Plan Review Details - Permit 07060013
Plan Review Stops For Permit 07060013
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-02 Cont ID  
Sent By amorse Date 2008-09-02 Time 14:20 Rev Time 0.00
Received By amorse Date 2008-09-02 Time 14:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-21 Cont ID  
Sent By amorse Date 2008-06-21 Time 06:56 Rev Time 0.00
Received By amorse Date 2008-06-21 Time 06:56 Sent To PC
Notes
2008-06-21 07:14:47 
  
 DENIED
  
 1)ONLY ONE COPY OF THE SOIL REPORT WAS SUBMITTED,
 PLEASE INCLUDE 2 COPIES OF ALL SUBMITTED MATERIALS WITH
 PERMIT APPLICATION
  
 2)OWNER/AGENT TO SIGN BOTH COPIES OF THE ENERGY
 CALC'S, PLEASENOTE HOWEVER THAT CORRECTIONS ARE
 REQUIRED TO THE SUMMER AND WINTER AS-BUILT
 CALCULATIONS. THE OVERHANG HEIGHT, POINT MULTIPLIERS,
 OVERHAND FACTORS AND TOTAL GLAZING AREA ARE NOT
 CORRECT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-06 Cont ID  
Sent By amorse Date 2007-12-06 Time 15:38 Rev Time 0.00
Received By amorse Date 2007-12-06 Time 15:38 Sent To PC
Notes
2007-12-06 15:39:48 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST
 REVIEW:
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 *****THE PERSONS RESPONSIBLE FOR THE DRAWINGS ARE
 REQUIRED TO REVIEW AND APPROVE PRODUCT APPROVALS FOR
 USE, (IN THIS CASE MR. WILLIAM YURASEK)*****
  
 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL
 *****ENERGY CALC'S SHALL MATCH VALUES DESIGNATED IN THE
 DRAWINGS, NEW PITCHED ROOF AREA ON DRAWINGS SHOW R30
 INSULATION BUT ENERGY CALC'S UNDER ATTIC IS R19, AREA
 OF EXISTING PORCH NOT ADDRESSED IN CALC'S, WOOD FRAME
 WALLS NOT ADDRESSED IN CALC'S, PLEASE NOTE THATWALLS
 WERE REVISED ON THE NEW DRAWING FROM 2X6 TO 2X4 BUT THE
 R-VALUE IS STILL R19 ON PAGE 2 CURTAIN WALL
 DETAIL******
  
 7)PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES ARE
 NOT ACCEPTABLE PER 471.025 F.S. PLEASE SEE THAT
 ENGINEERS SIGNATURE ON THE SOIL REPORT IS A PHOTOCOPY
 ALSO THE REPORT STATES THAT IT IS IN ACCORDANCE WITH
 THE 2001 FBC
 ******SIGNATURES HAVE NOT BEEN CHANGED TO
 ORIGINALS******
  
 10)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE
 BEING MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL
 OF ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 NEW COMMENT:
  
 1)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By amorse Date 2007-07-11 Time 13:44 Rev Time 0.00
Received By amorse Date 2007-07-11 Time 13:44 Sent To PC
Notes
2007-07-11 14:33:20 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE INFORMATION.
  
 NOTE: COUNTY STAMP STATES THAT NO ADDITIONAL SPACE, YET
 DRAWINGS AND PERMIT STATE THAT ADDITION IS BEING BUILT.
 COUNTY FEES ARE TO BE PAID FOR ADDITION OR PROVIDE A
 LETTER FROM COUNTY THAT NONE ARE REQUIRED FOR THE
 ADDITION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 3)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES. ALL
 CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 4)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 NOTE: THE COPIES THAT WERE SUBMITTED ARE NOT SIGNED BY
 THE OWNER/AGENT.
  
 7)PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES ARE
 NOT ACCEPTABLE PER 471.025 F.S. PLEASE SEE THAT
 ENGINEERS SIGNATURE ON THE SOIL REPORT IS A PHOTOCOPY
 ALSO THE REPORT STATES THAT IT IS IN ACCORDANCE WITH
 THE 2001 FBC
  
 8)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS
  
 9)PROVIDE THE COMPLETE WIND DESIGN DATA THAT APPLIES
 TO BUILDING PER 1603.1.4 FBC
  
 10)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE
 BEING MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL
 OF ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 11)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 12)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 13)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 14)PROVIDE MIN ROOF SHEATHING ATTACHMENT
 PER R803.2.3.1 FBC RES. 2006 AMENDMENTS SPECIFY 8D RING
 NAILS AT 6" O/C FIELD AND EDGE AND 4" O/C FIELD AND
 EDGE IN ZONE 2 & 3
  
 15)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004. PLEASE NOTE THAT ONLY ONE COPY OF
 DRAWING HAS BEEN SIGNED ANDNEITHER WAS DATED
  
 16)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES. WITH 30" CLEAR ABOVE
 OPENING
  
 17)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 18)SPECIFY PT WOOD PLATE AT LOCATIONS WHERE REQUIRED
 PER 319.1 FBC RES.
  
