| Plan Review Stops For Permit 07060216 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-16 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-16 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-03 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-03 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2007-12-03 11:47:02 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | FROM PREVIOUS LISTS: | | | | | | 1.)THE GC HAS REQUESTED A ROOF PERMIT.GC CAN ONLY | | | INSTALL NAIL ON SYSTEMS (SHINGLES OR SHAKE).MODIFIED | | | AND TILE ARE NOT WITHIN THE SCOPE OF A GC LICENSE. | | | | | | ROOFING CONTRACTOR REQUIRED.PLEASE HAVE A ROOFING | | | CONTRACTOR SIGN ON AS A SUBCONTRACTOR. | | | | | | 2.)PROVIDE THE SITE PLAN WHICH WAS PREVIOUSLY IN THE | | | PACKAGE; TWO SETS, STAMPED BY ZONING. | | | | | | 3.)PROVIDE ROOF PRODUCT APPROVALS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-25 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-25 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2007-09-25 10:13:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | FROM PREVIOUS LIST: | | | | | | 1.)THE GC HAS REQUESTED A ROOF PERMIT.GC CAN ONLY | | | INSTALL NAIL ON SYSTEMS (SHINGLES OR SHAKE).MODIFIED | | | AND TILE ARE NOT WITHIN THE SCOPE OF A GC LICENSE. | | | | | | ROOFING CONTRACTOR REQUIRED.PLEASE HAVE A ROOFING | | | CONTRACTOR SIGN ON AS A SUBCONTRACTOR. | | | | | | 2.)ADDRESSED. | | | | | | 3.)THE ENGINEER'S SIGNATURE IS TO BE AN ORIGINAL | | | SIGNATURE; PHOTOCOPIES WERE SUBMITTED. | | | | | | 2ND REVIEW, CONTRACTOR WROTE A NOTE STATING THAT | | | SIGNATURES ARE DIFFERENT.COMPARE SHEET 1 TO SHEET 1, | | | SHEET 2 TO SHEET 2.THE SIGNATURES ARE ALL | | | PHOTOCOPIES, ALL REQUIRED TO BE ORIGINALS. | | | | | | 4-6.)ADDRESSED. | | | | | | NEW COMMENT: | | | | | | 7.)DECLARE WIND DESIGN CRITERIA FOR THE WALLS, | | | FBC301.PLANS STATE "WIND BREAK".WIND DESIGN | | | CRITERIA PROVIDED FOR ROOF ONLY.PRODUCT APPROVALS | | | WERE SUBMITTED BUT THE SUPPORTING DOCUMENTATION | | | (EVALUATION REPORT, INSTALLATION INSTRUCTIONS) WAS NOT | | | INCLUDED.CODE COMPLIANCE CANNOT BE DETERMINED DUE TO | | | INSUFFICIENT INFORMATION PROVIDED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-13 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-13 |
Time |
09:28 |
Sent To |
E |
|
| Notes |
| 2007-07-13 09:33:12 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)THE GC HAS REQUESTED A ROOF PERMIT.GC CAN ONLY | | | INSTALL NAIL ON SYSTEMS (SHINGLES OR SHAKE).MODIFIED | | | AND TILE ARE NOT WITHIN THE SCOPE OF A GC LICENSE. | | | | | | 2.)ADDITIONAL FEES DUE (RADON), SEE ATTACHED. | | | | | | 3.)THE ENGINEER'S SIGNATURE IS TO BE AN ORIGINAL | | | SIGNATURE; PHOTOCOPIES WERE SUBMITTED. | | | | | | 4.)PROVIDE INFORMATION IN REGARDS TO THE ROOMS IN THE | | | HOUSE WHICH OPEN INTO THIS AREA, EITHER WITH WINDOWS OR | | | WITH DOORS.SHOW HOW EMERGENCY EGRESS FOR BEDROOMS IS | | | AFFECTED, FBC R 310. | | | | | | 5.)THE APPLICATION STATES THAT A BITUMEN ROOF WILL BE | | | INSTALLED, PLANS SHOW THAT TILE WILL BE INSTALLED TO | | | MATCH THE EXISTING HOUSE.CLARIFY SCOPE OF WORK.SHOW | | | ROOF PITCH ON THE PLAN. | | | | | | 6.)PROVIDE PRODUCT APPROVALS FOR THE DOOR, WINDOWS, | | | ROOF, ROOF PANELS.WWW.FLORIDABUILDING.ORG, FAC9B72 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-11 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-11 |
Time |
10:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-26 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-26 |
Time |
07:46 |
Sent To |
B |
|
| Notes |
