Plan Review Details - Permit 07051183
Plan Review Stops For Permit 07051183
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-06 Cont ID  
Sent By lmartine Date 2009-01-06 Time 14:10 Rev Time 0.00
Received By lmartine Date 2009-01-06 Time 14:10 Sent To  
Notes
2009-01-06 14:13:47REVISION IS TO DELETE PORTIONS OF APPROVED PLANS FOR
 THE PURPOSE OF OCCUPYING THE DWELLING. DELETED SCOPE OF
 WORK WILL BE INCLUDED WITH #08110273.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-11-24 Cont ID  
Sent By rmcdouga Date 2008-11-24 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2008-11-24 Time 13:10 Sent To  
Notes
2008-11-24 10:35:25REVISED SHEETS A1 AND A2 ARE DENIED.
  
 1) THE DESIGNER OF RECORD FOR THE PERMITTED PROJECT
 PLANS IS ARCHITECT EMILIO JOSE AGRENOT. A DIFFERENT
 ARCHITECT, RAFAEL A. RODRIGUEZ SIGNED AND SEALED THE
 REVISED SHEETS. FS 481 REQUIRES ANY CHANGES TO THE
 APPROVED PLANS BE DONE BY THE DESIGNER OF RECORD.
  
 2) COMMENTS ON THE REVISION SUBMITTAL FORM STATE
 REMOVING MASTER BEDROOM AND BATH AND PATIO FROM THE
 PLANS AND APPLYING UNDER NEW PERMIT. THE REVISED PLANS
 INDICATE THAT THE EXISTING PORCH HAS BEEN ENCLOSED AND
 THE MASTER BATH AND BEDROOM HAS BEEN RECONFIGURED FROM
 THE EXISTING CONFIGURATION SHOWN ON THE APPROVED PLANS.
 PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-10-16 Cont ID  
Sent By amorse Date 2007-10-16 Time 16:37 Rev Time 0.00
Received By amorse Date 2007-10-16 Time 16:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-09-27 Cont ID  
Sent By amorse Date 2007-09-27 Time 16:06 Rev Time 0.00
Received By amorse Date 2007-09-27 Time 16:06 Sent To PC
Notes
2007-09-27 16:14:21 
  
 DENIED
  
 1)DESIGN CRITERIA ON S/3 AND STRUCTURAL CALCULATIONS
 FOR THE NANA DOOR SYSTEM DO NOT MATCH, CALC'S CANNOT BE
 LESS THAN WHAT THE DRAWINGS SPECIFY
  
 2)IF 140 MPH EXP "B" WHICH IS THE CORRECT DESIGNATION
 FOR THE CITY OF WEST PALM BEACH IS USED AS THE WIND
 DESIGN CRITERIA ALL PRODUCT APPROVALS WILL WORK
  
 3)PLEASE CORRECT PAGES A/3.0 AND A/3.1 MANY WINDOW
 MARKS AND MEASUREMENTS DO NOT MATCH WINDOW SCHEDULE
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-15 Cont ID  
Sent By amorse Date 2007-09-15 Time 09:15 Rev Time 0.00
Received By amorse Date 2007-09-15 Time 09:15 Sent To PC
Notes
2007-09-15 09:30:28 
  
 DENIED
  
 1)THE DESIGN PRESSURE ON THE DRAWING EXCEED THE
 MAXIMUM ALLOWABLE PRESSURES IN THE PRODUCT APPROVALS
 FOR THE NANA FOLDING DOORS (-55 PSF), THE FRENCH DOORS
 DEPENDING UPON GLASS TYPE (TYPE B -76 PSF), HORIZONTAL
 SLIDERS (-80 PSF), AND FIXED WINDOWS (-78 PSF).
 *****THESE COMMENTS WERE ADDRESSED ON 2ND REVIEWUNDER
 NEW COMMENTS 1, 2, AND 3.*****
  
 *****NOTE AS A SUGGESTION, THE CITY OF WEST PALM BEACH
 IN GENERAL AND IN THIS CASE IS IN A 140 MPH EXPOSURE
 "B" WIND ZONE, UNDER THESE PARAMETERS THE PRODUCT
 APPROVALS WOULD MEET DESIGN PRESSURE REQUIREMENTS*****
  
