Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By btrobaug Date 2007-12-03 Time 12:11 Rev Time 0.00
Received By btrobaug Date 2007-12-03 Time 11:33 Sent To PC
Notes
2007-12-03 12:11:32 
  
 PERMIT #07060228
 ELECTRICAL PLAN REVIEW
 826 HIGH STREET
 12/3/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THESE ITEMS THAT WERE REDLINED ON THE PERMIT SET OF
 PLANS WERE NOT INCLUDED ON THE REVISION. INCLUDE SAME
 FOR COMPLIANCE WITH THE FOLLOWING ARTICLES.
  
 A) 210.63 HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.
  
 B) 210.8(A) DWELLING UNITS ALL 125-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED
 IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 210.8(A)(6) KITCHENS ? WHERE THE RECEPTACLES ARE
 INSTALLED TO SERVE THE COUNTERTOP SURFACES.
  
 C) 210.52 DWELLING UNIT RECEPTACLE OUTLETS. (E)
 OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING AND EACH UNIT
 OF A TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT
 LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT GRADE LEVEL
 AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  
 THIS IS A COMMENT GENERATED BY THE REVISION SUBMITTED.
  
 2} THE NOTE ON THE PLAN INDICATES A WALL BEING REMOVED,
 BUT THE WALL REMAINS INCLUDED IN THE REVISION, AND
 DEVICES ARE LOCATED ON SAME. RESUBMIT REVISION TO
 CLEARLY INDICATE THE SCOPE OF THE WORK TO BE DONE.
 106.1.3 FBC AS AMENDED.
  
 3} IT IS UNCLEAR WHAT THE SYMBOLS AT THE SINK REFER TO,
 PLEASE CLARIFY. 106.1.3 FBC.
  
 4} THIS IS A REVISION, NOT A SUBMITTAL, FEES ARE DUE,
 PAY SAME WHEN PLANS ARE PICKED UP.
  
 NOTE: A BUILDING REVISION IS REQUIRED FOR REMOVING THE
 WALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-02 Cont ID  
Sent By btrobaug Date 2007-07-02 Time 07:19 Rev Time 0.00
Received By btrobaug Date 2007-07-02 Time 07:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 12:17 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 11:33 Sent To I
Notes
2007-06-18 12:11:30 
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE FOUR SETS OF PLANS SUBMITTED THAT DO NOT
 MATCH. SUBMIT TWO COPIES OF PLANS, THAT ARE ALIKE, FOR
 REVIEW. THE PLANS MUST BE DRAWN WITH ENOUGH CLARITY TO
 DETERMINE SPACING REQUIREMENTS ARE CORRECT PER CODE.
 BATHS AND KITCHEN MUST INCLUDE CABINET LAYOUT.
  
 2} HAND DRAWN PLANS IN PENCIL ARE NOT ACCEPTABLE FOR
 RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3 FBC
 AS AMENDED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 4] THE PLANS INCLUDED A RISER DIAGRAM, BUT A NOTE
 INDICATES THAT THE SERVICE IS EXISTING. PLEASE REMOVE
 ALL PLANS THAT ARE NOT TO BE IN THE SCOPE OF THIS
 APPLICATION.
  
 5} INCLUDE THE CONDUCTOR SIZES ON THE PANEL SCHEDULE SO
 COMPLIANCE WITH 310.16 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 12:40 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 12:40 Sent To E
Notes
2007-11-27 12:40:50TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 13:24 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 13:24 Sent To E
Notes
2007-06-27 13:24:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 12:19 Rev Time 0.00
Received By btrobaug Date 2007-06-08 Time 16:58 Sent To PC
Notes
2007-06-08 16:58:26TO "E" BOX