Plan Review Details - Permit 07051187
Plan Review Stops For Permit 07051187
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By kconrad Date 2007-09-11 Time 17:14 Rev Time 0.00
Received By kconrad Date 2007-09-11 Time 3:45 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-11 Cont ID  
Sent By kconrad Date 2007-07-11 Time   Rev Time 0.00
Received By kconrad Date 2007-07-09 Time 18:58 Sent To I
Notes
2007-07-09 19:02:41PROJECT: 851 VILLAGE BLVD. #502
  
 PROJECT DETAIL: INTERIOR DEMOLITION
  
 REVIEW: 2004 FLORIDA EXISTING BUILDING CODE WITH 2006
 REVISIONS
  
 STATUS: DENIED
  
  
  
 COMMENTS:
  
 1)PLEASE CONTACT MR. ALEX ORTEGA OF THE DEP AT
 355.3023,EXT. 1148 PRIOR TO COMMENCING DEMOLITION. AN
 APPROVAL FROM THIS AGENCY MUST BE OBTAINED AS PER THE
 FOLLOWING CODE SECTION:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 2) REQUIRE SIGNED AND SEALED PLANS AS PER THE FOLLOWING
 REQUIREMENTS:
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 3) THE PROPOSED SCOPE OF WORK IF FOR DEMOLITION ONLY. A
 DEMOLITION AND REMODEL PLAN HAS BEEN SUBMITTED ON SHEET
 A1.0. PLEASE REVISE SCOPE OF WORK OR PROVIDE A FLOOR
 PLAN FOR DEMOLITION ONLY. IF THE INTENDED SCOPE OF WORK
 IS REVISED A COMPLETE SET OF PLANS MUST BE SUBMITTED.
  
 4) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 5) IF THERE ARE ANY QUESTIONS WITH REFERENCE TO THESE
 COMMENTS, PLEASE CONTACT ME PRIOR TO RE-SUBMITTING THE
 APPLICABLE PLANS.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By kconrad Date 2007-06-13 Time 20:03 Rev Time 0.00
Received By kconrad Date 2007-06-13 Time 20:03 Sent To I
Notes
2007-06-13 20:03:41REQUIRE DEMOLITION PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 17:35 Sent To  
Notes
2007-09-04 17:39:49** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THE EXACT COMMENTS FROM THE PREVIOUS
 REVIEW.
  
 1) NOTE: PLEASE SEE CODE REFERENCES ARE STILL NOT SHOWN
 ON THE PLANS.
 FBC 2004 W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE MISSING CERTIFICATE OF
 AUTHORIZATION/FIRM LICENSE NUMBER FOR ARCHITECTRUAL
 BUSINESS ON TITLE BLOCKS PER FAC 61G1-16.004 AND FS
 481.219.
 PLEASE SEE THE ATTACHED PRINT OUT FROM THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION WHICH SHOWS THE
 ADDRESS FOR THE ARCHITECT LISTED IN CINCINATTI, OHIO
 WHEREAS LANS INDICATE LEXINGTON, KY.
 PLEASE CLARIFY.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 07:10 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 07:01 Sent To  
Notes
2007-06-21 07:10:44*** UNSAT***
  
  
 1) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES
 AS ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED.
 SOME CODES STATED NEVER EXISTED.(2003 NEC)
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR THE ARCHITECT AND ARCHITECT FIRM. PLEASE SEE
 MISSING THE PRINTED NAMES FOR DESIGNERS.
 PLEASE SEE THE PRINTED LICENSE NUMBERS FOR DESIGNERS.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBERS FOR BOTH FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 FOR
 ARCHITECT AND FIRM..
 PLEASE SEE FLORIDA STATUTES 481.219 FOR ARCHITECT AND
 FIRM.
  
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE SHEETS ARE NOT SIGNED, DATED OR
 SEALED BY THE DESIGNER OF RECORD. PLEASE SEE FS
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By mwennerg Date 2007-09-19 Time 10:20 Rev Time 0.00
Received By mwennerg Date 2007-09-19 Time 10:20 Sent To  
Notes
2007-09-19 10:21:26***DENIED***
  
 PLEASE NOTE SAME COMMENTS FROM FIRST FIRE REVIEW:
 PLEASE ADDRESS COMMENTS.
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING
 REQUIREMENTS FOR PLANS.
  
 2) WILL ANY EXISTING BUILDING FIRE PROTECTION EQUIPMENT
 BE IMPACTED BY THIS WORK?
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) SITE SHALL BE CLEANED OF EXCESSIVE CONSTRUCTION
 DEBRIS DAILY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By mwennerg Date 2007-06-27 Time 12:34 Rev Time 0.00
Received By mwennerg Date 2007-06-27 Time 12:34 Sent To  
Notes
2007-06-27 12:39:35***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING
 REQUIREMENTS FOR PLANS.
  
 2) WILL ANY EXISTING BUILDING FIRE PROTECTION EQUIPMENT
 BE IMPACTED BY THIS WORK?
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) SITE SHALL BE CLEANED OF EXCESSIVE CONSTRUCTION
 DEBRIS DAILY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 15:23 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 15:23 Sent To  
Notes
2007-09-04 10:59:31TO "BOB"#5
2007-08-23 15:23:21WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By kconrad Date 2007-07-11 Time 16:54 Rev Time 0.00
Received By kconrad Date 2007-06-20 Time 13:33 Sent To I
Notes
2007-06-20 13:33:29TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-21 Cont ID  
Sent By tgordon Date 2007-06-21 Time 09:38 Rev Time 0.20
Received By tgordon Date 2007-06-21 Time 09:38 Sent To  
Notes
2007-06-21 09:38:56DEMO.

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 07:45 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 07:15 Sent To  
Notes
2007-09-15 07:47:13NO PLUMBING OR GAS DEMO WORK SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By jleech Date 2007-07-02 Time 07:33 Rev Time 0.00
Received By jleech Date 2007-07-02 Time 07:33 Sent To  
Notes
2007-07-02 07:52:09DENIED;
 1. NOT ENOUGH INFORMATION;
 A)WHAT EQUIPMENT, SANITARY PIPING,AND
 GAS PIPING IS TO BE REMOVED?
 B)IS THERE A GREASE TRAP, AND IF SO WILL
 IT BE RE-USED?
 2. ADD NOTES TO PLANS;
 1) ALL PLUMBING DEMO WORK TO BE DONE BY A
 LICENSED PLUMBING CONTRACTOR PERMIT AND INSPECTIONS
 REQUIRED.
 2) NO DEAD ENDS PERMITED IN THE SANITARY
 AND GREASY WASTE PIPING, SEE SECTION 704.5.
 3) ALL GAS PIPING NOT BEING USED MUST BE
 REMOVED BACK TO THE METER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By choops Date 2007-09-05 Time 10:45 Rev Time 0.00
Received By choops Date 2007-09-05 Time 10:45 Sent To  
Notes
2007-09-05 10:45:28*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.