Plan Review Details - Permit 07060142
Plan Review Stops For Permit 07060142
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-06 Cont ID  
Sent By rmcdouga Date 2007-11-06 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2007-11-06 Time 08:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By rmcdouga Date 2007-10-30 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2007-10-30 Time 16:45 Sent To  
Notes
2007-10-30 16:48:14F STATUS WILL BE CHANGED TO P AFTER PLANS HAVE BEEN
 TAKEN TO PALM BEACH COUNTY FOR IMPACT FEE STAMPS AND
 ARE RESUBMITTED WITH COPY OF PAID IMPACT FEE RECEIPT.
 ALSO NEED NOC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-15 Cont ID  
Sent By rmcdouga Date 2007-08-15 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2007-08-15 Time 13:51 Sent To  
Notes
2007-08-15 19:03:012004 FBC W/2006 SUPPLEMENT
 2004 EXISTING BUILDING CODE
 UNPERMITTED CHANGE OF OCCUPANCY
 CONVERT GARAGE TO STUDIO (U TO R-3)
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE OCCUPANCY CLASSIFICATION IS R-3 . PLEASE CORRECT
 ON SHEET A001.
  
 4) THE CONSTRUCTION TYPE IS VB. PLEASE CORRECT ON SHEET
 A001.
  
 5) THE JOB DESCRIPTION IS TO CHANGE OF OCCUPANCY FROM
 UTILITY TO R-3. CONVERT A GARAGE TO A STUDIO. PLEASE
 CORRECT ON SHEET A001.
  
 6)SPECIFY ON THE PLANS WHICH WALLS ARE EXISTING AND
 WHICH ONES ARE NEW.
  
 7) PROVIDE STRUCTURAL DETAILS OF THE 6" CMU WALL
 SHOWING THAT IT COMPLIES TO THE 2004 FBC.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE SPRAYED FOAM
 INSULATION.
  
 9) SHOW COMPLIANCE WITH THE FOLLOWING EXISTING BUILDING
 REQUIREMENTS :
 807.2 WIND LOADS.
 BUILDINGS AND STRUCTURES SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER WIND IMPORTANCE FACTORS BASED ON THE
 FLORIDA BUILDING CODE, BUILDING TABLE 1604.5, (HIGH
 -VELOCITY HURRICANE ZONES SHALL COMPLY WITH TABLE
 1615.2) SHALL BE ANALYZED AND SHALL COMPLY WITH THE
 APPLICABLE WIND LOAD PROVISIONS OF THE FLORIDA BUILDING
 CODE, BUILDING .
 707.5.1 EVALUATION AND ANALYSIS.
 AN ENGINEERING EVALUATION AND ANALYSIS THAT ESTABLISHES
 THE STRUCTURAL ADEQUACY OF THE ALTERED STRUCTURE SHALL
 BE PREPARED BY A REGISTERED ARCHITECT OR ENGINEER AND
 SUBMITTED TO THE BUILDING CODE OFFICIAL. WHERE MORE
 THAN 30 PERCENT OF THE TOTAL SUM OF FLOOR AND ROOF
 AREAS OF THE BUILDING OR STRUCTURE HAS BEEN OR IS
 PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN
 A 12-MONTH PERIOD, THE EVALUATION AND ANALYSIS SHALL
 DEMONSTRATE THAT THE ALTERED BUILDING OR STRUCTURE
 COMPLIES WITH THE FLORIDA BUILDING CODE, BUILDING FOR
 WIND LOADING.
 707.5.2 LIMITED STRUCTURAL ALTERATION.
 WHERE NOT MORE THAN 30 PERCENT OF THE TOTAL SUM OF
 FLOOR AND ROOF AREAS OF THE BUILDING IS INVOLVED IN
 STRUCTURAL ALTERATION WITHIN A 12-MONTH PERIOD, THE
 EVALUATION AND ANALYSIS SHALL DEMONSTRATE THAT THE
 ALTERED BUILDING OR STRUCTURE COMPLIES WITH THE LOADS
 APPLICABLE AT THE TIME THE BUILDING WAS CONSTRUCTED.
  
 10) SPECIFY THE RAFTER TO CONC. BEAM CONNECTORS.
  
 11) SHOW COMPLIANCE WITH R311.4.1 EXIT DOOR REQUIRED.
 NOT LESS THAN ONE EXIT DOOR CONFORMING TO THIS SECTION
 SHALL BE PROVIDED FOR EACH DWELLING UNIT. THE REQUIRED
 EXIT DOOR SHALL PROVIDE FOR DIRECT ACCESS FROM THE
 HABITABLE PORTIONS OF THE DWELLING TO THE EXTERIOR
 WITHOUT REQUIRING TRAVEL THROUGH A GARAGE. ACCESS TO
 HABITABLE LEVELS NOT HAVING AN EXIT IN ACCORDANCE WITH
 THIS SECTION SHALL BE BY A RAMP IN ACCORDANCE WITH
 SECTION R311.6 OR A STAIRWAY IN ACCORDANCE WITH SECTION
 R311.5 .
  
