Plan Review Details - Permit 07060154
Plan Review Stops For Permit 07060154
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-12-17 Cont ID  
Sent By shill Date 2007-12-17 Time 14:48 Rev Time 0.00
Received By shill Date 2007-12-17 Time 14:48 Sent To  
Notes
2007-12-17 14:48:32REVISION AND PENETRATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-30 Cont ID  
Sent By lmartine Date 2007-10-30 Time 08:40 Rev Time 0.00
Received By lmartine Date 2007-10-30 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-18 Cont ID  
Sent By shill Date 2007-09-18 Time 08:20 Rev Time 0.00
Received By shill Date 2007-09-18 Time 08:20 Sent To  
Notes
2007-09-18 08:37:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)DESIGNER OF RECORD FOR THE BUILDING, JEFFREY
 GASPAR, IS TO REVIEW THE DRAWINGS (SHOP DRAWING REVIEW
 STAMP).
  
 3RD REQUEST; NOT ADDRESSED.
  
 2.)SEE FBC TABLE 302.3.2.THE FIRE SEPARATION IS TO
 BE IN COMPLIANCE WITH FBC TABLE 302.3.2 EXCEPT FOR
 NONSEPARATED USE, FBC302.3.1.IF THIS CAN BE A
 NONSEPARATED USE, PLEASE SHOW CALCULAATIONS ON THE PLAN
 FBC302.3.1, FBC TABLE 503.
  
 SEE COMMENT 3.A NONSEPARATED USE WAS DECLARED BUT THE
 PLANS DO NOT SHOW COMPLIANCE WITH FBC TABLE 503.
  
 3.)SHOW HOW THE NEW OCCUPANCY COMPLIES WITH FBC TABLE
 503.
  
 3RD REVIEW - THE PLANS STATE THAT THIS IS A TYPE III B
 BUILDING, AND THAT THE FLORIDA BUILDING CODE 2004
 COMMENTARY STATES THAT A FBC 2001 TYPE V B IS NOW A
 TYPE III B.PLEASE NOTE THE FOLLOWING -
  
 A.PLEASE ADVISE AS TO WHERE THIS LANGUAGE IN THE
 COMMENTARY IS LOCATED AS I AM UNABLE TO FIND IT.ALSO
 PLEASE NOTE THE INCONSISTENCY; THE 2001 CODE CLASSIFIED
 BUILDINGS AS "PROTECTED" AND "UNPROTECTED", NOT "A" OR
 "B".
  
 B.THE COMMENTARY AND THE CODE BOTH STATE THAT A 2HOUR
 FIRE RESISTANCE RATING IS REQUIRED FOR TYPE III B; SEE
 PAGE 6-2 OF THE COMMENTARY AND FBC602.3,FBC TABLE
 601.ALSO SEE ATTACHED COMMENTARY WHICH I HAVE
 HIGHLIGHTED.
  
 C.PLANS STATE THAT THE EXTERIOR WALL IS 1 HOUR;
 THEREFORE, CANNOT BE A TYPE III B.IF THE PLANS ARE
 INCORRECT AND THE EXTERIOR BEARING WALLS ARE 2 HOUR,
 PLEASE REVISE PLAN AND PROVIDE A DETAIL SHOWING HOW THE
 EXISTING WALLS COMPLY WITH THE 2HOUR REQUIREMENT AS I
 BELIEVE THE BUILDING WAS PERMITTED WITH NO FIRE
 RESISTANCE REQUIRED FOR EXTERIOR WALLS.
  
 D.PLEASE SEE FBC 506.2 REGARDING FRONTAGE INCREASES;
 COULD THIS SECTION APPLY?CALCULATIONS WERE PROVIDED
 WHICH SHOW ALLOWABLE OPENINGS BUT DO NOT STATE DISTANCE
 TO PROPERTY LINE.BASED ON FBC TABLE 704.8, 45%
 INDICATES THAT EACH EXTERIOR WALL IS 20-25' FROM THE
 PROPERTY LINE; THEREFORE, IT APPEARS THAT A FRONTAGE
 INCREASE MAY POSSIBLY RESOLVE THE ISSUE.
  