 2)UNDER LEVEL 2 ALTERATIONS THE MAIN FLOOR BATHROOM
 IS REQUIRED TO MEET THE ACCESSIBILITY REQUIREMENTS OF
 THE FBC 2004, AS SUCH PROVIDE AT MINIMUM 1 ACCESSIBLE
 BATHROOM PER R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90
 DEGREES
  
 3)PLEASE REMOVE ALL OLD SHEETS FROM RESUBMITTED
 PERMIT APPLICATION
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-13 Cont ID  
Sent By amorse Date 2007-08-13 Time 17:39 Rev Time 0.00
Received By amorse Date 2007-08-13 Time 17:39 Sent To PC
Notes
2007-08-13 18:22:57 
  
 DENIED 2ND REVIEW
  
 THE FOLLOWING REVIEW COMMENTS WERE NOT FULLY ADDRESSED
 ON THE FIRST REVIEW
  
 1)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/
 FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 ******NOTE PRODUCT APPROVALS WERE NOT SUBMITTED FOR THE
 MULLIONS THAT ARE REQUIRED AT THE GREAT ROOM FRONT
 WINDOWS OR THE FRONT ENTRY DOOR******
  
 3)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 ****** NOTE: THESE PRODUCT APPROVALS CAN BE FOUND AT
 THE ABOVE WEB SITE, THE FL#'SARE WRITTEN AT THE TOP
 OF THE MIAMI-DADE REPORTS. PLEASE SEE THAT THE
 MIAMI-DADE NOA'S ARE IN THE CERTIFYING AGENCY FOR THE
 STATE APPROVALS AND WILL ALSO NEED TO BE SUBMITTED WITH
 THE STATE COVER SHEETS******
  
 4)MANY KEY NOTES ON ARCHITECTURAL SHEETS DO NOT
 CORRESPOND WITH DRAWINGS PLEASE CLARIFY
  
 ******NOTE SEE ITEMS ON A/2.0, A/2.1 AND A/3.0 ALSO
 CHECK WINDOW SIZES VERSES SCHEDULE MARK, SEE 2ND FL.
 RIGHT ELEVATION ALL WINDOWS ARE THE SAME SIZE YET HAVE
 DIFFERENT MARKS******
  
 12)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID. PLEASE RERECORD AND SUBMIT PRIOR TO
 PERMIT BEING ISSUED.
  
 NEW COMMENTS
  
 1)NO DESIGN PRESSURES WERE GIVEN FOR THE FOLDING
 PANEL WALLS, PLEASE NOTE THE MAX. PRODUCT APPROVAL
 DESIGN PRESSURE IS -55 PSF.
  
 2)NO DESIGN PRESSURE WAS GIVEN FOR THE FIXED WINDOW,
 PLEASE NOTE THAT NOT ALL GLASS TYPES WILL MEET THE
 PRESSURES REQUIRED BY SCHEDULE ON S/3
  
 3)DESIGN PRESSURES IN THE FRENCH DOOR PRODUCT
 APPROVALS ONLY MEET SCHEDULE ON S/3 WITH TYPE "A"
 GLASS. THIS IS ALSO THE CASE WITHSOME WINDOWS AND
 OTHERS WILL NOT MEET THE PRESSURES IN SCHEDULE AT ALL
 FOR EXAMPLE TYPES B,C AND E IN ZONE 5 AND TYPE G IN
 ZONE 4.
  
 4)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
 IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE. NEW PAGES TO BE RESTAMPED BY
 HISTORIC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-07 Cont ID  
Sent By amorse Date 2007-07-07 Time 08:34 Rev Time 0.00
Received By amorse Date 2007-07-07 Time 08:34 Sent To PC
Notes
2007-07-07 09:05:35 
  
 DENIED
  
 1)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/
 FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 2)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 3)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 NOTE: THE FOLLOWING PRODUCT APPROVALS ARE REQUIRED
 EXTERIOR DOORS, WINDOWS, MULLIONS AND THE DOOR/WINDOW
 SYSTEM THAT WILL BE USED AT THE REAR OF NEW DINING
 ROOM.
  
