| | PROJECT: 777 SOUTH FLAGLER, WEST TOWER, SUITE #1701 |
| | PLAN REVIEW: 2004 FLORIDABUILDING AND EXISTING |
| | BUILDING CODE WITH 2006 REVISIONS |
| | 1ST REVIEW |
| | STATUS: DENIED |
| | |
| | |
| | PLAN REVIEW COMMENTS: |
| | |
| | 1) PRIOR TO RE-SUBMITTING THE REVIEWED PLANS, PLEASE |
| | MAKE CERTAIN TO REVIEW AND ADDRESS EACH COMMENT AS |
| | NOTED BELOW AND MAKE ALL CORRECTIONS WHERE APPLICABLE. |
| | FAILURE TO DO SO WILL IMPEDE THE EXPEDITING OF THE |
| | PERMIT ISSUANCE. |
| | |
| | 2) 105.8 NOTICE OF COMMENCEMENT. |
| | |
| | AS PER SECTION 713.135, FLORIDA STATUTES, WHEN ANY |
| | PERSON APPLIES FOR A BUILDING PERMIT, THE AUTHORITY |
| | ISSUING SUCH PERMIT SHALL PRINT ON THE FACE OF EACH |
| | PERMIT CARD IN NO LESS THAN 18-POINT, CAPITALIZED, |
| | BOLDFACED TYPE:"WARNING TO OWNER: YOUR FAILURE TO |
| | RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR |
| | PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU |
| | INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR |
| | AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF |
| | COMMENCEMENT." |
| | |
| | 3)301.5 . A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION |
| | 303,304 & 305 OF THIS CODE. |
| | |
| | 4) AS PER THE FBC 106.3.5, PLEASE PROVIDE THE FOLLOWING |
| | DATA: |
| | |
| | A) BUILDING CONSTRUCTION TYPE |
| | B) OCCUPANCY LOAD |
| | C) OCCUPANCY GROUP |
| | D) SPRINKLERED OR NON-SPRINKLERED. |
| | |
| | 5) INDICATE EXIT SIGNS AS PER FBC 1006.3 ON SHEETS |
| | A-LS1 AND A-2, SAFETY AND REFLECTED CEILING PLAN |
| | RESPECTIVELY: |
| | |
| | 1006.3 EXIT SIGNS. |
| | |
| | 1006.3.1 |
| | EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY |
| | VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT |
| | SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT |
| | SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS |
| | SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY |
| | LIGHTING. |
| | EXCEPTION: MAIN EXTERIOR EXIT DOORS THAT OBVIOUSLY AND |
| | CLEARLY ARE IDENTIFIABLE AS EXITS. |
| | |
| | 6) PLEASE INDICATE TRAVEL DISTANCESAND THE OCCUPANCY |
| | LOAD ON THE LIFE SAFETY PLAN AS PER THE WEST PALM BEACH |
| | ADMINISTRATIVE CODE, SECTION 106.3.5.1.1(7). |
| | |
| | 6A)605.4.1TWO EGRESS DOORWAYS REQUIRED. |
| | |
| | WORK AREAS SHALL BE PROVIDED WITH TWO EGRESS DOORWAYS |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS |
| | 605.4.1.1 AND 605.4.1.2. |
| | 605.4.1.1 |
| | OCCUPANT LOAD AND TRAVEL DISTANCE. |
| | IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN |
| | OCCUPANT LOAD GREATER THAN 50 OR IN WHICH THE TRAVEL |
| | DISTANCE TO AN EXIT EXCEEDS 75 FEET (22 860 MM) SHALL |
| | HAVE A MINIMUM OF TWO EGRESS DOORWAYS. |
| | EXCEPTION: STORAGE ROOMS IN GROUP S1 AND S2 OCCUPANCIES |
| | HAVING A MAXIMUM OCCUPANT LOAD OF 10. |
| | |
| | |
| | 7) PLEASE PROVIDE PRODUCT SPECIFICATIONS FOR THE |
| | FOLLOWING: |
| | |
| | |
| | A) NEW CARPET AS INDICATED ON SHEET A-ID1. |
| | B) WALL COVERING AS INDICATED BY MARK WC-2 ON SHEET |
| | A-ID1. |
| | C) NEW ENGINEERED WOOD FLOORING, MARK WF-1 ON SHEET |
| | A-ID1. |
| | |
| | PLEASE NOTE THAT ALL NEWLY INSTALLED INTERIOR |
| | FINISHES SHALL COMPLY WITH THE FLORIDA BUILDING CODE, |
| | SECTION 803.5: |
| | |
| | 803.5 INTERIOR FINISH REQUIREMENTS BASED ON |
| | GROUP. |
| | INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME |
| | SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE |
| | 803.5 FOR THE GROUP AND LOCATION DESIGNATED. INTERIOR |
| | WALL AND CEILING FINISH MATERIALS, OTHER THAN TEXTILES, |
| | TESTED IN ACCORDANCE WITH NFPA 286 AND MEETING THE |
| | ACCEPTANCE CRITERIA OF SECTION 803.2.1, SHALL BE |
| | PERMITTED TO BE USED WHERE A CLASS A CLASSIFICATION IN |
| | ACCORDANCE WITH ASTM E 84 IS REQUIRED. |
| | |
| | 8) PLEASE PROVIDE EXISTING/NEW DOOR SCHEDULE. |
| | |
| | 9) PLEASE INDICATE THE EXISTING RATED WALL PARTITIONS |
| | AND FIRE RESISTIVITY ON THE OVERALL FLOOR PLAN, SHEET |
| | A-1. |
| | |
| | 10) RAISED FLOORING SHALL CONFORM TO THE FOLLOWING |
| | REQUIREMENTS OF FBC 717.2.7 |
| | |
| | 717.2.7 CONCEALED SLEEPER SPACES. |
| | |
| | WHERE WOOD SLEEPERS ARE USED FOR LAYING WOOD FLOORING |
| | ON MASONRY OR CONCRETE FIRE-RESISTANCE-RATED FLOORS, |
| | THE SPACE BETWEEN THE FLOOR SLAB AND THE UNDERSIDE OF |
| | THE WOOD FLOORING SHALL BE FILLED WITH AN APPROVED |
| | MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND |
| | PRODUCTS OF COMBUSTION OR FIREBLOCKED IN SUCH A MANNER |
| | THAT THERE WILL BE NO OPEN SPACES UNDER THE FLOORING |
| | THAT WILL EXCEED 100 SQUARE FEET (9.3 M2) IN AREA AND |
| | SUCH SPACE SHALL BE FILLED SOLIDLY UNDER PERMANENT |
| | PARTITIONS SO THAT THERE IS NO COMMUNICATION UNDER THE |
| | FLOORING BETWEEN ADJOINING ROOMS. |
| | EXCEPTIONS: |
| | |
| | 1.FIREBLOCKING IS NOT REQUIRED FOR SLAB-ON-GRADE FLOORS |
| | IN GYMNASIUMS. |
| | 2.FIREBLOCKING IS REQUIRED ONLY AT THE JUNCTURE OF EACH |
| | ALTERNATE LANE AND AT THE ENDS OF EACH LANE IN A |
| | BOWLING FACILITY. |
| | |
| | 11) ALL WOOD BUCKS AND BLOCKING TO BE FIRE RETARDANT |
| | TREATED LUMBER AS PER THE FOLLOWING: |
| | |
| | 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I |
| | OR II CONSTRUCTION. |
| | COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES |
| | OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS: |
| | 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION |
| | 603. |
| | 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF |
| | THE FLORIDA BUILDING CODE, MECHANICAL. |
| | 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE |
| | PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED |
| | IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE. |
| | COMBUSTIBLE PIPING SHALL BEPERMITTED WITHIN |
| | CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE |
| | WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE |
| | FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | |
| | 12) PROVIDE DETAILS FOR THE INSTALLATION OF THE NEW |
| | CLORESTORY WINDOWS: |
| | |
| | A) GLAZING SPECIFICATIONS. |
| | B) WALL FRAMING/ATTACHMENT DETAILS. |
| | |
| | 13) PROVIDE NEW METAL WALL AND CEILING FRAMING DETAILS |
| | AS REFLECTED ON SHEET A-3 DETAIL 06 AND SECTION 05/A6. |
| | |
| | 14) PLEASE PROVIDEAN OVERALL DEMOLITION FLOOR PLAN, |
| | SHEET A-D1 FOR CONSTRUCTION CLARIFICATION AS PER THE |
| | FOLLOWING: |
| | |
| | 106.1 SUBMITTAL DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA SHALL |
| | BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION |
| | FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A DESIGN PROFESSIONAL WHERE REQUIRED BY THE |
| | STATUTES. WHERE SPECIAL CONDITIONS EXIST, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL |
| | CONSTRUCTION DOCUMENTS TO BE PREPARED BY A DESIGN |
| | PROFESSIONAL. |
| | |
| | |