Plan Review Details - Permit 07060061
Plan Review Stops For Permit 07060061
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 17:12 Rev Time 0.00
Received By shill Date 2007-07-26 Time 17:12 Sent To  
Notes
2007-07-26 17:15:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 3.)THE PLAN GIVES THE SLAB DIMENSION BUT NO OTHER
 INFORMATION.PROVIDE A PLAN FOR THE SLAB SHOWING ALL
 STRUCTURAL INFORMATION, AND STATE WHETHER THIS IS
 FORMED AND POURED OR IF THIS IS A PREFAB SLAB.PREFAB
 SLABS REQUIRE ENGINEERED CALCULATIONS TO SHOW HOW IT
 CAN RESIST THE WIND LOADS FBC R 301.
  
 4.)TWO IDENTICAL COLLATED SETS REQUIRED FOR
 PERMITTING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By btrobaug Date 2007-06-15 Time 12:20 Rev Time 0.00
Received By btrobaug Date 2007-06-15 Time 12:10 Sent To G
Notes
2007-06-15 12:20:23 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 TWO COPIES OF ALL DOCUMENTS ARE REQUIRED PER 106.1 FBC
 AS AMENDED.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE COST
 OF LABOR AND MATERIAL FOR THE INSTALLATION OF ALL
 COMPONENTS UNDER THE SCOPE OF THIS PERMIT. FBC 108.3.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By mperson Date 2007-06-28 Time 13:45 Rev Time 0.45
Received By mperson Date 2007-06-28 Time 13:45 Sent To B
Notes
2007-06-28 14:39:05DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. VALUE APPEARS TO BE TO LOW FOR THE PROPOSED
 GENERATOR:
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT SHOW ALL CUT SECTIONS AND CORRESPONDING
 LENGTHS. THIS INCLUDES THE EXISTING GAS SYSTEM, PLEASE
 REFERENCE THE PERMIT INFORMATION ATTACHED TO THE GAS
 COMMENTS THAT INDICATES EXISTING GAS TO A DRYER AND
 WATER HEATER. PLEASE CLEARLY INDICATE ON THE
 RESUBMITTED ISOMETRIC THE EXISTING GAS PIPE AND THE
 PROPOSED GAS PIPE TO THE GENERATOR.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE RESUBMITTED ISOMETRIC.
  
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 LP GAS 10 PSI WITH 0.5 TO APPLIANCES.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 A} GENERATOR (WITH BTU LOAD OF GENERATOR). PLEASE
 INCLUDE MANUFACTURER'S INSTALLATION INSTRUCTIONS WITH
 INFORMATION ON SETBACKS TO STRUCTURES.
 B} 1ST AND 2ND STAGE REGULATORS, WITH THE MAKE,
 MODEL NUMBER, LOAD CAPACITY, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 9. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP TANKS,
 TYPE OF TANK (DOT OR ASME), THE DISTANCE OF THE TANK
 FROM THE BUILDING AND ADJACENT PROPERTY LINES THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1, 6.6.16, AND 6.6.2.1.
  
 11. NOTE: PLEASE REFERENCE ZONING COMMENT#1 AND
 CLEARLY INDICATE THE PROPOSED GENERATORS LOCATION ON
 TWO COPIES OF A SITE PLAN INDICATING ALL DEMENSIONS
 FROM PROPERTY LINES AND DISTANCES FROM ADJACENT
 DWELLING STRUCTURES.
  
 12. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS ON ALL RESUBMITTED DRAWINGS PRIOR TO
 RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 08:44 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 08:44 Sent To E
Notes
2007-06-07 08:45:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 11:38 Sent To  
Notes
2007-06-06 11:38:39TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By tgordon Date 2007-06-14 Time 14:29 Rev Time 0.15
Received By tgordon Date 2007-06-14 Time 14:29 Sent To E
Notes
2007-06-15 08:14:57*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 2) PLEASE BE AWARE. PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED EQUIPMENT POWERED BY
 INTERNAL COMBUSTION ENGINES SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL
 NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT
 BE DRAWN INTO THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED
 BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT
 TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES
 TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE, BUILDING, WINDOWS,
 DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND
 EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD
 INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By choops Date 2007-06-06 Time 16:36 Rev Time 0.00
Received By choops Date 2007-06-06 Time 16:36 Sent To I
Notes
2007-06-06 16:40:55***FAILED***
  
  
 1)PLEASE INDICATE THE LOCATION OF GENERATOR ON
 SURVEYS, AND INDICATE SETBACK DIMENSIONS TO PROPERTY
 LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720