| 2007-11-26 08:21:16 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | SAME COMMENTS AS PREVIOUS TWO REVIEWS: | | | | | | 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK | | | INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO | | | REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT | | | PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC | | | AS AMENDED. | | | | | | 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH | | | 210.52(A)(1 & 2), IN THE SUNROOM.* CLARIFY IF THIS IS A | | | SUNROOM OR SCREEN ENCLOSURE. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.3.4.3.FBC.. * THIS INCLUDE THE ELECTRICAL SHEETS. | | | THE PLANS MUST BE DRAWN WITH CLARIT PER 106.1.3 FBC AS | | | AMENDED. | | | | | | RESPOND TO ALL COMMENTS IN WRITING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-25 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-25 |
Time |
07:06 |
Sent To |
B |
|
| Notes |
| 2007-09-25 07:19:14 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | SAME COMMENTS AS PREVIOUS REVIEW. | | | | | | 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK | | | INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO | | | REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT | | | PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC | | | AS AMENDED. | | | | | | 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH | | | 210.52(A)(1 & 2), IN THE SUNROOM.* CLARIFY IF THIS IS A | | | SUNROOM OR SCREEN ENCLOSURE. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.3.4.3.FBC.. * THIS INCLUDE THE ELECTRICAL SHEETS. | | | THE PLANS MUST BE DRAWN WITH CLARIT PER 106.1.3 FBC AS | | | AMENDED. | | | | | | RESPOND TO ALL COMMENTS IN WRITING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-13 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-13 |
Time |
11:33 |
Sent To |
PC |
|
| Notes |
| 2007-07-13 12:23:45 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PLANS AREN'T CLEAR AS TO THE SCOPE OF WORK | | | INSIDE THE RESIDENCE. THE ROOM(S) MUST BE DESIGNATED SO | | | REVIEW FOR THE PROPER CODE ARTICLES MAY BE MADE. SUBMIT | | | PLANS WITH SUFFICIENT CLARITY FOR REVIEW. 106.1.3 FBC | | | AS AMENDED. | | | | | | 2} THE RECEPTACLE SPACING DOES NOT COMPLY WITH | | | 210.52(A)(1 & 2), IN THE SUNROOM. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.3.4.3.FBC.. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-08 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-08 |
Time |
16:30 |
Sent To |
E |
|
| Notes |
| 2008-01-08 16:33:19 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-19 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-19 |
Time |
15:47 |
Sent To |
E |
|
| Notes |
| 2007-11-19 15:48:32 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-18 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-18 |
Time |
16:13 |
Sent To |
E |
|
| Notes |
| 2007-09-18 16:13:51 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-06-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-11 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-11 |
Time |
09:15 |
Sent To |
B |
|
| Notes |
| 2007-06-11 09:16:09 | TO "MISC" BOX#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-13 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-08 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2007-06-08 13:16:42 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-06-08 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-06-08 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-06-08 |
Time |
16:38 |
Sent To |
I |
|
| Notes |
| 2007-06-08 16:39:58 | PROVISO:SCREEN ENCLOSURE TO BE A MINIMUM OF 3' AWAY | | | FROM SIDE PROPERTY LINE. |
|
|