 5.)REGARDING IMPACT FEES, PLEASE BE ADVISED THAT PALM
 BEACH COUNTY HAS DETERMINED THAT IMPACT FEES ARE NOT
 REQUIRED AT THIS TIME.HOWEVER, FUTURE TENANT
 BUILDOUTS MAY REQUIRE AN IMPACT FEE ASSESSMENT (PER
 WILLIE SWOPE AND GWEN, PALM BEACH COUNTY, 233-5025).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-17 Cont ID  
Sent By shill Date 2007-07-17 Time 14:42 Rev Time 0.00
Received By shill Date 2007-07-17 Time 10:50 Sent To  
Notes
2007-07-17 14:52:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)DESIGNER OF RECORD FOR THE BUILDING, JEFFREY
 GASPAR, IS TO REVIEW THE DRAWINGS (SHOP DRAWING REVIEW
 STAMP).
  
 2.)SEE FBC TABLE 302.3.2.THE FIRE SEPARATION IS TO
 BE IN COMPLIANCE WITH FBC TABLE 302.3.2 EXCEPT FOR
 NONSEPARATED USE, FBC302.3.1.IF THIS CAN BE A
 NONSEPARATED USE, PLEASE SHOW CALCULAATIONS ON THE PLAN
 FBC302.3.1, FBC TABLE 503.
  
 3.)SHOW HOW THE NEW OCCUPANCY COMPLIES WITH FBC TABLE
 503.
  
 5.)IMPACT FEES MAY BE DUE.PLEASE HAVE THE PLANS
 STAMPED AND PROVIDE A RECEIPT SHOWING THAT FEES HAVE
 BEEN PAID.233-5025 FOR MORE INFORMATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By shill Date 2007-06-29 Time 17:56 Rev Time 0.00
Received By shill Date 2007-06-29 Time 17:56 Sent To  
Notes
2007-06-29 18:01:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)DESIGNER OF RECORD FOR THE BUILDING, JEFFREY
 GASPAR, IS TO REVIEW THE DRAWINGS (SHOP DRAWING REVIEW
 STAMP).
  
 2.)DECLARE OCCUPANT LOAD FOR THIS SPACE, AS WELL AS
 OCCUPANCY CLASSIFICATION AND SUBCLASSIFICATION FBC 3. A
 LETTER WAS PROVIDED IN REGARDS TO STORAGE CONTENTS;
 ARCHITECT IS TO DECLARE AN OCCUPANCY CLASSIFICATION FOR
 THIS SPACE.AS YOU ARE ALTERING THE SPACE IT IS NOT
 NECESSARILY THE SAME OCCUPANCY AS WHEN THE ORIGINAL
 BUILDING WS PERMITTED.THE 1 HOUR WALL IS NOT
 REQUIRED (BUT CAN ALWAYS EXCEED CODE COMPLIANCE), BUT
 CODE COMPLIANCE FOR THE EXEMPTION MUST BE SHOWN ON THE
 PLAN.SEE FBC302, FBC302.3.1.
  
 3.)DECLARE BUILDING TYPE UNDER FBC2004, INCLUDING A
 OR B.
  
 4.)THE SQUARE FOOT AREA ON THE ENERGY CALCS DO NOT
 MATCH THE PLAN, PLEASE CLARIFY.
  
 5.)IMPACT FEES MAY BE DUE.PLEASE HAVE THE PLANS
 STAMPED AND PROVIDE A RECEIPT SHOWING THAT FEES HAVE
 BEEN PAID.233-5025 FOR MORE INFORMATION.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-18 Cont ID  
Sent By dpalmer Date 2007-09-18 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2007-09-18 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 10:42 Sent To  
Notes
2007-09-11 11:37:38** TEMP FAILED STATUS AS PLANS WERE SUBMITTED BACK IN
 AS *REVISIONS* AND NOT AS A RESUB. PERMIT APPLICATION
 WAS NOT BROUGHT BACK IN. THE PREVIOUS STAMPED
 ELECTRICAL PLANS WERE ALSO NOT RESUBMITTED. CALLED AND
 SPOKE TO JACK HANSON AND HE WILL BRING IN PREVIOUS
 STAMPED PLANS. THE OTHER PLANS CAN BE BROUGHT IN WITH
 NOT FEE, BUT WILL STILL OWE RESUB FEE BALANCE FROM
 PREVIOUS RESUB ON 8/31.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-13 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2007-07-13 Time 18:36 Sent To  
Notes
2007-07-13 19:12:042007-07-13 19:12:04
 **** UNSAT ****
  
