| 2007-12-03 12:11:32 | |
| | |
| | PERMIT #07060228 |
| | ELECTRICAL PLAN REVIEW |
| | 826 HIGH STREET |
| | 12/3/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} THESE ITEMS THAT WERE REDLINED ON THE PERMIT SET OF |
| | PLANS WERE NOT INCLUDED ON THE REVISION. INCLUDE SAME |
| | FOR COMPLIANCE WITH THE FOLLOWING ARTICLES. |
| | |
| | A) 210.63 HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT OUTLET |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| | SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING MEANS. |
| | |
| | B) 210.8(A) DWELLING UNITS ALL 125-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED |
| | IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL |
| | HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | 210.8(A)(6) KITCHENS ? WHERE THE RECEPTACLES ARE |
| | INSTALLED TO SERVE THE COUNTERTOP SURFACES. |
| | |
| | C) 210.52 DWELLING UNIT RECEPTACLE OUTLETS. (E) |
| | OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING AND EACH UNIT |
| | OF A TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT |
| | LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT GRADE LEVEL |
| | AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE GRADE SHALL |
| | BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | |
| | THIS IS A COMMENT GENERATED BY THE REVISION SUBMITTED. |
| | |
| | 2} THE NOTE ON THE PLAN INDICATES A WALL BEING REMOVED, |
| | BUT THE WALL REMAINS INCLUDED IN THE REVISION, AND |
| | DEVICES ARE LOCATED ON SAME. RESUBMIT REVISION TO |
| | CLEARLY INDICATE THE SCOPE OF THE WORK TO BE DONE. |
| | 106.1.3 FBC AS AMENDED. |
| | |
| | 3} IT IS UNCLEAR WHAT THE SYMBOLS AT THE SINK REFER TO, |
| | PLEASE CLARIFY. 106.1.3 FBC. |
| | |
| | 4} THIS IS A REVISION, NOT A SUBMITTAL, FEES ARE DUE, |
| | PAY SAME WHEN PLANS ARE PICKED UP. |
| | |
| | NOTE: A BUILDING REVISION IS REQUIRED FOR REMOVING THE |
| | WALL. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |