| 2007-06-25 16:58:15 | PROJECT: 5405 BROADWAY/ NOZZLE NOLEN |
| | |
| | PROJECT DETAILS: STRUCTURAL REINFORCEMENT FOR CONCRETE |
| | CANOPY SLABS |
| | |
| | REVIEW: 2004 FLORIDA EXISTING BUILDING CODE WITH 2006 |
| | REVISIONS |
| | |
| | STATUS: DENIED |
| | |
| | |
| | BUILDING PLAN REVIEW COMMENTS: |
| | |
| | 1) ALL WORK SHALL COMPLY WITH THE FOLLOWING BUILDING |
| | CODE SECTION #302: |
| | |
| | REPAIRS |
| | 302.1SCOPE. |
| | REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE PATCHING |
| | OR RESTORATION OF MATERIALS, ELEMENTS, EQUIPMENT, OR |
| | FIXTURES FOR THE PURPOSE OF MAINTAINING SUCH MATERIALS, |
| | ELEMENTS, EQUIPMENT, OR FIXTURES IN GOOD OR SOUND |
| | CONDITION. |
| | 302.2APPLICATION. |
| | REPAIRS SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 4. |
| | |
| | 2) THE MATERIALS USED FOR REPAIR MUST CONFORM TO |
| | SECTION #401: |
| | |
| | 401.2PERMITTED MATERIALS. |
| | EXCEPT AS OTHERWISE REQUIRED HEREIN, WORK SHALL BE DONE |
| | USING MATERIALS PERMITTED BY THE APPLICABLE CODE FOR |
| | NEW CONSTRUCTION OR USING LIKE MATERIALS SUCH THAT NO |
| | HAZARD TO LIFE, HEALTH OR PROPERTY IS CREATED. |
| | EXCEPTION: REPAIRS TO A HISTORIC BUILDING SHALL BE |
| | PERMITTED USING ORIGINAL OR LIKE MATERIALS. MATERIALS |
| | SHALL COMPLY WITH SECTIONS 403.1, 403.2 AND 403.3. |
| | |
| | 401.3CONFORMANCE. |
| | THE WORK SHALL NOT MAKE THE BUILDING LESS CONFORMING TO |
| | THE BUILDING, PLUMBING, MECHANICAL, ELECTRICAL OR FIRE |
| | CODES OF THE JURISDICTION, OR TO ALTERNATIVE MATERIALS, |
| | DESIGN AND METHODS OF CONSTRUCTION, OR ANY PREVIOUSLY |
| | APPROVED PLANS, MODIFICATIONS, ALTERNATIVE METHODS, OR |
| | COMPLIANCE ALTERNATIVES, THAN IT WAS BEFORE THE REPAIR |
| | WAS UNDERTAKEN. |
| | |
| | 3)ALL WORK SHALL CONFORM TO THE STRUCTURAL |
| | REQUIREMENTS OF SECTION #407: |
| | |
| | 407.1GENERAL. |
| | REPAIRS OF STRUCTURAL ELEMENTS SHALL COMPLY WITH THIS |
| | SECTION. |
| | |
| | 407.2REDUCTION OF STRENGTH. |
| | REPAIRS SHALL NOT REDUCE THE STRUCTURAL STRENGTH OR |
| | STABILITY OF THE BUILDING, STRUCTURE, OR ANY INDIVIDUAL |
| | MEMBER THEREOF. |
| | EXCEPTION: SUCH REDUCTION SHALL BE ALLOWED, PROVIDED |
| | THE CAPACITY IS NOT REDUCED TO BELOW THE FLORIDA |
| | BUILDING CODE, BUILDING LEVELS. |
| | |
| | 407.3.1NEW STRUCTURAL FRAME MEMBERS. |
| | NEW STRUCTURAL FRAME MEMBERS USED IN THE REPAIR OF |
| | DAMAGED BUILDINGS, INCLUDING ANCHORAGE AND CONNECTIONS, |
| | SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4) PLEASE INDICATE THE EXISTING BUILDING AND CANOPY |
| | DIMENSIONS. |
| | |
| | 5) PLEASE PROVIDE THEDIMENSIONAL LOCATIONS OF THE |
| | CANOPY BRACKET INSTALLATION. |
| | |
| | 6) PLEASE PROVIDE A TYPICAL WALL SECTION REFLECTING THE |
| | EXISTING WALL CONSTRUCTION AND THE MECHANICAL |
| | ATTACHMENT OF THE CANOPY BRACKETS. |
| | |
| | 7) PLEASE INDICATE TYPE AND LENGTH OF WELDS OF BRACKETS |
| | / SUBMIT APPROVED SHOP DRAWINGS. |
| | |
| | |