 1) NOTE: PLEASE SEE THE PREVIOUS NOTE #1 AS THIS
 REQUESTED FOR THE CERTIFICATION SHEETS OF THE ENERGY
 CALCULATIONS TO BE SIGNED ETC AS REQUIRED PER
 13-103.1.1.1 OF THE FBC.
 PLEASE SEE THE OWNER AGENT IS STILL NOT SIGNED ON
 SHEETS.
  
 ** THE FOLLOWING WAS REDLINED ON PLANS AS ROOM
 DESIGNATIONS ARE NOW ON PLANS.
 THE SERVER ROOM AS SHOWN WILL NOT BE AN IT AND SHALL
 MEET CODE ACCORDINGLY. THIS SHALL BE VERIFIED IN FIELD.
 IF THIS IS AN IT ROOM, THEN PLEASE SEE REVISIONS PER
 NEC 645 AND NFPA-75 WILL BE REQUIRED.
 PLEASE SEE 2005 NEC/ NFPA-70 AND 2004 FBC W/ 2006
 REVISIONS WAS ALSO REDLINED ON PLANS AS THIS WAS
 MISSING. (MAY NOT STATE LATEST EDITION).
  
 ** COMMENT #1 ABOVE MUST BE ADDRESSED. ELECTRICAL PLANS
 ARE OK AND HAVE BEEN STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 12:41 Sent To  
Notes
2007-06-20 13:05:46*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH
 CORRELATE WITH THE PLANS. PLEASE SEE THE FIXTURES DO
 NOT MATCH. PLEASE SEE THE NUMBER AND TYPE OF FIXTURES
 DO NOT MATCH. PLEASE SEE THE WATTAGE OF FIXTURES ALSO
 DOES NOT MATCH.
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH
 PLANS AND CALCULATIONS.
 PLEASE SEE THE REQUIRED SIGNATURE FROM THE OWNER AGENT
 IS NOT ON THE SECOND SHEET AS REQUIRED.
 PLEASE SEE 13-415.1.AB.1.1.
  
 2) NOTE: PLEASE SEE THE RISER IS MISSING THE NEW
 FEEDERS TO THE NEW PANEL.
 240.4,310.16, FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE BOTH PANEL 100 AND 100A PANEL
 SCHEDULES ARE NOT SUBMITTED.
 PLEASE SEE THE CIRCUITING ON PLANS NEED TO COORDINATE
 WITH THE PANEL SCHEDULES TO BE SUBMITTED.
 PLEASE SEE 408.4, 310.16, 240.4. PLEASE SEE ALSO KNOW
 THE USE OF *GENERAL LIGHTING* OR GENERAL RECEPTACLES*
 IS NOT ACCEPTABLE ON PANEL SCHEDULE. EACH MUST BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. ALL
 ROOMS SHALL CONTAIN DESIGNATIONS. THE PANEL SCHEDULES
 NEED TO CORRELATE WITH THOSE DESIGNATIONS BY NUMERICAL
 OR NAMED DESIGNATIONS.
 PLEASE BE SURE THE PANEL INFORMATION IS STATED ON
 SCHEDULES: SIZE, VOLTAGE, AMPERAGE ETC.
  
 4) NOTE: PLEASE SEE THE PLANS DO NOT SHOW THE LOCATION
 OF THE NEW PANELS.
 PLEASE SEE 110.26, 408.7, 240.24.
  
