Plan Review Details - Permit 07051171
Plan Review Stops For Permit 07051171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-15 Cont ID  
Sent By amorse Date 2008-01-15 Time 16:41 Rev Time 0.00
Received By amorse Date 2008-01-15 Time 16:41 Sent To PC
Notes
2008-01-15 16:53:59 
  
 PASSED
  
 FEES ARE DUE IN THE AMOUNT OF $ 120.60 FOR INCREASED
 VALUE ON PERMIT
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-04 Cont ID  
Sent By amorse Date 2007-07-04 Time 06:55 Rev Time 0.00
Received By amorse Date 2007-07-04 Time 06:55 Sent To PC
Notes
2007-07-04 07:18:13 
  
 DENIED
  
 1)PER FLORIDA STATUTE 481.229 EXEMPTION FROM
 ARCHITECTURAL LICENSURE DOE NOT EXEMPT THE PERSONS
 RESPONSIBLE FROM PRINTING THEIR NAME AND SIGNING AND
 DATING THE DRAWINGS
  
 2)PROVIDE A COMPLETE SCOPE OF WORK ON THE DRAWINGS
 ALL WORK THAT WILL BE PERFORMED MUST BE IN THE SCOPE AS
 WORK OUTSIDE OF SCOPE CAN CAUSE INSPECTION FAILURE AND
 CONSTRUCTION DELAYS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 INCLUDING LABOR (OWNER BUILDER IS NOT EXEMPT) EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*. IF VALUE IS NOT CORRECTED IT WILL BE
 ADJUSTED IN THE NEXT PLAN REVIEW
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM.ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG PROVIDE PRODUCT
 APPROVALS FOR THE TRUSS CLIPS AND ANY OTHER TIES OR
 STRAPS TO BE USED.
  
 5)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 06:51 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 06:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-02 Cont ID  
Sent By btrobaug Date 2008-01-02 Time 08:10 Rev Time 0.00
Received By btrobaug Date 2008-01-02 Time 07:33 Sent To B
Notes
2008-01-02 08:10:10 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS HAVE NOT BEEN ADDRESSED FROM THE
 PREVIOUS REVIEW:
  
 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15
 AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE
 PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND
 CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE
 680.43 FOR LOCATION AND PROTECTION (GFI).
 * ALSO THE PANEL INDICATES A 2 POLE 30 AMP BREAKER.
 CORRELATE AND CORRECT THE LOAD CALCULATIONS TO REFLECT
 THE NAMEPLATE RATING.
  
 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES
 NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS.*THE
 DISCONNECT LOCATION STILL DOES NOT HAVE THE REQUIRED
 CLEARANCES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By btrobaug Date 2007-06-12 Time 10:18 Rev Time 0.50
Received By btrobaug Date 2007-06-12 Time 09:34 Sent To B
Notes
2007-06-12 10:18:04 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THE PANEL SCHEDULE NOTE "PROVIDE 200 AMP SERVICE" IS
 IN CONFLICT WITH THE RISER, WHICH INDICATES AN EXISTING
 150 AMP, AND NOTE AT THELOCATION ON THE PLAN ALSO
 INDICATES 150 AMP. PLEASE CLARIFY.
  
 2} CIRCUIT 14,16 FOR THE DISHWASHER/DISPOSAL INDICATE
 TWO DIFFERENT AMPERAGES FOR THE OCP.
  
 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15
 AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE
 PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND
 CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE
 680.43 FOR LOCATION AND PROTECTION (GFI).
  
 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES
 NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS.
  
 5} RECEPTACLES MUST BE ADDED IN THE "ENTRY", BEDROOM
 AND KITCHEN TO COMPLY WITH 221.52(A)(1) & (2). SEE
 REVIEWED SET OF PLANS FOR APPROXIMATE LOCATIONS.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 15:36 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 15:36 Sent To E
Notes
2007-12-27 15:36:25TO BILL TROBAUGHS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-04 Time   Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 15:57 Sent To  
Notes
2007-06-01 15:57:48TO "E" BOX

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***