| 2007-06-26 19:41:11 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | 1)FBC 1609.1WIND PRESSURES.BASED ON THE RWDI WIND |
| | TUNNEL TEST REPORT, SHEET S-6.00 OF THE STRUCTURAL |
| | PLANS FOR THE BUILDING (UNDER PERMIT # 05091425) SHOWS |
| | NEGATIVE WINDPRESSURES RANGING FROM -70 PSF TO -150 |
| | PSF.THESE DESIGN PRESSURE ARE FAR HIGHER THAN THE |
| | PRESSURES ASSUMED IN THE SUBMITTED ATLANTIC & CARIBBEAN |
| | ROOFING CONSULTING, LLC REPORTS 06-1274 L REV. AND |
| | 06-1274 H REV. (BOTH DATED 6/5/07) FOR THE |
| | DESIGN/SELECTION OF THE TILE AND ATTACHMENT FOR THE |
| | LOWER AND HIGHER ROOF.SUBMIT CALCULATIONS THAT MEET |
| | THE DESIGN PRESSURES ON STRUCTURAL PLAN SHEET S-6.00. |
| | IT IS NOTED THAT THE ATLANTIC & CARIBBEAN ROOFING |
| | CONSULTING, LLC REPORTS 06-1274 L AND 06-1274 H (BOTH |
| | DATED 8/15/06, PRIOR TO REVISION) DID MEET THE REQUIRED |
| | WIND PRESSURES, AND WERE CONSEQUENTLY REVIEWED AND |
| | STAMPED ON 9/9/06 UNDER PERMIT # 05091425. |
| | |
| | 2) FBC* 106.3.3ALL PRODUCT APPROVALS AND CALCULATIONS |
| | SHALL BE REVIEWED BY THE DESIGNER OF RECORD AND STAMPED |
| | WITH HIS/HER SHOP DRAWING REVIEW STAMP PRIOR TO |
| | SUBMITTAL FOR BUILDING OFFICIAL REVIEW. THERE ARE NO |
| | SHOP DRAWING REVIEW STAMPS FROM THE DESIGNER OF RECORD |
| | ON ANY OF THE SUBMITTED DOCUMENTS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: |
| | (561) 805 6652ROBERT BROWN |
| | E-MAIL: [email protected] |