 5) NOTE: PLEASE INDICATE NEW OR EXISTING GFI LOCATIONS
 FOR A/C EQUIPMENT.210.8, 210.63
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SUBMITTED
 FOR REVIEW AND/OR INFORMATION MISSING FROM PLANS, THERE
 MAY BE NEW COMMENTS ON THE NEXT REVIEW.
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-12 Cont ID  
Sent By mwennerg Date 2007-12-12 Time 12:10 Rev Time 0.00
Received By mwennerg Date 2007-12-12 Time 12:09 Sent To  
Notes
2007-12-12 12:11:00REVISION FOR DRYWALL PENETRATION SYSTEMS DATED
 11/27/07.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-19 Cont ID  
Sent By mwennerg Date 2007-09-19 Time 14:56 Rev Time 0.00
Received By mwennerg Date 2007-09-19 Time 14:56 Sent To  
Notes
2007-09-19 14:57:12PLANS APPROVED AND STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By mwennerg Date 2007-07-20 Time 15:34 Rev Time 0.00
Received By mwennerg Date 2007-07-20 Time 15:34 Sent To  
Notes
2007-07-20 15:35:24PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED AND PLANS WILL
 BE STAMPED BY FIRE WHEN RESUBMITTED FOR OTHER REVIEW
 COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mwennerg Date 2007-06-26 Time 13:13 Rev Time 0.00
Received By mwennerg Date 2007-06-23 Time 21:44 Sent To  
Notes
2007-06-26 13:44:55***DENIED***
  
 1) DOOR SCHEDULE LISTS DOOR #14 AS METAL UNDER THE FIRE
 RATING COLUMN. PLEASE INDICATE ACTUAL RATING IN TERMS
 OF MINUTES IF APPLICABLE.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) PLEASE PROVIDE INFORMATION REGARDING WHAT TYPE OF
 MATERIAL WILL BE STORED IN WAREHOUSE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 11:39 Sent To  
Notes
2007-12-07 14:07:27TO "BOB"#4
2007-12-04 11:39:33WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 10:43 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 10:43 Sent To  
Notes
2007-10-25 10:43:51WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 10:39 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 10:39 Sent To  
Notes
2007-09-10 13:52:13TO "BOB"#6
2007-09-04 10:40:11WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 16:47 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 16:47 Sent To  
Notes
2007-07-13 10:33:41TO "BOB"#6
2007-07-10 16:48:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-29 Cont ID  
Sent By shill Date 2007-06-29 Time 18:01 Rev Time 0.00
Received By shill Date 2007-06-07 Time 15:14 Sent To  
Notes
2007-06-19 09:00:17 
  
 TO "BOB" # 15
2007-06-07 15:14:47WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-29 Cont ID  
Sent By rregueir Date 2007-10-29 Time 18:22 Rev Time 0.00
Received By rregueir Date 2007-10-29 Time 18:22 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-09-17 Cont ID  
Sent By rregueir Date 2007-09-17 Time 10:49 Rev Time 0.00
Received By rregueir Date 2007-09-17 Time 10:09 Sent To  
Notes
2007-09-17 10:49:45REVIEW #: 3
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THE PERMIT APPLICATION WAS NOT RETURNED WITH THIS
 SUBMITTAL. BE SURE TO RETURN THE PERMIT APPLICATION
 WHEN RESUBMITTING TO FACILITATE PERMIT ISSUANCE.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS COMMENT DOES NOT APPEAR TO HAVE BEEN ADDRESSED.
 THERE IS NO EVIDENCE IN THIS SUBMITTAL THAT A REVIEW OF
 THESE PLANS BY THE BASE BUILDING DESIGNER(S) OF RECORD
 HAS TAKEN PLACE. IN ORDER FOR A TENANT BUILD-OUT PERMIT
 TO BE ISSUED FOR A SHELL BUILDING WHICH HAS NOT
 RECEIVED A C.O., THE BASE-BUILDING DESIGNER(S) OF
 RECORD SHALL PERFORM A SHP DRAWING REVIEW AND APPROVE
 THE TENANT BUILD-OUT PLANS. THIS IS THE 2ND TIME THIS
 HAS BEEN REQUESTED. SEE BUILDING PLAN REVIEW COMMENT #1
 FROM 7/17/07.
  
