Plan Review Details - Permit 07060216
Plan Review Stops For Permit 07060216
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-16 Cont ID  
Sent By shill Date 2008-01-16 Time 10:10 Rev Time 0.00
Received By shill Date 2008-01-16 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By shill Date 2007-12-03 Time 11:46 Rev Time 0.00
Received By shill Date 2007-12-03 Time 11:46 Sent To  
Notes
2007-12-03 11:47:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 FROM PREVIOUS LISTS:
  
 1.)THE GC HAS REQUESTED A ROOF PERMIT.GC CAN ONLY
 INSTALL NAIL ON SYSTEMS (SHINGLES OR SHAKE).MODIFIED
 AND TILE ARE NOT WITHIN THE SCOPE OF A GC LICENSE.
  
 ROOFING CONTRACTOR REQUIRED.PLEASE HAVE A ROOFING
 CONTRACTOR SIGN ON AS A SUBCONTRACTOR.
  
 2.)PROVIDE THE SITE PLAN WHICH WAS PREVIOUSLY IN THE
 PACKAGE; TWO SETS, STAMPED BY ZONING.
  
 3.)PROVIDE ROOF PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 10:08 Rev Time 0.00
Received By shill Date 2007-09-25 Time 10:08 Sent To  
Notes
2007-09-25 10:13:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 FROM PREVIOUS LIST:
  
 1.)THE GC HAS REQUESTED A ROOF PERMIT.GC CAN ONLY
 INSTALL NAIL ON SYSTEMS (SHINGLES OR SHAKE).MODIFIED
 AND TILE ARE NOT WITHIN THE SCOPE OF A GC LICENSE.
  
 ROOFING CONTRACTOR REQUIRED.PLEASE HAVE A ROOFING
 CONTRACTOR SIGN ON AS A SUBCONTRACTOR.
  
 2.)ADDRESSED.
  
 3.)THE ENGINEER'S SIGNATURE IS TO BE AN ORIGINAL
 SIGNATURE; PHOTOCOPIES WERE SUBMITTED.
  
 2ND REVIEW, CONTRACTOR WROTE A NOTE STATING THAT
 SIGNATURES ARE DIFFERENT.COMPARE SHEET 1 TO SHEET 1,
 SHEET 2 TO SHEET 2.THE SIGNATURES ARE ALL
 PHOTOCOPIES, ALL REQUIRED TO BE ORIGINALS.
  
 4-6.)ADDRESSED.
  
 NEW COMMENT:
  
 7.)DECLARE WIND DESIGN CRITERIA FOR THE WALLS,
 FBC301.PLANS STATE "WIND BREAK".WIND DESIGN
 CRITERIA PROVIDED FOR ROOF ONLY.PRODUCT APPROVALS
 WERE SUBMITTED BUT THE SUPPORTING DOCUMENTATION
 (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) WAS NOT
 INCLUDED.CODE COMPLIANCE CANNOT BE DETERMINED DUE TO
 INSUFFICIENT INFORMATION PROVIDED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By shill Date 2007-07-13 Time 09:28 Rev Time 0.00
Received By shill Date 2007-07-13 Time 09:28 Sent To E
Notes
2007-07-13 09:33:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE GC HAS REQUESTED A ROOF PERMIT.GC CAN ONLY
 INSTALL NAIL ON SYSTEMS (SHINGLES OR SHAKE).MODIFIED
 AND TILE ARE NOT WITHIN THE SCOPE OF A GC LICENSE.
  
 2.)ADDITIONAL FEES DUE (RADON), SEE ATTACHED.
  
 3.)THE ENGINEER'S SIGNATURE IS TO BE AN ORIGINAL
 SIGNATURE; PHOTOCOPIES WERE SUBMITTED.
  
 4.)PROVIDE INFORMATION IN REGARDS TO THE ROOMS IN THE
 HOUSE WHICH OPEN INTO THIS AREA, EITHER WITH WINDOWS OR
 WITH DOORS.SHOW HOW EMERGENCY EGRESS FOR BEDROOMS IS
 AFFECTED, FBC R 310.
  
