Plan Review Details - Permit 07060173
Plan Review Stops For Permit 07060173
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-10-01 Cont ID  
Sent By jwitmer Date 2008-10-01 Time 16:44 Rev Time 0.55
Received By jwitmer Date 2008-10-01 Time 16:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 11:11 Rev Time 0.77
Received By jwitmer Date 2008-08-12 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 16:27 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 16:27 Sent To  
Notes
2008-06-03 16:33:34BUILDING PLAN REVIEW
 PERMIT: 07060173
 ADD: 3200 N MILITARY TRAIL
 CONT: STATIC ELECTRIC
 TEL: (561)684-6100
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A-C)COMPLIED
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) NOTICE TO BE COMPLETED AT TIME OF CERTIFICATE OF
 COMPLETION. FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE A CERTIFICATE OF COMPLETION CAN BE
 ISSUED
  
 2) COMPLIED.
  
 3)2ND REQUEST,PLANS INDICATE A GALVANIZED PERFORATED
 STEEL DECKING, PLEASE PROVIDE INFORMATION INDICATING
 COMPLIANCE WITH 1009.5.1 EXCEPTION. 1009.5.1 STAIRWAY
 WALKING SURFACE.
 THE WALKING SURFACE OF TREADS AND LANDINGS OF A
 STAIRWAY SHALL NOT BE SLOPED STEEPER THAN ONE UNIT
 VERTICAL IN 48 UNITS HORIZONTAL (2-PERCENT SLOPE) IN
 ANY DIRECTION. STAIRWAY TREADS AND LANDINGS SHALL HAVE
 A SOLID SURFACE. FINISH FLOOR SURFACES SHALL BE
 SECURELY ATTACHED.
 EXCEPTION: IN GROUP F, H AND S OCCUPANCIES, OTHER THAN
 AREAS OF PARKING STRUCTURES ACCESSIBLE TO THE PUBLIC,
 OPENINGS IN TREADS AND LANDINGS SHALL NOT BE PROHIBITED
 PROVIDED A SPHERE WITH A DIAMETER OF 1 1 / 8 INCHES (29
 MM) CANNOT PASS THROUGH THE OPENING
  
 4) 2ND REQUEST.PLEASE PROVIDE ADDITIONAL INFORMATION
 REQUIRDING 1009.11 & 1012.3.
 1009.11 HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE. HANDRAILS SHALL BE ADEQUATE IN STRENGTH AND
 ATTACHMENT IN ACCORDANCE WITH SECTION 1607.7 .
 HANDRAILS FOR RAMPS, WHERE REQUIRED BY SECTION 1010.8 ,
 SHALL COMPLY WITH THIS SECTION.
 1012.3 OPENING LIMITATIONS.
  
 OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL PATTERNS
 SUCH THAT A 4-INCH-DIAMETER (102 MM) SPHERE CANNOT PASS
 THROUGH ANY OPENING UP TO A HEIGHT OF 34 INCHES (864
 MM). FROM A HEIGHT OF 34 INCHES (864 MM) TO 42 INCHES
 (1067 MM) ABOVE THE ADJACENT WALKING SURFACES, A SPHERE
 8 INCHES (203 MM) IN DIAMETER SHALL NOT PASS.
 EXCEPTIONS:
 1.THE TRIANGULAR OPENINGS FORMED BY THE RISER,
 TREAD AND BOTTOM RAIL AT THE OPEN SIDE OF A STAIRWAY
 SHALL BE OF A MAXIMUM SIZE SUCH THAT A SPHERE OF 6
 INCHES (152 MM) IN DIAMETER CANNOT PASS THROUGH THE
 OPENING.
 2.AT ELEVATED WALKING SURFACES FOR ACCESS TO AND
 USE OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A SPHERE WITH A DIAMETER OF 21
 INCHES (533 MM) CANNOT PASS THROUGH ANY OPENING.
 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A DIAMETER OF 21 INCHES
 (533 MM) TO PASS THROUGH ANY OPENING.
 4.IN ASSEMBLY SEATING AREAS, GUARDS AT THE END OF
 AISLES WHERE THEY TERMINATE AT A FASCIA OF BOXES,
 BALCONIES AND GALLERIES SHALL HAVE BALUSTERS OR
 ORNAMENTAL PATTERNS SUCH THAT A 4-INCH-DIAMETER (102
 MM) SPHERE CANNOT PASS THROUGH ANY OPENING UP TO A
 HEIGHT OF 26 INCHES (660 MM). FROM A HEIGHT OF 26
 INCHES (660 MM) TO 42 INCHES (1067 MM) ABOVE THE
 ADJACENT WALKING SURFACES, A SPHERE 8 INCHES (203 MM)
 IN DIAMETER SHALL NOT PASS.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-08 Cont ID  
Sent By jwitmer Date 2008-04-08 Time 11:35 Rev Time 0.77
Received By jwitmer Date 2008-04-08 Time 11:35 Sent To PC
Notes
2008-04-08 12:17:50BUILDING PLAN REVIEW
 PERMIT: 07060173
 ADD: 3200 N MILITARY TRAIL
 CONT: STATIC ELECTRIC
 TEL: (561)684-6100
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE A CERTIFICATE OF COMPLETION CAN BE
 ISSUED
  