 2. OK
  
 3. PLEASE REFERENCE THE CODE WHICH WAS IN EFFECT AT THE
 TIME OF APPLICATION: FBC 2004, NOT 2001 WHICH IS SHOWN
 AT C.U. MOUNTING DETAIL.
  
 4. THERE IS NO INFORMATION ON PLUMBING PLAN REGARDING
 CONDENSATE DISPOSAL OTHER THAN A NOTE PROHIBITING
 CONDENSATE FROM BEING DISCHARGED ON THE ROOF, WHICH IS
 NOT RELEVANT SINCE THERE ARE NO AIR HANDLERS ON THE
 ROOF. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2.1, FBC 106.1.1 AND FBC
 1503.6.
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. SHOW LOCATION OF DUCT SMOKE DETECTOR ON AHU-3
 SUPPLY. DETECTOR IS TO BE LOCATED UPSTREAM OF THE FIRST
 TAP IN ORDER TO MONITOR THE ENTIRE AIRFLOW PER FBC,M
 606.3.
  
 NOTE: A WRITTEN RESPONSE TO REVIEW COMMENTS MAY HELP
 THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-20 Cont ID  
Sent By rregueir Date 2007-07-20 Time 13:56 Rev Time 0.00
Received By rregueir Date 2007-07-19 Time 11:14 Sent To  
Notes
2007-07-20 11:52:03--------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THE WRITTEN RESPONS TO PREVIOUS MECHANICAL REVIEW
 COMMENTS IS NOT AN ACCURATE REFLECTION OF THE
 MECHANICAL PLAN REVIEW HISTORY RELATED TO THESE PLANS.
 THE PLANS WERE PREVIOUSLY SUBMITTED AS A REVISION TO
 THE SHELL BUILDING. HOWEVER, THEY WERE NOT REVIEWED AT
 THAT TIME. THEY WERE REJECTED DUE TO THE FACT THAT THEY
 WERE NOT DESIGNED BY THE ENGINEER OF RECORD FOR THE
 SHELL AND WERE DONE UNDER THE WRONG CODE (2004 FBC,
 WHILE THE SHELL IS UNDER THE 2001 FBC). IF THE PLANS
 WERE LOST, THEY WERE NOT LOST BY THIS OFFICE, AS OUR
 POLICY IS NOT TO RETAIN DENIED PLANS. ALL SETS ARE
 RETURNED TO THE CONTRACTOR ONCE REVIEWS ARE COMPLETE.
 IN FACT, OUR RECORDS INDICATE THAT PETE LOMBARDI PICKED
 UP THE DENIED PLUMBING, ELECTRICAL, MECHANICAL AND
 BUILDING REVISIONS ON MAY 21, 2007.
  
 THE PROVISO, WHICH REQUIRES PERMANENT MEANS OF ACCESS
 TO THE ROOF FOR SERVICE OF EQUIPMENT, HAS STILL NOT
 BEEN ADRESSED EITHER AS A PART OF THIS PERMIT
 APPLICATION OR THE BASE BUILDING PERMIT. THE FOLLOWING
 COMMENTS REPRESENT THE FIRST REVIEW OF THESE PLANS
 UNDER THIS PERMIT APPLICATION, UNDER THE CORRECT CODE,
 AND BY AN ACCEPTABLE DESIGNER BECAUSE THE MECHANICAL
 PLANS WERE NOT SUBMITTED AT TIME OF INITIAL
 APPLICATION.
  
 1. A SHOP DRAWING REVIEW OF THESE PLANS BY THE DESIGNER
 OF RECORD FOR THIS BUILDING IS NEEDED. SEE BUILDING
 REVIEW COMMENT #1.
  
 2. A/C SYSTEMS 2 AND 3 ON PLANS SHOW 10.6 AND 10 SEER
 RESPECTIVELY. ENERGY CALCULATIONS SHOW THEM BOTH TO BE
 13 SEER, WHICH IS THE MINIMUM REQUIRED PER FBC
 13-407.1.ABC.3.2A. PLEASE COORDINALTE DRAWINGS AND
 ENERGY CALCULATIONS.
  
