Plan Review Details - Permit 07060186
Plan Review Stops For Permit 07060186
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-06 Cont ID  
Sent By shill Date 2007-08-06 Time 19:17 Rev Time 0.00
Received By shill Date 2007-08-06 Time 19:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By shill Date 2007-07-13 Time 07:57 Rev Time 0.00
Received By shill Date 2007-07-13 Time 07:57 Sent To  
Notes
2007-07-13 08:06:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)PLEASE REVISE GENERAL NOTE 11 AS CHOOSING ONE OF
 THE OPTIONS DOES NOT PROVIDE CODE COMPLIANCE WITH
 BARRIER REQUIREMENTS OF FBC R 4101.17.
  
 2.)SHOW THE DISTANCE FROM THE HOUSE TO THE POOL.
  
 3.)THE PLANS REFER TO FBC424.PLEASE REVISE TO
 INCLUDE THE CORRECT CODE REFERENCES IN FBC RESIDENTIAL,
 CHAPTER 41.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By btrobaug Date 2007-07-20 Time 10:01 Rev Time 0.00
Received By btrobaug Date 2007-07-20 Time 09:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 11:27 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 11:16 Sent To P
Notes
2007-06-18 11:27:05 
 DENIED/INCOMPLETE INFORMATION
  
 1} : PLEASE SUBMIT LOAD CALCULATIONS
 PER PER 220, 215.5, INCLUDING THE ADDED LOADS FOR THE
 HEAT PUMP AND POOL EQUIPMENT. INDICATE THE SIZE OF THE
 EXISTING SERVICE.
  
 2} THE HEAT PUMP THAT IS TO BE INSTALLED IS NOT SHOWN
 ON THE ELECTRICAL SCHEMATIC, PLEASE INCLUDE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-08-02 Cont ID  
Sent By mperson Date 2007-08-02 Time 09:17 Rev Time 0.00
Received By mperson Date 2007-08-02 Time 09:18 Sent To B
Notes
2007-08-02 09:19:26NOTE: POOL HEATER HAS BEEN REMOVED FROM THE
 RESUBMITTAL.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-07-03 Cont ID  
Sent By mperson Date 2007-07-03 Time 16:25 Rev Time 0.00
Received By mperson Date 2007-07-03 Time 16:25 Sent To B
Notes
2007-07-03 16:26:47NOTE: PROPOSED POOL HEATER IS ELECTRIC.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-06-06 Cont ID  
Sent By swurafti Date 2007-06-06 Time 11:17 Rev Time 0.00
Received By swurafti Date 2007-06-06 Time 11:17 Sent To  
Notes
2007-06-06 11:17:49HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 13:41 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 13:41 Sent To Z
Notes
2007-07-18 13:42:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 09:14 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 09:14 Sent To E
Notes
2007-06-11 09:15:04TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-16 Time   Rev Time 0.00
Received By adarroug Date 2007-06-08 Time 13:18 Sent To  
Notes
2007-06-08 13:19:06TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By mperson Date 2007-08-02 Time 09:17 Rev Time 0.33
Received By mperson Date 2007-08-02 Time 09:17 Sent To G
Notes
2007-08-02 09:26:45PLEASE NOTE RED LINE CORRECTION TO THE LEGEND
 CORRELATING THE "VALVES" WITH THE EQUIPMENT LAYOUT.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By mperson Date 2007-07-03 Time 16:13 Rev Time 0.33
Received By mperson Date 2007-07-03 Time 16:13 Sent To G
Notes
2007-07-03 16:24:54DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A NATIONALLY
 RECOGNIZED TESTING AGENCY (NRTL). (MANUFACTURE
 SHEETS REQUIRED WITH THE MAKE AND MODEL NUMBER, PLEASE
 SUBMIT)
  
 2. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED WITH THE MAKE AND MODEL NUMBER, PLEASE
 SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By choops Date 2007-07-19 Time 10:24 Rev Time 0.00
Received By choops Date 2007-07-19 Time 10:24 Sent To E
Notes
2007-07-19 10:25:27PROVISO:MUST BE ENCLOSED BY A FENCE CONFORMING WITH
 SECTION, 94-304(D)(2)(B)+(C) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By choops Date 2007-06-08 Time 16:53 Rev Time 0.00
Received By choops Date 2007-06-08 Time 16:53 Sent To I
Notes
2007-06-08 16:58:48***FAILED***
  
  
 1)PLEASE PROVIDE SETBACK DIMENSION FROM POOL
 EQUIPMENT TO THE SIDE PROPERTY LINE.
  
 2)ENCLOSURE FENCE MUST COMPLETELY ENCLOSE POOL AND
 MEET THE MINIMUM REQUIREMENTS SHOWN BELOW (PLEASE
 INDICATE SUCH ON THE SURVEYS).
  
 AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTIONS 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720