLAN WITH THE LOCATION OF THE
 GENERATOR AND ALL BUILDINGS PROVIDE DIMENSIONS OF
 CLOSENESS TO BUILDINGS AND ALSO INDICATE WINDOWS AND
 DOORS IN THE WALLS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 6) PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR
 VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE
 VENTS, ETC.
  
 MECHANICAL CODE 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE MOUNTED
 DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY
 FROM AN OIL TANK VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED
 GRADE.
  
 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219
 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1
 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO PREVENT RAIN
 FROM ENTERING THE VENT SYSTEM.
 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICALEXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN ATTIC OR
 CRAWL SPACE
  
 401.5 OPENING LOCATION. OUTDOOR AIR EXHAUST AND INTAKE
 OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET (3048
 MM) FROM LOT LINES OR BUILDINGS ON THE SAME LOT. WHERE
 OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO
 THE CENTERLINE OF THE STREET OR PUBLIC WAY.
  
 7) GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 18:06 Sent To  
Notes
2007-06-23 18:32:39*** UNSAT ***
  
 ** AS THERE IS SUBSTANTIAL INFORMATION NOT SUBMITTED,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW AS
 MANY ITEMS CAN NOT BE REVIEWED FOR CODE COMPLIANCE.
  
 1) NOTE: PLEASE SUBMIT PLANS DONE BY AN ENGINEER PER FS
 471.003(2)(H)(2A)
 THE SCOPE OF WORK DOES NOT MEET THE EXCEPTIONS FOR AN
 ELECTRICAL CONTRACTOR.
 PLEASE SEE COMMENTS FROM BUILDING FOR POSSIBLE REQUIRED
 ENGINEER SLAB/TIE DOWN INFORMATION.
  
 2) NOTE:PLEASE SUBMIT COMPLETED SITE PLANS, SURVEY
 ETC. PLEASE SEE ZONING AND COMMENTS FROM OTHER TRADES
 FOR PLANS NEEDED. THE SIZE OF THE TANK WILL HAVE
 COMMENTS FROM MECHANICAL REVIEWER.
 PLEASE SEE BUILDING COMMENTS AS NO PLANS WERE SUBMITTED
 FOR SLAB, CONNECTIONS, ETC.
 PLEASE INDICATE ALL DIMENSIONS ON PLANS, SITE PLANS,
 AND SURVEY.
 PLEASE PROVIDE INFORMATION IF IN A FLOOD ZONE AND KNOW
 THE ELEVATION WILL BE NEEDED ON PLANS.
 FBC 106.1, 106.3.5.1.2
 THERE ARE SEVERAL ITEMS NOT KNOWN AT THIS TIME AND CAN
 NOT BE REVIEWED.
  
 3) NOTE: PLEASE KNOW THE FOLLOWING CODES WILL BE
 REQUIRED ON PLANS FOR DESIGN AND SCOPE OF WORK.
 2004 FBC W/2006 REVISIONS.
 2002 NFPA-110
 2005 NFPA-70
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR
 OTHER CODES WHICH MAY BE REQUIRED.
  
 4) NOTE: PLEASE SUBMIT TWO COMPLETE PACKAGES OF
 MANUFACTURE SPECS/CUT SHEETS FOR ALL EQUIPMENT
 INCLUDING THE FOLLOWING.
 GENERATOR, GENERATOR ENCLOSURE, FUEL TANK(S) ETC.
 SOME OF THESE ITEMS WILL BE REVIEW BY OTHER TRADE(S).
 NEC 110.3, 90.7.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 GENERATOR, ATS, MAIN(S), DESIGN COSTS ETC EVEN IF ANY
 OF THIS IS OWNER SUPPLIED.
 THE VALUE AS SHOWN IS EXTREMELY LOW AND A VALUE MAY BE
 ASSESSED BY THIS OFFICE BASED ON GUIDES ADOPTED BY THE
 FLORIDA BUILDING CODE.
 THE COST SHALL INCLUDE ALL.
 FBC 108.3
  
 6) NOTE: PLEASE SUBMIT PLANS WITH A COMPLETE LAYOUT OF
 ALL EXISTING ELECTRICAL SERVICE EQUIPMENT AT THIS
 BUILDING. PLEASE INDICATE ALL MAINS, DISCONNECTS ETC.
 AT THIS TIME AS THE LOCATION OF THESE ITEMS ARE NOT
 CLEAR, NO REVIEW OF LOCATIONS CAN BE DONE.
 PLEASE KNOW THAT NO DISCONNECTING MEANS IS SHOWN AND
 ONE WILL BE REQUIRED. PLEASE KNOW THE BREAKER IN THE
 GENERATOR MAY NOT BE USED DUE TO REQUIREMENTS FROM
 ZONING AND DOES NOT MEET THE EXCEPTIONS IN THE NEC.
 FBC 106.1.2, 106.3.5.1.2
 NEC 230.70,230.71,230.72, 225.31-225.39, 702.11 PLEASE
 SEE MISSING DISCONNECTING MEANS AS REQUIRED. THIS IS
 BASED ON NO INFORMATION PROVIDED.
  
