| Plan Review Stops For Permit 07060275 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-01-07 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-01-07 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-11-19 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-11-15 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2007-11-19 16:30:21 | SITE ADDRESS IS CORRECT AS 4335 EASLEY DR .PERMIT WAS | | | CORRECTLY ASIGNED TO THIS ADDRESS. | | | | | | QUESTIONS/COMMENTS ,PLEASE CONTACT: | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] | | | | | 2007-11-15 14:17:52 | APPL READS 4325 N. HAVERHILL RD. COPY OF APPL SENT TO | | | LILI |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-30 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-30 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-11 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-10 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2007-10-11 08:23:34 | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07060275 | | | ADD: 4325 N. HAVERHILL RD | | | CONT: JOE SCHMIDT CONST. INC. | | | TEL: (561)748-7811 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | 10/11/07 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)SINKS REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 | | | SHALL COMPLY WITH SECTION 11-4.24. SHOW COMPLIANCE. | | | **NOTED** | | | HOWEVER, SHEET 3 ELEVATION #3 SHALL INDICATE THE | | | REQUIRED DIMENSIONS FOR THE HEIGHT OF THE COUNTER, KNEE | | | CLEARANCE, DEPTH OF THE SINK, CLEAR FLOOR SPACE ETC. | | | THE COUNTER SHALL NOT BE HIGHER THAN 34 INCHES ABOVE | | | THE FINISH FLOOR. CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND SHOW SUFFICIENT CLARITY TO INDICATE THE | | | NATURE AND EXTENT OF THE WORK PROPOSED. 106.1.1 | | | | | | 3)61G15-23.002.ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. | | | THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER SHALL BE | | | ON EACH PAGE. | | | **NOTED** | | | WPB AMENDMENTS.106.1.3 THE BUILDING OFFICIAL MAY | | | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR | | | PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE | | | CONFORMITY TO ITS RECORD RETENTIONS PROGRAM. THE ?HAND | | | WRITTEN? INFORMATION ON THE DRAWINGS IS NOT ACCEPTABLE. | | | SUBMIT TWO NEW SETS OF DRAWINGS WITH ALL REQUIRED | | | INFORMATION. | | | | | | NOTE:IF THIS IS A TYPE I OR II BUILDING, THE BACKING | | | FOR THE CABINETS SHALL BE FIRE RETARDANT-TREATED WOOD. | | | **OK** | | | | | | **NEW** | | | 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO | | | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR | | | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION | | | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected]. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-21 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-20 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2007-06-20 18:57:24 | BUILDING PLAN REVIEW | | | PERMIT: 07060275 | | | ADD:4325 N. HAVERHILL RD | | | CONT: JOE SCHMIDT CONST. INC. | | | TEL: (561)748-7811 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)SINKS REQUIREDTO BE ACCESSIBLE BY SECTION 11-4.1 | | | SHALL COMPLY WITH SECTION 11-4.24. SHOW COMPLIANCE. | | | | | | 3)61G15-23.002.ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. | | | THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER SHALL BE | | | ON EACH PAGE. | | | | | | NOTE:IF THIS IS A TYPE I OR II BUILDING, THE BACKING | | | FOR THE CABINETS SHALL BE FIRE RETARDANT-TREATED WOOD. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-04 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-04 |
Time |
16:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-20 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-20 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2007-06-20 09:51:43 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} IT IS UNCLEAR IF THERE IS ANY ELECTRICAL WORK ADDED | | | WITH THIS PERMIT OR IF IT IS EXISTING. PLEASE CLARIFY | | | NEW (IF ANY) FROM EXISTING ON THE PLAN. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY.THE ENGINEER MUST PROVIDE THEIR | | | TITLE BLOCK. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-01-07 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-07 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2008-01-07 10:24:49 | PERMIT APPLICATION HAS BEEN CORRECTED TO REFLECT THE | | | ADDRESS INDICATED IN TITLE BLOCK OF EACH SHEET. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-11-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-29 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-29 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2007-11-29 12:05:33 | *****UNSAT***** | | | | | | | | | | | | | | | 1.THE NUMERICAL ADDRESS IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET DOES NOT CORRELATE WITH THE | | | ADDRESS AS SHOWN IN OUR SYSTEM WHICH IS 4335 EASLEY | | | DRIVE.THE UPDATED PLANS ARE TO BE SUBMITTED WITH NO | | | INK, PENCIL, OR WHITE-OUTED MARKINGS | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-15 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-15 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2007-10-15 12:03:06 | *****DENIED***** | | | | | | THE FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEEDS TO BE ADDRESSED: | | | | | | | | | 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET.THE UPDATED PLANS ARE TO | | | BE SUBMITTED WITH NO INK, PENCIL, OR WHITE-OUTED | | | MARKINGS | | | | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-06-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-04 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-23 |
Time |
21:23 |
Sent To |
|
|
| Notes |
| 2007-06-23 21:33:39 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE REMOVAL AND/OR THE STOCKING OF NEW BUILDING | | | MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER WITH | | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | | THEREOF (INCLUDING STREETS, ROADS, FIRE LANES). | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-15 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-15 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2007-11-19 10:01:30 | TO "BOB"#1 | | 2007-11-15 14:22:30 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-27 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-27 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2007-10-01 14:37:52 | TO "BOB"#17 | | 2007-09-27 10:28:31 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-06-26 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-06-11 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2007-06-12 08:25:37 | TO "BOB"#10 | | 2007-06-11 09:22:05 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-10-17 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-10-17 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2007-10-17 14:17:17 | NO MECHANICAL WORK ON THIS PLANLM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-06-26 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-06-26 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2007-06-26 08:25:23 | SHOW A DETAIL OF CANOPY TO BE INSTALLED OVER SINK I | | | AND ANY OTHER MECHANICAL WORK TO BE DONEUNDER THIS SET | | | OF PLANS. | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-10 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-10 |
Time |
07:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-12 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-12 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2007-10-12 10:04:59 | DENIED; | | | 1. PAGE 3 ELEVATION 3; PLEASE SHOW ALL MEASUREMENTS | | | REQUIRED TO MEET THE ACCESSIBILITY CODE FOR SINKS FBC | | | BUILDING CHAPTER 11 SECTIONS 11-4.24.1 THRU 11-4.24.7. | | | 2. SEE BUILDING PLAN REVIEWER'S NOTE # 3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-06-26 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-06-26 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2007-06-26 08:17:55 | DENIED; | | | 1. THE PERSON TAKING RESPONSIBILTY FOR THE DESIGN MUST | | | PRINTSIGN, AND DATE THEIR NAME TO SAME PER | | | 106.3.4.3. FBC CHAPTER 1. | | | 2. SHEET 2 NEW DRENCH SHOWER AND EYE WASH EMERGENCY | | | EQUIPMENT; PLEASE SUPPLY CUT SHEETS FROM MANUFACTURE. | | | 3. SCOPE OF PLUMBING WORK IS NOT CLEAR. | | | A) IS LOCATION OF SINKS BEING MOVED? SHOW | | | DEMO PAGE. | | | B) IS ANY GAS OR COMPRESSED AIR LINES BEING | | | RELOCATED? | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|