 5.)THE APPLICATION STATES THAT A BITUMEN ROOF WILL BE
 INSTALLED, PLANS SHOW THAT TILE WILL BE INSTALLED TO
 MATCH THE EXISTING HOUSE.CLARIFY SCOPE OF WORK.SHOW
 ROOF PITCH ON THE PLAN.
  
 6.)PROVIDE PRODUCT APPROVALS FOR THE DOOR, WINDOWS,
 ROOF, ROOF PANELS.WWW.FLORIDABUILDING.ORG, FAC9B72

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-11 Cont ID  
Sent By btrobaug Date 2008-01-11 Time 10:18 Rev Time 0.00
Received By btrobaug Date 2008-01-11 Time 10:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-11-26 Cont ID  
Sent By btrobaug Date 2007-11-26 Time 08:21 Rev Time 0.00
Received By btrobaug Date 2007-11-26 Time 07:46 Sent To B
Notes
2007-11-26 08:21:16 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 SAME COMMENTS AS PREVIOUS TWO REVIEWS:
  
 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK
 INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO
 REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT
 PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC
 AS AMENDED.
  
 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH
 210.52(A)(1 & 2), IN THE SUNROOM.* CLARIFY IF THIS IS A
 SUNROOM OR SCREEN ENCLOSURE.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.3.4.3.FBC.. * THIS INCLUDE THE ELECTRICAL SHEETS.
 THE PLANS MUST BE DRAWN WITH CLARIT PER 106.1.3 FBC AS
 AMENDED.
  
 RESPOND TO ALL COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By btrobaug Date 2007-09-25 Time 07:19 Rev Time 0.00
Received By btrobaug Date 2007-09-25 Time 07:06 Sent To B
Notes
2007-09-25 07:19:14 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 SAME COMMENTS AS PREVIOUS REVIEW.
  
 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK
 INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO
 REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT
 PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC
 AS AMENDED.
  
 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH
 210.52(A)(1 & 2), IN THE SUNROOM.* CLARIFY IF THIS IS A
 SUNROOM OR SCREEN ENCLOSURE.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.3.4.3.FBC.. * THIS INCLUDE THE ELECTRICAL SHEETS.
 THE PLANS MUST BE DRAWN WITH CLARIT PER 106.1.3 FBC AS
 AMENDED.
  
 RESPOND TO ALL COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By btrobaug Date 2007-07-13 Time 12:23 Rev Time 0.00
Received By btrobaug Date 2007-07-13 Time 11:33 Sent To PC
Notes
2007-07-13 12:23:45 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK
 INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO
 REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT
 PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC
 AS AMENDED.
  
 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH
 210.52(A)(1 & 2), IN THE SUNROOM.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.3.4.3.FBC..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-08 Cont ID  
Sent By adarroug Date 2008-01-08 Time 16:30 Rev Time 0.00
Received By adarroug Date 2008-01-08 Time 16:30 Sent To E
Notes
2008-01-08 16:33:19TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 15:47 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 15:47 Sent To E
Notes
2007-11-19 15:48:32TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 16:13 Sent To E
Notes
2007-09-18 16:13:51TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 09:15 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 09:15 Sent To B
Notes
2007-06-11 09:16:09TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-13 Cont ID  
Sent By shill Date 2007-07-13 Time 09:33 Rev Time 0.00
Received By shill Date 2007-06-08 Time 13:16 Sent To  
Notes
2007-06-08 13:16:42TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-06-08 Cont ID  
Sent By choops Date 2007-06-08 Time 16:38 Rev Time 0.00
Received By choops Date 2007-06-08 Time 16:38 Sent To I
Notes
2007-06-08 16:39:58PROVISO:SCREEN ENCLOSURE TO BE A MINIMUM OF 3' AWAY
 FROM SIDE PROPERTY LINE.