Plan Review Details - Permit 07060056
Plan Review Stops For Permit 07060056
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By mperson Date 2007-09-21 Time 14:01 Rev Time 0.00
Received By mperson Date 2007-09-21 Time 14:01 Sent To PC
Notes
2007-09-21 14:06:54REVISION: LAYOUT CHANGED & DELIVERY PRESSURE INCREASED
 TO 2 PSI.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
 POOL HEATER WITH POOL PERMT #07041051:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By mperson Date 2007-08-20 Time 08:03 Rev Time 0.33
Received By mperson Date 2007-08-20 Time 08:03 Sent To PC
Notes
2007-08-20 08:15:02REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE GAS REVISION FOR PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. THE REVISED GAS ISOMERIC DOES NOT NOT INDICATE ALL
 THE CORRESPONDING LENGTHS OF THE INDICATED CUT SECTIONS
 OF PIPE. PLEASE CORRECT AND RESUBMIT.
  
 2. THE REVISED GAS ISOMETRIC DOES NOT INDICATE THE
 ABOVE GROUND PIPING MATERIAL. PLEASE CORRECT AND
 RESUBMIT.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: IN ORDER TO VERIFY THIS ALL THE CORRESPONDING
 LENGTHS OF THE CUT SECTIONS OF PIPE MUST BE INDICATED
 ON THE GAS REVISION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-06-27 Cont ID  
Sent By mperson Date 2007-06-27 Time 14:13 Rev Time 0.45
Received By mperson Date 2007-06-27 Time 14:13 Sent To PC
Notes
2007-06-27 14:16:03IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 15:54 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 15:54 Sent To G
Notes
2007-08-29 15:55:01TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 10:02 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 10:02 Sent To G
Notes
2007-08-15 10:02:43TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By mperson Date 2007-06-27 Time 14:16 Rev Time 0.00
Received By mperson Date 2007-06-06 Time 09:02 Sent To  
Notes
2007-06-06 09:02:21TO "G" BOX