 4)MANY KEY NOTES ON ARCHITECTURAL SHEETS DO NOT
 CORRESPOND WITH DRAWINGS PLEASE CLARIFY
  
 5)ADD TEMPERED GLAZING TO NOTE #8 ON SHEET A-3.1
  
 6)WINDOW MARKS ON SHEET A-3.0 ARE NOT IN AREA OF
 WINDOWS
  
 7)NEW FLOOR PLAN ON A-3.0AT SECTION B/A-5.0 SHOWS 3
 STEPS WHILE THE SECTION AND THE STRUCTURAL SHEETS SHOW
 4 STEPS PLEASE MAKE CORRECTION. ALSO THE SECTION ON
 A-5.0 IS MISLABELED
  
 8)TWO DIFFERENT SECTIONS ON SHEET S-1 ARE BOTH
 LABELED 3/S-1 PLEASE CORRECT
  
 9)NOTE ON S-1 FOR THE TIE IN OF FOUNDATION AND TIE
 BEAM IS INCORRECT (NO SHEET S-6)
  
 10)ELEVATION VIEW OF EXISTING TIE BEAM ON S-2
 INCORRECT (NO SHEET S-5)
  
 11)COLUMN INFORMATION FOR MARK TC NOT PROVIDED IN THE
 COLUMN SCHEDULE ONSHEET S-4
  
 12)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS
 VOID. PLEASE RERECORD NOC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 08:04 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 07:28 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-02 Cont ID  
Sent By btrobaug Date 2007-08-02 Time 17:25 Rev Time 0.00
Received By btrobaug Date 2007-07-31 Time 17:05 Sent To M
Notes
2007-08-02 17:25:38 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHEET E-2.0, PROVIDE CONDUCTOR AND CONDUIT SIZE AND
 TYPE FOR THE SERVICE RISER ON THE RISER DIAGRAM. ALSO
 THE WORD "EXISTING" STILL APPEARS FOR THAT RISER.
  
 2} SHEET E-2.0, PANEL "B" ON THE RISER IS MCB, ON THE
 SCHEDULE IT'S MLO. CLARIFY.
  
 3} SHEET E-2.0, THE FEEDER FOR PANEL "A" IS 1/0 ON THE
 RISER, LISTED AS 2/0 IN PANEL "B" SCHEDULE. NOTE 1/0 IS
 SUFFICIENT.
  
 4} SHEET E-1.0 THE DOORWAY BETWEEN THE OFFICE AND
 KITCHEN BEING CLOSED OFF REQUIRES A RECEPTACLE TO BE
 ADDED FOR COUNTERTOP SPACING, 210.52(C)(1).
  
 5} THE COUNTER NEXT TO THE RELOCATED REFRIGERATOR
 (KITCHEN) REQUIRES A RECEPTACLE, 210.51(C)(1).
  
 6} A RECEPTACLE IS REQUIRED AT BOTH SIDES OF THE RANGE
 IN THE ISLAND PER 210.52(C)(2).
  
 7} ALL COUNTERTOP RECEPTACLES IN THE KITCHEN MUST BE
 GFCI PROTECTED, 210.8(A)(6).
  
 8} THE JUCUZZI MUST BE GFCI PROTECTED PER
 680.43(A)(3).
  
 THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE LEVEL
 OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THE EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. MAKE A NOTE ON THE PLAN FOR FIELD
 CLARIFICATION
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By btrobaug Date 2007-06-21 Time 17:37 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 08:28 Sent To M
Notes
2007-06-21 17:37:38 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE
 LEVEL OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND
 305 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME
 ON THE PLAN.
  
 2} THERE ARE CONFLICTING NOTES ON THE RISER DIAGRAM,
 SHEET E-2.0. EXISTING STATED FOR THE RISER, AND
 "NEW"FEEDER AND METER, WHICH ALSO APPEARS TO BE A
 METER/MAIN COMBINATION. IF NEW PER 110.9 AND 110.10:
 OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.SHEET E-1.0 ALSO INDICATES
 EXISTING. PLEASE CORRELATE.
  
 3} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE
 SAME ON THE PLANS TO SHOW COMPLIANCE.
  
 5} THE NEW WHIRLPOOL AND JACUZZI NOTED ON SHEET A-3.1
 DO NOT APPEAR IN THE PANEL SCHEDULE.
  