 2) ONE SET OF PLANS IS A COPY NOT SIGNED NOR SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) PLANS INDICATE A GALVANIZED PERFORATED STEEL
 DECKING, PLEASE PROVIDE INFORMATION INDICATING
 COMPLIANCE WITH 1009.5.1 EXCEPTION.
  
 4) PLEASE PROVIDE ADDITIONAL INFORMATION REQUIRDING
 1009.11 & 1012.3.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 15:11 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2008-04-08 12:07:22BUILDING PLAN REVIEW
 PERMIT: 07060173
 ADD: 3200 N MILITARY TRAIL
 CONT: STATIC ELECTRIC COMPANY
 TEL: (561)242-8869
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E)PLANS PULLED BEFORE FIRST BUILDING REVIEW WAS
 COMPLETE.
  
 2) ONE SET OF PLANS IS A COPY NOT SIGNED AND SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) NOTE: FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE A CERTIFICATE OF COMPLETION WILL BE
 ISSUED.
  
 4) PLANS INDICATE A PERFORATED GALVANIZED DECKING,
 PLEASE PROVIDE INFORMATION INDICATING COMPLIANCE WITH
 1009.5.1 SEE EXCEPTIONS.
  
 5) PLANS FAIL TO INDICATE A HANDRAIL/ GUARDRAIL SYSTEM,
 1012.3 & 1009.11.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2007-07-03 15:12:22PLANS PULLED FROM REVIEW BY CONTRACTOR BEFORE REVIEW
 COULD BE DONE.WHEN PLANS COME BACK, IT WILL COUNT AS
 1ST RESUB. DV PALMER.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-10-01 Cont ID  
Sent By jleahy Date 2008-10-01 Time 09:00 Rev Time 2.30
Received By jleahy Date 2008-10-01 Time 08:47 Sent To  
Notes
2008-10-01 08:59:46 
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-08-12 Cont ID  
Sent By dpalmer Date 2008-08-12 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2008-08-12 Time 12:53 Sent To  
Notes
2008-08-12 12:53:53 
 ** DENIED PLANS.**
  
 ** NEW PLANS ONCE AGAIN WHICH ARE COMPLETELY REVISED
 FROM PREVIOUS PLANS.
 ** NEW DESIGNER OF RECORD.
  
 1) NOTE: THE GENERATOR IS NOW BEING SHOWN AS A
 SEPARATELY DERIVED SYSTEM HOWEVER THE RISER INDICATES A
 3-POLE TRANSFER SWITCH.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE.
 250.20, 250.30, ETC.
  
 2) NOTE: AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.110,250.24,250.122 ETC.
 THE RISER FOR FEEDERS FROM ATS TO EXISTING MAIN AT
 BUILDING IS MISSING AN EQUIPMENT GROUNDING CONDUCTOR.
 250.32, 250.122.
 MUST ALSO PLACE NOTE ON PLANS TO SEPARATE ALL NEUTRALS
 AND EQUIPMENT GROUNDING AT EXISTING MAIN ONE OF ONE.
  
  
 ** MUST INSTALL EQUIPMENT GROUNDING. THE ONLY WAY
 EQUIPMENT GROUNDING IS NOT REQUIRED IS *IF* THERE ARE
 NO OTHER METAL CURRENT CARRYING PARTS BETWEEN SOURCES
 OR EQUIPMENT. BASED ON THE BRANCH CIRCUIT FROM THE
 EXISTING SERVICE TO GENERATOR AND OTHER POSSIBLE
 CURRENT CARRYING PARTS THIS IS REQUIRED.
  