 19)DRAWINGS STATE FIXED WINDOWS IN ALL LOCATIONS AND
 THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 AWNING TYPE. ALSO THE DESIGN PRESSURE MAXIMUM IS -50
 PSF AND THE DESIGN LOADS GIVEN ARE -50.7 PSF IN ZONE 4
 AND -59.7 PSF IN ZONE 5
  
 20)DRAWINGS SHOW 4 NEW SLIDING GLASS DOORS AND NO SGD
 PRODUCT APPROVALS WERE SUBMITTED
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By btrobaug Date 2007-11-13 Time 14:45 Rev Time 0.00
Received By btrobaug Date 2007-11-13 Time 14:12 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 07:15 Rev Time 0.50
Received By btrobaug Date 2007-06-18 Time 06:57 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 07:59 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 07:59 Sent To M
Notes
2008-08-26 07:59:58TO "MECH" TOM G.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 15:54 Sent To M
Notes
2008-06-09 15:56:21TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 10:08 Sent To Z
Notes
2007-11-06 10:08:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 08:22 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 08:22 Sent To E
Notes
2007-06-07 08:24:28TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-11 Time   Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 10:18 Sent To  
Notes
2007-06-05 10:18:29TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 11:15 Rev Time 0.45
Received By tgordon Date 2008-08-26 Time 11:15 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-06-10 Cont ID  
Sent By tgordon Date 2008-06-10 Time 09:45 Rev Time 0.45
Received By tgordon Date 2008-06-10 Time 09:45 Sent To B
Notes
2008-06-10 09:55:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS ARE REQUIRING 21,025 TOTAL
 COOLING BTU'S, THE MECHANICAL PLANS ARE SHOWING 30,000
 TOTAL COOLING BTU'S. THE PLANS CAN ONLY CALL FOR 15%
 MORE TOTAL COOLING BTU'S THAN THE COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-6071..ABC.1.1.A 2.5 TON
 A/C SYSTEM IS TO LARGE FOR THE ADDITION, PER THE
 COOLING LOAD CALCULATIONS, PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) AS NOTED IN LAST REVIEW 11-13-07 NOTE #3. THE
 MECHANICAL PLANS ALSO NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 15:38 Rev Time 0.30
Received By tgordon Date 2007-11-13 Time 15:38 Sent To P
Notes
2007-11-13 15:50:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE A/C SYSTEM LISTED COULD NOT BE FOUND IN THE ARI
 DIRECTORY, PLEASE SUBMIT THE ARI LISTING FOR THE
 SYSTEM. SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J.
 CAL'S.), SEE 2004 FBC 13-607.1.ABC.1.
  
 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By tgordon Date 2007-06-18 Time 16:31 Rev Time 0.25
Received By tgordon Date 2007-06-18 Time 16:31 Sent To P
Notes
2007-06-18 16:37:47*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 2) PLANS SHOW A NEW A/C SYSTEM #2, PLEASE SUBMIT
 MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY OF WPB
 AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 07:59 Rev Time 0.00
Received By jleech Date 2007-12-03 Time 07:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-07-05 Cont ID  
Sent By jleech Date 2007-07-05 Time 07:34 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 07:34 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-09 Cont ID  
Sent By choops Date 2007-11-09 Time 14:43 Rev Time 0.00
Received By choops Date 2007-11-09 Time 14:43 Sent To E
Notes
2007-11-09 14:44:17***APPROVED - RESUB #1***
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By choops Date 2007-06-05 Time 16:10 Rev Time 0.00
Received By choops Date 2007-06-05 Time 16:10 Sent To I
Notes
2007-06-05 16:14:23***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF A CURRENT SURVEY,
 SHOWING THE SCOPE OF WORK WITH DIMENSIONS AND SETBACK
 DIMENSIONS FROM PROPOSED ADDITION TO PROPERTY LINES.
  
 2)PROVIDE ELEVATION DIMENSIONS FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S SLOPE.
  
 3)SHOW PROPOSED A/C EQUIPMENT ON SURVEY WITH SETBACK
 DIMENSION FROM OUTERMOST EDGE OF A/C EQUIPMENT TO
 PROPERTY LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720