 6} NOTES #12 & 13 ON SHEET A-2.2 AND NOTE #26 ON SHEET
 A-4.0 REGARDING THE SERVICE CONDUCTORS , ARE
 CONFLICTING. SEE COMMENT #2.
 NOTE: IT APPEARS THAT THE NOTES ON SHEETS A-2.2 AND
 A-4.0, ARE REGARDING THE OTHERS SHEET.
  
 7} NOTE #5, SHEET E-1.0 REGARDING THE BRANCH CIRCUIT
 FOR THE DINING ROOM RECEPTACLE WOULD VIOLATE
 210.52(B)(1) AND (2), SMALL APPLIANCE WITH NO OTHER
 OUTLETS..
  
 NOTE THE RECESS FIXTURES MUST COMPLY WITH ARTICLE
 13-606.1ABC 1.2.4, FBC.
  
 THERE MAY BE ADDITIONAL COMMENTS DEPENDING ONTHE
 LEVEL OF ALTERATION THAT IS DECLARED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-09-12 Cont ID  
Sent By mperson Date 2007-09-12 Time 11:30 Rev Time 0.00
Received By mperson Date 2007-09-12 Time 11:30 Sent To B
Notes
2007-09-12 11:34:30****************PROVISO****************
 THE CORRECT LONGEST LENGTH OF THE GAS SYSTEM IS 57' NOT
 THE INDICATED 55'. GAS SYSTEM IS SIZED CORRECT.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-08-09 Cont ID  
Sent By mperson Date 2007-08-09 Time 09:51 Rev Time 0.45
Received By mperson Date 2007-08-09 Time 09:53 Sent To B
Notes
2007-08-09 10:52:01DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **NO**SHEET P-2.0 THE RESUBMITTED GAS ISOMETRIC
 INDICATING THE SLEEVE IS NOT COMPLIANT PER FBC-2004
 FUEL GAS , SECTION 404.11 PIPING UNDERGROUND BENEATH
 BUILDINGS IS PROHIBITED EXCEPT WHERE THE PIPING IS
 ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC PIPE OR
 STEEL PIPE DESIGNED TO WITHSTAND THE SUPERIMPOSED
 LOADS. SUCH CONDUIT SHALL EXTEND INTO AN OCCUPIABLE
 PORTION OF THE BUILDING AND, AT THE POINT WHERE THE
 CONDUIT TERMINATES IN THE BUILDING, THE SPACE BETWEEN
 THE CONDUIT AND THE GAS PIPING SHALL BE SEALED TO
 PREVENT THE POSSIBLE ENTRANCE OF ANY GAS LEAKAGE.WHERE
 THE END SEALING IS CAPABLE OF WITHSTANDING THE FULL
 PRESSURE OF THE GAS PIPE, THE CONDUIT SHALL BE DESIGNED
 FOR THE SAME PRESSURE AS THE PIPE. SUCH CONDUIT SHALL
 EXTEND NOT LESS THAN 4 INCHES (102 MM) OUTSIDE THE
 BUILDING, SHALL BE VENTED ABOVE GRADE TO THE OUTDOORS,
 AND SHALL BE INSTALLED SO AS TO PREVENT THE ENTRANCE OF
 WATER AND INSECTS. THE CONDUIT SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 404.8.
 **PLEASE REFERENCE THE DETAIL ATTACHED TO THE GAS
 COMMENTS AND PLEASE HAVE SHEETS P-1.0 NOTE #4 AND SHEET
 P-2.0 GAS ISOMETRIC REFLECT THIS DETAIL ON THE
 RESUBMITTAL.
  
 3. **NO** SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE CORRESPONDING LENGTHS ARE NOT BEING INDICATED
 FOR ALL CUT SECTIONS OF PIPE ON SHEET P-2.0 GAS
 ISOMETRIC.
  
 4. **NO** SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS CAN NOT BE VERIFIED UNTIL GAS COMMENT #3 HAS
 BEEN ADDRESSED.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 5. SHEET P-2.0 GAS ISOMETRIC: THE FBC GAS SIZING TABLE
 402.4(1) IS WRONG, THE CORRECT SIZING TABLE IS 402.4(2)
 PLEASE CORRECT THIS ON THE RESUB.
  
 6. PLEASE ADD THE FOLLOWING TO THE GAS NOTES ON SHEET
 P-2.0:
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION. METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE
 PROTECTED IN AN APPROVED MATTER.
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPINGS SHALL BE APPROVED FOR THE
 APPLICATION AND SHALL BE FACTORY APPLIED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mperson Date 2007-06-26 Time 15:56 Rev Time 0.45
Received By mperson Date 2007-06-26 Time 15:55 Sent To B
Notes
2007-06-26 16:42:38DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.SHEET P-2.0 NATURAL GAS ISOMETRIC DOES NOT REFLECT
 THE FLOOR PLAN NATURAL GAS ON SHEET P-1.0, THE FLOOR
 PAN ON THAT SHEET INDICATES THE GAS METER AT ONE END
 WITH THE RANGE AND WATER HEATER AT THE OTHER. NOTE: THE
 ISOMETRIC ON SHEET P-2.0 IS INDICATING THE GAS METER
 BETWEEN THE TWO APPLIANCES. PLEASE CORRELATE THE TWO
 SHEETS ON THE RESUBMITTAL.
  
 2. SHEET P-1.0 DRAWING NOTES #4 IS INDICATING FOR THE
 NEW RANGE, A NEW GAS LINE UNDER SLAB IN 4" SCH. 40 PVC
 CONDUIT WITH LONG SWEEP ELLS. THE GAS ISOMETRIC ON
 SHEET P-2.0 IS NOT REFLECTING THIS. PLEASE INDICATE THE
 SLEEVE ON THE RESUBMITTED GAS ISOMETRIC AND PLEASE
 PROVIDE A DETAIL OF THE SLEEVE COMPLIANT WITH FBC-2004
 FUEL GAS SECTION 404.11 PIPING UNDERGROUND BENEATH
 BUILDINGS, WITH THE PIPING MATERIAL OF SCHEDULE 40
 BLACK STEEL BEING USED AS INDICATED ON SHEET P-2.0.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: CORRESPONDING LENGTHS ARE NOT BEING INDICATED FOR
 ALL CUT SECTIONS OF PIPE ON SHEET P-2.0.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THERE ARE TWO INDICATIONS OF PIPE LENGTHS BEING
 INDICATED ON SHEET P-2.0, ONE IS 30' OF 1" PIPE AND THE
 OTHER IS 100' OF 3/4" PIPE. UNTIL COMMENT #3 IS
 ADDRESSED THIS COMMENT CAN NOT BE VERIFIED. THE 100' OF
 3/4" PIPE TO THE NEW RANGE CAN'T BE RIGHT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-05-31 Cont ID  
Sent By swurafti Date 2007-05-31 Time 15:58 Rev Time 0.00
Received By swurafti Date 2007-05-31 Time 15:58 Sent To  
Notes
2007-05-31 15:59:11HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-12-12 Cont ID  
Sent By adarroug Date 2008-12-12 Time 10:33 Rev Time 0.00
Received By adarroug Date 2008-12-12 Time 10:33 Sent To M
Notes
2008-12-12 10:33:39TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-11-21 Cont ID  
Sent By adarroug Date 2008-11-21 Time 09:58 Rev Time 0.00
Received By adarroug Date 2008-11-21 Time 09:58 Sent To B
Notes
2008-11-21 09:58:27TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 14:39 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 14:39 Sent To Z
Notes
2008-11-12 14:39:23TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 09:59 Sent To B
Notes
2007-10-11 10:00:06TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 10:01 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 10:01 Sent To B
Notes
2007-09-24 10:02:11TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 16:27 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 16:27 Sent To Z
Notes
2007-08-31 16:31:35TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 13:30 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 13:30 Sent To Z
Notes
2007-07-27 13:30:48TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 09:55 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 09:55 Sent To E
Notes
2007-06-05 09:55:21TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-07 Time   Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 10:27 Sent To  
Notes
2007-06-04 10:27:43TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-01-09 Cont ID  
Sent By hmoser Date 2009-01-09 Time 14:25 Rev Time 0.00
Received By hmoser Date 2009-01-09 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 14:51 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 14:49 Sent To B
Notes
2008-12-14 14:51:30MECH REVISION SUBMITTED SEPATARELY TO BE REVIEWED WITH
 BUILDING PERMIT REVISION SUBMITTED 11/10/08. ROUTED TO
 LM DESK WITH MAIN SUBMITTED REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By tgordon Date 2007-09-11 Time 10:55 Rev Time 0.20
Received By tgordon Date 2007-09-11 Time 10:55 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-06 Cont ID  
Sent By tgordon Date 2007-08-06 Time 14:03 Rev Time 0.30
Received By tgordon Date 2007-08-06 Time 14:03 Sent To P
Notes
2007-08-06 14:09:38*** PROVISO ***
 1) THE CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By tgordon Date 2007-06-22 Time 08:53 Rev Time 0.45
Received By tgordon Date 2007-06-22 Time 08:53 Sent To P
Notes
2007-06-22 08:58:19*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600-04 R
 (SOUTH 7 8 9) SEE 2004 FBC 13-600.3.C, PLEASE CORRECT.
  