 3) NOTE: BASED ON COMMENT #1 ABOVE PLEASE SUBMIT
 REVISED SPECS/CUT SHEETS FOR TRANSFER SWITCH. 110.3,
 90.7
  
 4) NOTE: THIS RISER IS NOW SHOWING MAINS AND
 DISCONNECTING MEANS WHICH WERE NEVER PREVIOUSLY SHOWN.
 ALL MAINS AND MEANS OF DISCONNECT SHALL MEET CODE FOR
 GROUPING AND ALSO FOR SIGNAGE REQUIRED AND LABELING ALL
 MEANS OF DISCONNECT FOR SHUTTING DOWN POWER UNDER BOTH
 CONDITIONS.
 230.2E, 700.8, 701.9, 702.8
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-30 Cont ID  
Sent By dpalmer Date 2008-05-30 Time 08:09 Rev Time 0.00
Received By dpalmer Date 2008-05-30 Time 08:09 Sent To  
Notes
2008-05-30 08:09:57** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SEVERAL NEW COMMENTS ARE NOW BASED ON
 COMPLETELY REVISED ELECTRICAL RISER DIAGRAM WHICH NOW
 CONTAINS SEVERAL NEW CHANGES WHICH WERE NOT PART OF
 PREVIOUSLY SUBMITTED PLANS.
  
 1) NOTE: PLEASE SEE PLANS NOW SHOW A NEW 500KVA
 TRANSFORMER WHICH WAS NOT PART OF PREVIOUS PLANS.
 PLEASE SEE 250.20,250.30 AS THIS IS NOW A SEPARATELY
 DERIVED SYSTEM.
  
 2) NOTE: PLEASE SEE THE TRANSFORMER AS NOTED ABOVE IS
 ALSO SHOWING NEUTRAL CONDUCTORS TO THE TRANSFORMER. HOW
 IS THIS POSSIBLE WHEN THE TRANSFORMER IS SEPARATELY
 DERIVED?
 PLEASE COMPLETE PLANS, CONDUCTORS, RISER, GROUNDING
 ELECTRODE SYSTEM ETC PER 2005 NEC.
 THERE ARE TOO MANY CODE SECTIONS TO NOTE.
 FBC 106.3.5.1.2
 NEC 225, 230, 240, 250, ETC.
  
 3) NOTE: PLEASE SEE RISER WHICH SHOWS TWO BLACK LINES
 FROM THE GENERATOR. ONE IS SHOWN TO TRANSFER SWITCH AND
 THE OTHER TO THE TRANSFORMER. WHAT IS THIS SECOND
 LINE?
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE RISER IS STILL SHOWING EQUIPMENT
 GROUNDING CONDUCTORS BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 250.6, 250.24
  
 ** THERE ARE SEVERAL ITEMS WHICH CAN NOT BE DETERMINED
 AT THIS TIME. HOWEVER PLEASE SEE THE COMMENTS ABOVE AND
 PLEASE TAKE A LOOK AT THE PLANS/RISER SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 17:51 Sent To  
Notes
2008-03-08 17:51:53** DENIED 2NDREVIEW**
  
 ** PLEASE SEE SOME OF THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING ALONG
 WITH SOME NEW COMMENTS BASED ON NEW PLANS SUBMITTED FOR
 REVIEW.
  
  
 1) NOTE: PLEASE SEE THE PLANS NOW SUBMITTED ARE
 PHOTO-COPIES OF SIGNED, DATED AND SEALED PLANS. PLEASE
 SEE FAC 61G15-23.002 AND FS 471.025 WHICH REQUIRES ALL
 DOCUMENTS TO CONTAIN ORIGINAL SIGNATURES, DATES AND
 RAISED SEALS. THIS IS REQUIRED WHETHER OR NOT COMMENT
 IS MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE THERE ARE STILL NO LOAD
 CALCULATIONS SUBMITTED AS PREVIOUSLY REQUESTED. PLEASE
 SEE NFPA-70 2005 220.87 AND SUBMIT. THE LOADS IN AMPS
 SHOWN ON RISER CAN NOT BE VERIFIED, WHAT IS THE
 VOLTAGE?
 702.5
  
 3) NOTE: PLEASE KNOW A LICENSED CONTRACTOR OTHER THAN
 THE ELECTRICAL CONTRACTOR AS SIGNED ON WILL BE REQUIRED
 FOR STRUCTURAL WORK. EC MAY NOT PERFORM WORK AS SHOWN.
 PLEASE ALSO SEE THE VALUE FOR COMPLETE SCOPE OF WORK
 INCLUDING STRUCTURAL HAS NOT BEEN ADJUSTED.
 PLEASE SEE FBC 108.3.
  
