Plan Review Details - Permit 07060213
Plan Review Stops For Permit 07060213
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-12 Cont ID  
Sent By jgomez Date 2007-06-12 Time 16:44 Rev Time 0.00
Received By jgomez Date 2007-06-12 Time 16:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By jgomez Date 2007-06-08 Time 16:45 Rev Time 0.00
Received By jgomez Date 2007-06-08 Time 16:45 Sent To PC
Notes
2007-06-08 16:54:26BUILDING REVIEW CHECKLIST:
 1- NOA #04-0506.03 SUBMITTED FOR FLAT ROOF ASSEMBLY
 EXPIRED ON 05/23/07. NEED TO PROVIDE CURRENT NOA.
  
 2-SELECTED ASSEMBLY ON PAGE 16 OF NOA SUBMITTED SHOWS
 2 DIFFERENT BASE SHEET FASTENING OPTIONS. PLEASE MARK
 WHICH OPTION IS GOING TO BE USED.
  
 3- SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION
 #7.PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 AND TABLE 1609.6.2.1(2) OF FBC 2004.
  
 ***NOTE:
 SEE ATTACHED CITY POLICY FOR ROOFING PERMITS AND
 INFORMATION REQUIRED FOR PLAN REVIEW.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712