 2) THE CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-12 Cont ID  
Sent By mperson Date 2007-09-12 Time 11:29 Rev Time 0.00
Received By mperson Date 2007-09-12 Time 11:29 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-09 Cont ID  
Sent By mperson Date 2007-08-09 Time 08:58 Rev Time 0.45
Received By mperson Date 2007-08-09 Time 08:58 Sent To G
Notes
2007-08-09 09:48:55DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. SHEET P-1.0 SANITARY PIPING ISOMETRIC:
 A} **OK**
 B} **OK**
 C} **NO/OK**PER FBC-2004 PLUMBING SECTION 708.9
 ACCESS, PLEASE INDICATE THE CLEANOUT FOR THE WASHING
 MACHINE AT 4' AFF.
 ** THE CORRECTED WASHING MACHINE ISOMETRIC IS WRONG THE
 DRAIN STACK SHALL BE 3"AND THE FIXTURE DRAIN SHALL BE
 2" PER FBC-2004 PLUMBING SECTION 406.3 AND THE CLEANOUT
 SHALL BE 3" PER FBC-2004 PLUMBING SECTION 708.7 AND BE
 LOCATED AT 4' AFF PER FBC-2004 PLUMBING SECTION 708.9
 AND THE CLEANOUT SHALL BE LOCATED ABOVE THE FIXTURE
 DRAIN.
 D} **OK**
  
 THE FOLLOWING ARE NEW ITEMS:
  
 3. SHEET A-2.1 2ND FLOOR DEMOLITION PLAN: THE EXISTING
 BATH TUB SHOULD BE #17 NOT #19 PER THE DEMOLITION KEY
 NOTES.
  
 4. SHEET P-1.O SANITARY PIPING ISOMETRIC: PLEASE
 CORRECT THE WORDING FOR THE NOTE ON SLOPE TO THE
 FOLLOWING PER TABLE 704.1. "SLOPE ALL PIPING 2-1/2" AND
 LESS @ 1/4" PER FT. AND SLOPE ALL PIPING 3" TO 6" @
 1/8" PER FT.".
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mperson Date 2007-06-26 Time 15:18 Rev Time 0.55
Received By mperson Date 2007-06-26 Time 15:18 Sent To G
Notes
2007-06-26 15:55:24DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A-3.0: THE FOLLOWING NEW KEY NOTES ARE NOT
 BEING INDICATED ON THE NEW WORK FIRST FLOOR PLAN.
 A} #8 EXISTING SHOWER AND SHOWER DOOR TO REMAIN.
 B} #23 NEW GAS SERVICE AT FLOOR FOR NEW GAS RANGE.
  
 2. SHEET P-1.0 SANITARY PIPING ISOMETRIC: PLEASE
 CORRECT THE FOLLOWING.
 A}MASTER BATH: THE LAV BY THE JACUZZI IS NOT
 VENTED. THE TRAP IS MORE THAN EIGHT FEET (8') FROM THE
 VENT. PER FBC-2004 PLUMBING TABLE 906.1, A2" FIXTURE
 DRAIN WITH AN 1-1/2" TRAP CAN ONLY BE 6' FROM THE VENT.
 AN AIR ADMITTANCE VALVE IS SUGGESTED PER FBC-2004
 PLUMBING SECTION 917.3.
 B} PLEASE CLEARLY INDICATE WHAT "WSB" IS ON THE
 RESUBMITTAL. IS THIS THE WASHING MACHINE SUPPLY BOX?
 C} PER FBC-2004 PLUMBING SECTION, 708.9 ACCESS, PLEASE
 INDICATE THE CLEANOUT FOR THE WASHING MACHINE AT 4'
 A.F.F.
 D} PER FBC-2004 PLUMBING, SECTION 406.3 PLEASE
 INDICATE THE SIZE FOR THE WASHING MACHINE TRAP AND
 STANDPIPE TO BE 2".
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 4 Status P Date 2008-11-20 Cont ID  
Sent By adavila Date 2008-11-20 Time 13:42 Rev Time 0.00
Received By adavila Date 2008-11-19 Time 17:01 Sent To I
Notes
2008-11-20 13:43:21PLANNING AND ZONING DEPARTMENT
  