 4) NOTE: PLEASE SEE RISER AS THIS STILL SHOWS AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED. AS THE CODE
 REQUIRES BONDING AT THE FIRST MEANS OF DISCONNECT ANY
 EQUIPMENT GROUNDING CONDUCTORS INSTALLED BEFORE THE
 FIRST MEANS OF DISCONNECT WOULD PARALLEL THE NEUTRAL
 AND CREATE OBJECTIONABLE CURRENTS.
 PLEASE SEE THE RISER WHICH SHOWS THIS SAME 1/0 AS
 EXISTING WHICH IS NOT POSSIBLE. AS THE INSIDE MSB IS
 NOW AFTER THE FIRST MEANS OF DISCONNECT ONLY NOW WOULD
 THE EQUIPMENT GROUNDING CONDUCTOR BE INSTALLED AND
 NEEDS TO BE SHOWN AS NEW.
 PLEASE ALSO PLACE NOTE ON PLANS AS ALL NEUTRALS AND
 EQUIPMENT GROUNDS WILL BE REQUIRED TO BE SEPARATED IN
 EIXSITNG EQUIPMENT.
 250.24, 250.6
  
 5) NOTE: PLEASE SEE THE RISER DOES NOT SHOW ANY BREAKER
 AT THE GENERATOR AND THE SPECS SUBMITTED DOES NOT
 CLEARLY SHOW A BREAKER OR OVER CURRENT PROTECTION?
 PLEASE KNOW AS NOTED ABOVE FOR LOAD CALCULATIONS, AS
 THE VOLTAGE FOR SYSTEM COULD NOT LOCATED, WE CAN NOT
 DETERMINE SOME ITEMS FOR CODE COMPLIANCE AT THIS TIME.
 240.4, 310.16, 445.13.
  
 6) NOTE: PLEASE SEE THE GENERATOR SPECS INDICATE
 CHARGING FOR BATTERY ETC HOWEVER THE PLANS DO NOT SHOW
 ANY ELECTRICAL FROM SERVICE TO THESE ITEMS.
 BLOCK HEATER? BATTERY CHARGER? ETC
 408.4, 240.4, 310.16, ETC
 PLEASE PROVIDE ADDITIONAL INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 18:00 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 17:40 Sent To  
Notes
2007-06-23 17:59:57*** UNSAT ***
  
  
 1) NOTE:PLEASE SEE THE SUBMITTED PLANS MAY NOT BE
 DONE BY AN ELECTRICAL CONTRACTOR. THIS SCOPE OF WORK
 INCLUDING ELECTRICAL, SLAB WORK ETC SHALL BE DONE BY A
 PROFESSIONAL ENGINEER AS REQUIRED UNDER FS 471.003 THE
 DOCUMENTS SUBMITTED DOE NOT CORRELATE FOR ELECTRICAL.
 NO REVIEW WAS DONE AS ENGINEERED PLANS ARE NEEDED AND
 THE SHEETS SUBMITTED DO NOT CORRELATE. PLEASE SEE
 BUILDING REVIEW COMMENTS AS ENGINEERING WILL ALSO BE
 REQUIRED FOR SLAB AND ATTACHMENT. THE 6INCH SLAB AS
 SHOWN DOES NOT PROVIDE THE INFORMATION NEEDED. PLEASE
 PROVIDE COMPLETED PLANS FOR ALL ELECTRICAL AND OTHER
 WORK FOR REVIEW.
 FBC 106.1, 106.3.5.1.2, 106.1.2
  
 2) NOTE: PLEASE KNOW THE FOLLOWING CODES WILL BE
 REQUIRED ON PLANS FOR DESIGN AND SCOPE OF WORK. 2004
 FBC W/2006 REVISIONS.
 2002 NFPA-110
 2005 NFPA-70
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR
 OTHER CODES WHICH MAY BE REQUIRED.
  
