Plan Review Details - Permit 07060035
Plan Review Stops For Permit 07060035
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-27 Cont ID  
Sent By kconrad Date 2007-11-27 Time 17:45 Rev Time 0.00
Received By kconrad Date 2007-11-27 Time 16:15 Sent To I
Notes
2007-11-27 18:06:59PROJECT: 520 PURITAN ROAD/#07060035
  
 PROJECT SCOPE: STRUCTURAL REPAIRS/INTERIOR REMODEL
  
 STATUS:PASSED
  
 CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE
 W/2006 REVISIONS
 2004 FLORIDA RESIDENTIAL BUILDING CODE W/ 2006
 REVISIONS
 CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE
 ADMINISTRATION AMENDMENTS, CHAPTER 1, 2004 EDITION
  
  
 COMMENTS:
  
 1) PLEASE BE ADVISED THAT A SEPARATE ROOFING PERMIT
 MUST BE APPLIED FOR BY A LICENSED ROOFING CONTRACTOR AS
 PER THE FOLLOWING FLORIDA STATUTE. THEREFORE, A
 REVISION TO THE INITIAL SCOPE OF WORK IS DENIED.
  
 THE 2007 FLORIDA STATUTES
  
 TITLE XXXII
 REGULATION OF PROFESSIONS AND OCCUPATIONS CHAPTER 489
 CONTRACTING
  
 489.113QUALIFICATIONS FOR PRACTICE; RESTRICTIONS.--
  
 (3)A CONTRACTOR SHALL SUBCONTRACT ALL ELECTRICAL,
 MECHANICAL, PLUMBING, ROOFING, SHEET METAL, SWIMMING
 POOL, AND AIR-CONDITIONING WORK, UNLESS SUCH CONTRACTOR
 HOLDS A STATE CERTIFICATE OR REGISTRATION IN THE
 RESPECTIVE TRADE CATEGORY, HOWEVER:
  
 (B)A GENERAL, BUILDING, OR RESIDENTIAL CONTRACTOR
 SHALL NOT BE REQUIRED TO SUBCONTRACT THE INSTALLATION,
 OR REPAIR MADE UNDER WARRANTY, OF WOOD SHINGLES, WOOD
 SHAKES, OR ASPHALT OR FIBERGLASS SHINGLE ROOFING
 MATERIALS ON A NEW BUILDING OF HIS OR HER OWN
 CONSTRUCTION.
  
 (G)NO GENERAL, BUILDING, OR RESIDENTIAL CONTRACTOR
 CERTIFIED AFTER 1973 SHALL ACT AS, HOLD HIMSELF OR
 HERSELF OUT TO BE, OR ADVERTISE HIMSELF OR HERSELF TO
 BE A ROOFING CONTRACTOR UNLESS HE OR SHE IS CERTIFIED
 OR REGISTERED AS A ROOFING CONTRACTOR.
  
  
 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-03 Cont ID  
Sent By kconrad Date 2007-10-03 Time 18:05 Rev Time 0.00
Received By kconrad Date 2007-10-03 Time 15:45 Sent To I
Notes
2007-10-03 18:05:45PROJECT: 520 PURITAN ROAD/#07060035
  
 PROJECT SCOPE: STRUCTURAL REPAIRS/INTERIOR REMODEL
  
 STATUS:FAILED
  
 CODE REVIEW:2004 FLORIDA EXISTING BUILDING CODE
 W/2006 REVISIONS
 2004 FLORIDA RESIDENTIAL BUILDING CODE W/ 2006
 REVISIONS
 CITY OF WEST PALM BEACH/ FLORIDA BUILDING CODE
 ADMINISTRATION AMENDMENTS, CHAPTER 1, 2004 EDITION
  
  
 COMMENTS:
  
  
 1) AS PER THE FEBC, SECTION 301.5 : A DESIGN
 PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE CLARIFY IF THERE WILL BE A NEW ROOF INSTALLED
 OR AN ISOLATED REPAIR.
  
 4) PLEASE NOTE THE PERCENTAGE OF SIDING TO BE
 REPAIRED/REPLACED.
  
 5) DRAWING A-3 SHOWS A NEW CONCRETE PIER; INDICATE
 DIMENSIONS / CONCRETE SPECIFICATIONS AND SOIL BEARING
 CAPACITY.
  
 6) SPECIFY SPECIES/GRADE OF LUMBER TO BE USED FOR
 REPAIR. DRAWINGS ARE NOT DETAILED: SHOW MECHANICAL
 CONNECTIONS/SPLICES ETC:
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 7) REQUIRE ENERGY CALCULATIONS AS PER THEFEBC,
 SECTION 512.1:
  
 512.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 8) REQUIREA SEPARATE ELECTRICAL PERMIT FOR
 REPAIR/REPLACEMENT OF THE ELECTRICAL SYSTEM.
  