 12) EXISTING BUILDING 812.5 ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING. PROVIDE A BATHROOM WITH A 29" CLEAR OPENING
 AS REQUIRED BY FBC CHAPTER 11.
  
 13) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 14) SUBMIT MIAMI-DADE OR STATE OF FLORIDA PRODUCT
 APPROVALS FOR THE WINDOWS, STORM PANELS AND DOORS.
  
 15)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By rmcdouga Date 2007-07-11 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2007-07-11 Time 14:04 Sent To Z
Notes
2007-07-11 15:01:42DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ARCHITECTURAL FIRM IS REQUIRED TO INDICATE THE
 FIRM LICENSE NUMBER IN THE TITLE BLOCK ON EACH DRAWING.
 SEE FAC 61G1-16.004 AND FS 481.
  
 3) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. SEE FBC CHAPTER 13.
  
 4) I HAVE BEEN UNABLE TO LOCATE ANY DOCUMENTATION THAT
 A PERMIT WAS ISSUED TO CONVERT THE GARAGE TO LIVING
 SPACE. THE PROPERTY APPRAISER ALSO LISTS THIS STRUCTURE
 AS A FINISHED DETACHED GARAGE. UNLESS YOU CAN PROVIDE
 DOCUMENTATION THAT THIS CONVERSION WAS PERMITED, I WILL
 HAVE TO CONSIDER IT AN ILLEGAL CONVERSION AND IT WILL
 HAVE TO BE RETURNED TO A GARAGE OR APPLY FOR THE
 PERMITS NEEDED TO CHANGE IT INTO LIVING SPACE. COUNTY
 IMPACT FEES WILL BE REQUIRED FOR THE CHANGE.
  
 5) THE FINISHED FLOOR ELEVATION APPEARS TO BE AT OR
 NEAR THE EXTERIOR GRADE. THIS DOES NOT COMPLY WITH CODE
 REQUIREMENTS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-07 Cont ID  
Sent By btrobaug Date 2007-08-07 Time 07:42 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 06:54 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 07:48 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 07:19 Sent To M
Notes
2007-06-18 07:31:57 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD. ALSO SEE THE REFERENED CODES
 FOR THE 2004 FBC, CHANGE NOTES TO CORRECT CODE
 REFERENCE STANDARDS. SHEET A001.
  
 3} PER 230.70(A)(1) A DISCONNECT IS REQUIRED OUTSIDE AT
 THE METER IF THERE IS MORE THAN 8 FEET OF UNPROTECTED
 CONDUCTORS ENTERING THE BUILDING(LOCAL AMENDMENT).
  
 4} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 6} 240.24D) NOT IN VICINITY OF EASILY IGNITIBLE
 MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN
 THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS. SEE WATER HEATER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-06-05 Cont ID  
Sent By ssherman Date 2007-06-05 Time 10:16 Rev Time 0.00
Received By ssherman Date 2007-06-05 Time 10:16 Sent To  
Notes
2007-06-05 10:16:34HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 09:50 Sent To B
Notes
2007-10-19 09:51:03TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 14:23 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 14:23 Sent To Z
Notes
2007-07-30 14:24:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By rmcdouga Date 2007-07-11 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2007-06-06 Time 14:53 Sent To  
Notes
2007-06-06 14:57:57TO "SFR""E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-07 Cont ID  
Sent By tgordon Date 2007-08-07 Time 14:07 Rev Time 0.25
Received By tgordon Date 2007-08-07 Time 14:07 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 07:54 Rev Time 0.30
Received By tgordon Date 2007-06-19 Time 07:54 Sent To Z
Notes
2007-06-19 08:07:14*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE ADJUST VALUE TO SHOW ALL LABOR AND MATERIAL
 COST (FAIR MARKET VALUE).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-15 Cont ID  
Sent By jleech Date 2007-08-15 Time 09:01 Rev Time 0.00
Received By jleech Date 2007-08-15 Time 09:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By jleech Date 2007-07-05 Time 07:52 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 07:51 Sent To B
Notes
2007-07-05 07:59:04DENIED;
 1. CORPORATE LICENSE NUMBER REQUIRED TO BE IN THE TITLE
 BLOCK.
 2. WATER HEATERS IN BEDROOM CLOSETS MUST BE ISOLATED BY
 WALLS, DOOR OR ACCESS PANEL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-01 Cont ID  
Sent By choops Date 2007-08-01 Time 17:10 Rev Time 0.00
Received By choops Date 2007-08-01 Time 17:10 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-06-21 Cont ID  
Sent By choops Date 2007-06-21 Time 08:23 Rev Time 0.00
Received By choops Date 2007-06-21 Time 08:23 Sent To P
Notes
2007-06-21 08:24:50NOTE:MUST OBTAIN A RENTAL LICENSE IF RENTING GUEST
 HOUSE IN THE FUTURE.