 3) NOTE: PLEASE SUBMIT TWO COMPLETE PACKAGES OF
 MANUFACTURE SPECS/CUT SHEETS FOR ALL EQUIPMENT
 INCLUDING THE FOLLOWING.
 THESE PACKAGES SHOULD BE BOUND TOGETHER IN SOME FASHION
 WITH TABS OF SOME SORT TO LABEL EACH IN PACKAGE.
 GENERATOR, MAIN SWITCHGEAR, ATS, GENERATOR ENCLOSURE,
 FUEL TANK(S) ETC.
 NEC 110.3, 90.7.
 FBC 106.1.2
 * SOME OF THESE WERE SUBMITTED, HOWEVER NOT ALL WHICH
 IS NEEDED.
  
 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR , MATERIALS, EQUIPMENT,
 GENERATOR, ATS, MAIN(S), DESIGN COSTS ETC EVEN IF ANY
 OF THIS IS OWNER SUPPLIED.
 FBC 108.3
  
 5) NOTE: PLEASE SEE 250.6, 250.24 AS NO * EQUIPMENT
 GROUNDING CONDUCTOR * IS INSTALLED BEFORE THE FIRST
 MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE BE SURE COMPLETE LOAD CALCULATIONS ARE
 SUBMITTED FOR EXISTING SERVICE.
 PLEASE CLARIFY HOW THE 2000AMP SERVICE IS NOW BEING
 DOWN-SIZED TO 1400AMPS??
  
 ** ALL COMMENTS ABOVE SHOULD BE FORWARDED TO THE
 ENGINEER WHO WILL BE TAKING OVER PROJECT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-10-03 Cont ID  
Sent By mwennerg Date 2008-10-03 Time 09:54 Rev Time 0.00
Received By mwennerg Date 2008-10-03 Time 09:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-10-01 Cont ID  
Sent By mwennerg Date 2008-10-01 Time 13:40 Rev Time 0.00
Received By mwennerg Date 2008-10-01 Time 13:40 Sent To  
Notes
2008-10-01 13:41:15*DENIED***
  
 1) MOST COMMENTS HAVE BEEN ADDRESSED HOWEVER IT IS
 STILL UNCLEAR WHAT EQUIPMENT WILL BE TIED INTO THE
 GENERATOR. PLEASE BE SPECIFIC REGARDING LIFE SAFETY
 EQUIPMENT. PLANS WILL BE STAMPED WHEN RETURNED FOR
 ELECTRICAL COMMENTS ONLY IF THIS ISSUE HAS BEEN
 ADDRESSED. IF COMMENT IS NOT ADDRESSED, REVIEW WILL BE
 RETURNED TO FAILED STATUS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 8-4-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-08-20 Cont ID  
Sent By mwennerg Date 2008-08-20 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2008-08-20 Time 14:20 Sent To  
Notes
2008-08-20 14:20:41***DENIED***
  
 1) MOST COMMENTS HAVE BEEN ADDRESSED HOWEVER IT IS
 STILL UNCLEAR WHAT EQUIPMENT WILL BE TIED INTO THE
 GENERATOR. PLEASE BE SPECIFIC REGARDING LIFE SAFETY
 EQUIPMENT. PLANS WILL BE STAMPED WHEN RETURNED FOR
 ELECTRICAL COMMENTS ONLY IF THIS ISSUE HAS BEEN
 ADDRESSED. IF COMMENT IS NOT ADDRESSED, REVIEW WILL BE
 RETURNED TO FAILED STATUS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 8-4-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-02 Cont ID  
Sent By mwennerg Date 2008-06-02 Time 13:16 Rev Time 0.00
Received By mwennerg Date 2008-06-02 Time 13:16 Sent To  
Notes
2008-06-02 13:19:51***DENIED***
  
 1) MOST COMMENTS HAVE BEEN ADDRESSED HOWEVER IT IS
 STILL UNCLEAR WHAT EQUIPMENT WILL BE TIED INTO THE
 GENERATOR. PLEASE BE SPECIFIC REGARDING LIFE SAFETY
 EQUIPMENT. PLANS WILL BE STAMPED WHEN RETURNED FOR
 ELECTRICAL COMMENTS ONLY IF THIS ISSUE HAS BEEN
 ADDRESSED. IF COMMENT IS NOT ADDRESSED, REVIEW WILL BE
 RETURNED TO FAILED STATUS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 8-4-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-07 Cont ID  
Sent By mawillia Date 2008-04-07 Time 17:10 Rev Time 0.00
Received By mawillia Date 2008-04-07 Time 16:54 Sent To  
Notes
2008-04-07 17:09:38*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.PLEASE PROVIDE FURTHER DETAILS REGARDING FUEL
 STORAGE TO INCLUDE AMOUNT, LOCATION, AND TANK
 SPECIFICATIONS.
  