 6) NOTE: PLEASE PROVIDE THE OCP ON THE GENERATOR.
 FBC 106.1.2, NEC 240.4, 310.16, 445.13 ETC.
  
 7) NOTE: PLEASE PROVIDE COMPLETED ROUTE OF CONDUITS FOR
 REVIEW. PLEASE KNOW IF ANY RATED WALLS ARE PENETRATED,
 MUST PROVIDE THE UL LISTING, ANSI, ASTM STANDARDS ETC.
 THESE WALL DETAILS WILL BE REVIEWED AND RATINGS ON
 WALLS WILL BE NEEDED. THERE ARE RATED WALLS BASED ON
 THE BRIEF INFORMATION PROVIDED AND THIS INFORMATION IS
 NEEDED.
 FBC 106.1.2, 106.3.5.1.2
 NEC 300.21
  
 ** ALL COMMENTS ABOVE SHOULD BE FORWARDED TO THE
 ENGINEER WHO WILL BE TAKING OVER PROJECT AND MAY NEED
 THIS INFORMATION FROM REVIEWER(S).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 21:03 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 20:43 Sent To  
Notes
2007-07-26 21:02:49*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 110.
  
 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4.PROVIDE DISTANCE OF AT LEAST 10' TO BUILDING
 OPENINGS ARE ACHIEVED.
  
 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE GENERATOR
 AND ASSOCIATED EQUIPMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 20:44 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 10:14 Sent To  
Notes
2007-06-22 16:37:37TO "COMM" BD#1
2007-06-11 11:17:23WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By rregueir Date 2007-07-12 Time 09:05 Rev Time 0.00
Received By rregueir Date 2007-07-12 Time 08:32 Sent To  
Notes
2007-07-12 09:30:54-----------------DENIED----------------
  
 1. THE INSTALLATION OF THE GENERATOR AND ALL RELATED
 MATERIALS AND EQUIPMENT SHALL BE INCLUDED IN THE SCOPE
 OF WORK FOR THIS PERMIT. THE PERMIT VALUATION SHALL BE
 ADJUSTED TO INCLUDE THE ENTIRE SCOPE OF WORK PER FBC
 108.3.
  
 2. A PENALTY OF 300 PERCENT OF THE USUAL PERMIT FEE IN
 ADDITION TO THE REQUIRED PERMIT FEE IS DUE AS THE WORK
 HAS COMMENCED PRIOR TO PERMIT ISSUANCE PER FBC 108.4.
  
 3. PROVIDE ALL RELEVANT DOCUMENTATION, TWO SETS,
 RELATED TO THE EXPANDED SCOPE OF WORK INCLUDING
 GENERATOR SUBMITTAL, TYPE OF FUEL, MEANS OF FUEL
 STORAGE. ALSO, PROVIDE A SITE PLAN SHOWING LOCATION OF
 EQUIPMENT, DISTANCES FROM PROPERTY LINES AND ADJACENT
 BUILDINGS, LOCATION OF GENERATOR EXHAUST AND PROTECTION
 FROM VEHICLE DAMAGE IF APPLICABLE.
  
 NOTE: ABOVE GROUND FUEL TANKS OF 550 GALLONS OR MORE
 REQUIRE THE APPROVAL OF THE PALM BEACH COUNTY
 DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT. FOR
 ADDITIONAL INFORMATION PLEASE CONTACT THEM AT
 561-233-2400 OR WWW.PBCGOV.COM/ERM/
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By jroach Date 2007-06-26 Time 18:05 Rev Time 0.00
Received By jroach Date 2007-06-26 Time 18:04 Sent To  
Notes
2007-06-26 18:10:25***FAILED***
  
 1) TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED
 SHOWING THE LOCATION OF THE GENERATOR.SETBACK
 DIMENSIONS SHALL BE PROVIDED FROM ALL PROPERTY LINES.
  
 2) TWO (2) COPIES OF A CURRENT SURVEY SHALL BE PROVIDED
 SHOWING THE LOCATION OF ALL ON-SITE IMPROVEMENTS,
 EASEMENTS, ETC.
  
 3) GENERATORS SHALL BE SCREENED ACCORDING TO SECTION
 94-444(B) OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.A FOUR-SIDED ENCLOSURE SHALL BE PROVIDED
 AND SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL.THE ENCLOSURE SHALL BE LANDSCAPED WITH
 SHRUBS PLANTED AT TWO (2) FOOT INTERVALS.
  
 QUESTONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.