 9) REQUIRE A TITLE BLOCK ON ALL PLANS:
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED
 481.203(6), 481.203(8), 481.2131(1),
 481.219(3),(4),(5), 481.221,
 481.225(1)(E),(G), 481.2251(1)(H) FS. HISTORY?
 NEW 9-7-00.
  
 10) THE SUBMITTED PLANS SHALL COMPLY WITH THE FOLLOWING
 FLORIDA STATUE:
  
 471.025SEALS.--
 (1)THE BOARD SHALL PRESCRIBE, BY RULE, ONE OR MORE
 FORMS OF SEAL TO BE USED BY LICENSEES. EACH LICENSEE
 SHALL OBTAIN AT LEAST ONE SEAL IN THE FORM APPROVED BY
 RULE OF THE BOARD AND MAY, IN ADDITION, REGISTER HIS OR
 HER SEAL ELECTRONICALLY IN ACCORDANCE WITH SS.
 668.001-668.006. ALL FINAL DRAWINGS, SPECIFICATIONS,
 PLANS, REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD AND ALL
 FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE OWNER'S
 REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE, DATED,
 AND SEALED WITH SAID SEAL. SUCH SIGNATURE, DATE, AND
 SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT TO
 WHICH THEY ARE AFFIXED. DRAWINGS, SPECIFICATIONS,
 PLANS, REPORTS, FINAL DOCUMENTS, OR DOCUMENTS PREPARED
 OR ISSUED BY A LICENSEE MAY BE TRANSMITTED
 ELECTRONICALLY AND MAY BE SIGNED BY THE LICENSEE,
 DATED, AND SEALED ELECTRONICALLY WITH SAID SEAL IN
 ACCORDANCE WITH SS. 668.001-668.006.
 (2)IT IS UNLAWFUL FOR ANY PERSON TO SEAL OR DIGITALLY
 SIGN ANY DOCUMENT WITH A SEAL OR DIGITAL SIGNATURE
 AFTER HIS OR HER LICENSE HAS EXPIRED OR BEEN REVOKED OR
 SUSPENDED, UNLESS SUCH LICENSE HAS BEEN REINSTATED OR
 REISSUED. WHEN AN ENGINEER'S LICENSE HAS BEEN REVOKED
 OR SUSPENDED BY THE BOARD, THE LICENSEE SHALL, WITHIN A
 PERIOD OF 30 DAYS AFTER THE REVOCATION OR SUSPENSION
 HAS BECOME EFFECTIVE, SURRENDER HIS OR HER SEAL TO THE
 EXECUTIVE DIRECTOR OF THE BOARD AND CONFIRM TO THE
 EXECUTIVE DIRECTOR THE CANCELLATION OF THE LICENSEE'S
 DIGITAL SIGNATURE IN ACCORDANCE WITH SS.
 668.001-668.006. IN THE EVENT THE ENGINEER'S LICENSE
 HAS BEEN SUSPENDED FOR A PERIOD OF TIME, HIS OR HER
 SEAL SHALL BE RETURNED TO HIM OR HER UPON EXPIRATION OF
 THE SUSPENSION PERIOD.
 (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED
 HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY
 PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR
 OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN.
 HISTORY.--SS. 12, 42, CH. 79-243; SS. 2, 3, CH. 81-318;
 SS. 14, 15, CH. 89-30; S. 4, CH. 91-429; S. 144, CH.
 92-149; S. 334, CH. 97-103; S. 4, CH. 97-241; S. 40,
 CH. 2000-356; S. 32, CH. 2000-372; S. 2, CH. 2001-63;
 S. 26, CH. 2002-299.
  
  
 11) PLEASE BE ADVISED THAT YOU MAY NOT SEAL DRAWINGS
 PREPARED BY OTHERS AS PER THE FOLLOWING FLORIDA
 STATUE:
  
 F.S. 471.033DISCIPLINARY PROCEEDINGS.--
  
 (J)AFFIXING OR PERMITTING TO BE AFFIXED HIS OR HER
 SEAL, NAME, OR DIGITAL SIGNATURE TO ANY FINAL DRAWINGS,
 SPECIFICATIONS, PLANS, REPORTS, OR DOCUMENTS THAT WERE
 NOT PREPARED BY HIM OR HER OR UNDER HIS OR HER
 RESPONSIBLE SUPERVISION, DIRECTION, OR CONTROL.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By kconrad Date 2007-07-05 Time 10:57 Rev Time 0.00
Received By kconrad Date 2007-07-05 Time 10:57 Sent To I
Notes
2007-07-05 10:58:53REQUIRE SIGNED AND SEALED STRUCTURAL REPAIR PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 10:36 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 10:36 Sent To B
Notes
2007-11-06 10:36:50TO "MISC" BOX#1--1ST REVIEW, PLANS WERE PRE-ISPECT.