 2.PLEASE SHOW LOCATION OF EXHAUST IN RELATION TO ANY
 BUILDING OPENINGS AND MEANS OF EGRESS.
  
 3.WHAT EQUIPMENT WILL BE POWERED BY THE GENERATOR?
  
 4.OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 15:12 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 15:12 Sent To  
Notes
2007-07-02 15:20:57***DENIED***
  
 1) PLEASE PROVIDE FURTHER DETAILS REGARDING FUEL
 STORAGE TO INCLUDE AMOUNT, LOCATION,TANK
 SPECIFICATIONS.
  
 2) PLEASE SHOW LOCATION OF EXHAUST IN RELATION TO ANY
 BUILDING OPENINGS AND MEANS OF EGRESS.
  
 3) WHAT EQUIPMENT WILL BE POWERED BY GENERATOR?
  
 4) WORK SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status P Date 2008-09-17 Cont ID  
Sent By tgordon Date 2008-09-17 Time 09:55 Rev Time 0.00
Received By tgordon Date 2008-09-17 Time 09:55 Sent To  
Notes
2008-09-17 09:56:53GENERATOR WITH 2,000 GAL. DIESEL FUEL TANK.

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2008-05-27 Cont ID  
Sent By tgordon Date 2008-05-27 Time 09:55 Rev Time 0.05
Received By tgordon Date 2008-05-27 Time 09:55 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 15:12 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2007-07-03 15:12:37PLANS PULLED FROM REVIEW BY CONTRACTOR BEFORE REVIEW
 COULD BE DONE.WHEN PLANS COME BACK, IT WILL COUNT AS
 1ST RESUB. DV PALMER.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 15:12 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2007-07-03 15:13:06DIESEL GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-16 Cont ID  
Sent By adarroug Date 2008-09-16 Time 11:59 Rev Time 0.00
Received By adarroug Date 2008-09-16 Time 11:59 Sent To  
Notes
2008-09-16 12:02:54TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 10:45 Sent To  
Notes
2008-07-29 10:49:07TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 10:42 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 10:42 Sent To  
Notes
2008-05-14 10:42:25TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-25 Cont ID  
Sent By adarroug Date 2008-02-25 Time 11:27 Rev Time 0.00
Received By adarroug Date 2008-02-25 Time 11:27 Sent To  
Notes
2008-02-25 11:27:40TO "COMM" BD#32--PLANS PULLED FROM 1ST REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-03 Time   Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 11:51 Sent To  
Notes
2007-06-21 14:50:05TO "COMM" BD#29
2007-06-06 11:52:05WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-09-17 Cont ID  
Sent By tgordon Date 2008-09-17 Time 09:54 Rev Time 0.45
Received By tgordon Date 2008-09-17 Time 09:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-07-31 Cont ID  
Sent By tgordon Date 2008-07-31 Time 16:30 Rev Time 0.30
Received By tgordon Date 2008-07-31 Time 16:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By tgordon Date 2008-05-27 Time 09:52 Rev Time 0.30
Received By tgordon Date 2008-05-27 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-10 Cont ID  
Sent By tgordon Date 2008-02-29 Time 10:42 Rev Time 0.25
Received By tgordon Date 2008-02-29 Time 10:42 Sent To  
Notes
2008-03-10 10:03:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ONLY ONE SET OF PLANS HAVE BEEN SIGNED AND SEALED BY
 THE ENGINEER, PLEASE CORRECT PER 2004 FAC
 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 15:13 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2007-07-03 15:13:19PLANS PULLED FROM REVIEW BY CONTRACTOR BEFORE REVIEW
 COULD BE DONE.WHEN PLANS COME BACK, IT WILL COUNT AS
 1ST RESUB. DV PALMER.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 15:13 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2007-07-03 15:13:46DIESEL GENERATOR

Review Stop Z ZONING
Rev No 6 Status P Date 2008-10-03 Cont ID  
Sent By eschneid Date 2008-10-03 Time 08:43 Rev Time 0.00
Received By eschneid Date 2008-10-03 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2008-09-24 Cont ID  
Sent By eschneid Date 2008-09-24 Time 10:21 Rev Time 0.00
Received By eschneid Date 2008-09-24 Time 10:21 Sent To  
Notes
2008-09-24 10:30:18FAILED
  
 THIS PERMIT FAILS BASED ON THE PROVISO STATED ON THE
 ZONING REVIEW OF 8/6/08 NOT HAVING BEEN ADDRESSED ON
 THE RESUBMITTAL.
  