 ***PASSED***
  
 *** PLEASE NOTE THAT DUE TO THE CHANGE IN THE SCOPE OF
 WORK AS INDICATED IN THIS REVISION, RENOVATIONS OF THE
 EXISTING DINING AREA, AND MASTER BEDROOM AND BATHROOM,
 SHALL BE REVIEWED AND APPROVED ON A SEPARATE PERMIT.***
  
 *** PLEASE NOTE THAT IF THE WORK VALUE OF THIS PERMIT
 WITH THE WORK VALUE FOR THE RENOVATION OF THE EXISTING
 DINING AREA, AND MASTER BEDROOM AND BATHROOM EVER
 EXCEED 50 PERCENT OF THE VALUE OF THE STRUCTURE (EXCEED
 $308,842.5), THE SUBJECT PROPERTY SHALL BE BROUGHT INTO
 COMPLIANCE WITH ARTICLE XIV, LANDSCAPING, LAND CLEAR
 AND TREE PROTECTION, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).***
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-05 Cont ID  
Sent By choops Date 2007-09-05 Time 12:23 Rev Time 0.00
Received By choops Date 2007-09-05 Time 12:23 Sent To E
Notes
2007-09-05 12:25:29***APPROVED******RESUB #2***
  
 PROVISO:A/C EQUIPMENT MUST BE SETBACK A MINIMUM OF 1'
 TO THE WEST SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-30 Cont ID  
Sent By choops Date 2007-07-30 Time 11:20 Rev Time 0.00
Received By choops Date 2007-07-30 Time 11:20 Sent To E
Notes
2007-07-30 11:29:05***FAILED***
  
  
 1)AS THE DRIVEWAY MATERIAL CHANGES, SO DOES THE
 ALLOWABLE SQUARE FOOTAGE WITHIN THE FRONT YARD.PLEASE
 PROVIDE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES
 WITHIN THE FRONT YARD (FRONT 29'11" FROM THE FRONT
 PROPERTY LINE)
  
 2)NEW PLANS TO BE APPROVED AND RESTAMPED BY HISTORIC
 PRESERVATION.OLD PLANS STAMPED BY HISTORIC NOT TO BE
 INCLUDED WITH NEW PACKET, ONLY ONE SET OF OLD PLANS TO
 BE SUBMITTED FOR REFERENCE.REMOVE EXCESS PLANS FROM
 PACKETS.
  
 3)SHOW ALL MECHANICAL EQUIPMENT BEING PROPOSED ON
 SITE PLAN (WINE COMPRESSOR) INCLUDE SETBACK DIMENSIONS
 TO ALL MECHANICAL EQUIPMENT FROM PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By choops Date 2007-06-05 Time 09:18 Rev Time 0.00
Received By choops Date 2007-06-05 Time 09:17 Sent To I
Notes
2007-06-05 09:23:28***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF AN ACTUAL, CURRENT
 SURVEY; SHOWING THE SCOPE OF WORK WITH DIMENSIONS AND
 SETBACK DIMENSIONS.
  
 2)SHOW SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO PROPERTY LINES ON SURVEYS AND SITEPLANS.
  
 3)INDICATE WHAT DRIVEWAY UPGRADES ARE TAKING PLACE,
 INCLUDE DIMENSIONS.
  
 4)IF POND IS INCLUDED, PLEASE ADD TO SCOPE OF WORK
 AND PROVIDE SETBACK DIMENSIONS TO PROPERTY LINES ON
 SURVEYS.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720