Plan Review Details - Permit 07060192
Plan Review Stops For Permit 07060192
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 10:55 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 10:50 Sent To  
Notes
2007-06-11 10:55:04*****APPROVED*****
  
  
 PLAN SHEET STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By rregueir Date 2007-06-11 Time 11:09 Rev Time 0.00
Received By rregueir Date 2007-06-08 Time 13:17 Sent To PC
Notes
2007-06-08 13:17:35TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-06-11 Cont ID  
Sent By rregueir Date 2007-06-11 Time 08:46 Rev Time 0.00
Received By rregueir Date 2007-06-11 Time 08:40 Sent To FIRE
Notes
2007-06-11 08:46:02******************PROVISO*******************
  
 THE MANUAL ACTUATION DEVICE (REMOTE PULL STATION) SHALL
 BE LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE
 COOKING AREA, A MINIMUM OF 10 FEET AND A MAXIMUM OF 20
 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE MANUAL
 ACTUATION DEVICE SHALL BE LOCATED A MINIMUM OF 4 FEET
 AND A MAXIMUM OF 5 FEET ABOVE THE FLOOR. THE MANUAL
 ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40 POUNDS
 AND A MAXIMUM MOVEMENT OF 14 INCHES (356 MM) TO ACTUATE
 THE FIRE SUPPRESSION SYSTEM. FBC 904.11.1
  