 3. PLEASE SHOW CONDENSING UNIT CONNECTION DETAIL TO
 EXISTING ROOF STANDS TO BE ENGINEERED FOR 140 MPH WIND
 ZONE PER FBC,M 301.13 AND FBC CH.1609.
  
 4. PLEASE SHOW MEANS AND LOCATION OF CONDENSATE
 DISPOSAL PER FBC,M 307.2.1.
  
 5. PLEASE PROVIDE AIR BALANCE SCHEDULE SHOWING SUPPLY,
 RETURN, OUTDOOR AIR AND EXHAUST CFM TOTALS SHOWING THE
 SPACE TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS
 PER FBC 13-409.1.
  
 6. SHUTOFF DAMPER CONTROLS ARE REQUIRED: OUTDOOR AIR
 SUPPLY SYSTEMS SHALL BE EQUIPPED WITH MOTORIZED DAMPERS
 THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES
 SERVED ARE NOT IN USE. GRAVITY (NON MOTORIZED) DAMPERS
 ARE ACCEPTABLE IN SYSTEMS WITH A DESIGN OUTSIDE AIR
 INTAKE OF 300 CFM OR LESS. FBC 13-409.1.ABC.3.3
  
 7. OUTDOOR AIR CALCULATIONS ARE TO BE BASED ON FBC,M
 TABLE 403.3 OR ASHRAE 62.1-2004, NOT ASHRAE 62-1989
  
 8. WHERE MECHANICAL EXHAUST IS REQUIRED BY TABLE 403.3
 (TOILET ROOMS), RECIRCULATION OF AIR FROM SUCH SPACES
 SHALL BE PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3. THIS CAN BE ACHIEVED BY
 INTERLOCKING THE BATH FAN WITH THE AHU SUPPLYING AIR TO
 THE TOILET ROOMS (IN THIS CASE, AHU 3).
  
 9. PROVISIONS SHALL ALSO BE MADE TO ASSURE VENTILATION
 IS ALSO PROVIDED IN TOILET ROOMS WHENEVER THESE SPACES
 ARE OCCUPIED PER FBC,M 401.3. THIS MAY BE ACCOMPLISHED
 BY HAVING THE EXHAUST FANS ACTIVATE WHENEVER THE LIGHTS
 ARE ON IN THE SPACE BEING SERVED OR OTHER APPROVED
 MEANS.
  
 10. AHU 2 AND AHU 3 REQUIRE FAN SHUT-DOWN BY SMOKE
 DTETECTOR PER FBC,M 606.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By rregueir Date 2007-06-19 Time 18:52 Rev Time 0.00
Received By rregueir Date 2007-06-19 Time 18:45 Sent To  
Notes
2007-06-19 18:52:33-------------------DENIED-------------------
  
 PLEASE PROVIDE MECHANICAL PLANS AND EQUIPMENT SCHEDULES
 AS REQUIRED BY FBC 106.3.5.1.4
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 10:10 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 10:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 08:20 Rev Time 0.00
Received By jleech Date 2007-07-31 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By jleech Date 2007-06-25 Time 14:06 Rev Time 0.00
Received By jleech Date 2007-06-25 Time 14:06 Sent To  
Notes
2007-06-25 14:26:39DENIED;
 1. PAGE A-1 ROOM FINISH SCHEDULE; BATHROOM WALLS TO
 COMPLY WITH FBC-2004 BUILDING SECTION 1210.2. PAINT CAN
 CHIP OR BE SCRATCHED.
 2. SERVICE SINK NOT SHOWN ON FLOOR PLAN. PAGE A-1.
 3. SHOW DETAIL OF DRINKING FOUNTAIN WITH ALL REQUIRED
 HANDICAP REQUIREMENTS.
 4. PAGE P-1 PLUMBING NOTE #18, CHANGE CODE DATE TO
 2004.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695