 UPON RESUBMITTAL OF THIS PERMIT, THE PLANS SHALL SHOW:
  
 A HEDGE, PLANTED 2 FOOT ON CENTER, IS REQUIRED TO BE
 PLANTED ON THE NORTH, EAST AND WEST SIDES OF THE ATS
 PAD/EQUIPMENT. NOTE THAT THE TYPE OF PLANT MATERIAL
 USED FOR THE HEDGE SHALL BE STATED.
  
 NOTE: THE LANDSCAPE AND WALL APPROVED UNDER PERMIT
 NUMBER 07110451 AND THE LANDSCAPE THAT WILL BE ADDED TO
 THIS PERMIT SHALL BE INSTALLED PRIOR TO THE CERTIFICATE
 OF COMPLETION FOR THE GENERATOR AND RELATED EQUIPMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-08-06 Cont ID  
Sent By eschneid Date 2008-08-06 Time 17:22 Rev Time 0.00
Received By eschneid Date 2008-08-06 Time 17:22 Sent To  
Notes
2008-08-06 17:28:58PASSED W/PROVISOS
  
 PROVISO - 1) THE CLIMBING VINES SHALL BE FICUS REPENS
 AND SHALL BE PLANTED 18 INCHES ON CENTER.
  
 PROVISO - 2) A HEDGE, PLANTED 2 FOOT ON CENTER, IS
 REQUIRED TO BE PLANTED ON THE NORTH, EAST AND WEST
 SIDES OF THE ATS PAD/EQUIPMENT.
  
 NOTE: THE LANDSCAPE AND WALL SHALL BE INSTALLED PRIOR
 TO THE CERTIFICATE OF COMPLETION FOR THE GENERATOR.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-21 Cont ID  
Sent By eschneid Date 2008-05-21 Time 14:09 Rev Time 0.00
Received By eschneid Date 2008-05-21 Time 14:08 Sent To  
Notes
2008-05-21 14:10:15PASSED
  
 NOTE:THE WALL AND LANDSCAPE APPROVED UNDER PERMIT #
 07110451 IS REQUIRED TO BE INSTALLED, PRIOR TO THE
 CERTIFICATE OF COMPLETION FOR THE GENERATOR.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-03-03 Cont ID  
Sent By eschneid Date 2008-03-03 Time 15:06 Rev Time 0.00
Received By eschneid Date 2008-03-03 Time 15:06 Sent To  
Notes
2008-03-03 15:15:39FAILED
  
 1) REPEAT COMMENT - A SURVEY OR SITE PLAN SHOWING THE
 PROPOSED LOCATION OF THE GENERATOR, INCLUDING
 DIMENSIONS TO ALL STRUCTURES AND PROPERTY LINES IS
 REQUIRED.THIS SHALL BE TO SCALE AND SHOW THE PROPOSED
 WALL AND THE LANDSCAPE STRIP ON THE NORTH SIDE OF THE
 GENERATOR WALL.
  
 2) REPEAT COMMENT - THE GENERATOR IS REQUIRED TO BE
 SCREENED WITH A HEDGE ALONG THE ENCLOSURE WALL.THE
 DETAILS SHALL BE INCLUDED WITH THIS PERMIT.PERMIT #
 07110451 IS REQUIRED TO BE APPROVED AND THE WORK
 COMPLETED, PRIOR TO THE CERTIFICATE OF COMPLETION FOR
 THE GENERATOR.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-10-01 Cont ID  
Sent By eschneid Date 2007-06-25 Time 16:35 Rev Time 0.00
Received By eschneid Date 2007-06-25 Time 16:35 Sent To  
Notes
2007-06-25 16:42:03FAILED
  
 1) A SURVEY SHOWING THE PROPOSED LOCATION OF THE
 GENERATOR, INCLUDING DIMENSIONS TO ALL STRUCTURES AND
 PROPERTY LINES IS REQUIRED.
  
 2) THE GENERATOR IS REQUIRED TO BE SCREENED WITH A WALL
 AND HEDGE.THESE DETAILS SHALL BE INCLUDED WITH THE
 PERMIT AND A SEPARATE PERMIT FOR THE WALL/LANDSCAPE IS
 REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL OF THIS
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.