Plan Review Details - Permit 07051171
| Plan Review Stops For Permit 07051171 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-01-15 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-01-15 |
Time |
16:41 |
Sent To |
PC |
|
| Notes |
| 2008-01-15 16:53:59 | | | | | | | PASSED | | | | | | FEES ARE DUE IN THE AMOUNT OF $ 120.60 FOR INCREASED | | | VALUE ON PERMIT | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-04 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-07-04 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-07-04 |
Time |
06:55 |
Sent To |
PC |
|
| Notes |
| 2007-07-04 07:18:13 | | | | | | | DENIED | | | | | | 1)PER FLORIDA STATUTE 481.229 EXEMPTION FROM | | | ARCHITECTURAL LICENSURE DOE NOT EXEMPT THE PERSONS | | | RESPONSIBLE FROM PRINTING THEIR NAME AND SIGNING AND | | | DATING THE DRAWINGS | | | | | | 2)PROVIDE A COMPLETE SCOPE OF WORK ON THE DRAWINGS | | | ALL WORK THAT WILL BE PERFORMED MUST BE IN THE SCOPE AS | | | WORK OUTSIDE OF SCOPE CAN CAUSE INSPECTION FAILURE AND | | | CONSTRUCTION DELAYS | | | | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | INCLUDING LABOR (OWNER BUILDER IS NOT EXEMPT) EXCLUDING | | | LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD), | | | MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER | | | 108.3 FBC*. IF VALUE IS NOT CORRECTED IT WILL BE | | | ADJUSTED IN THE NEXT PLAN REVIEW | | | | | | 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE | | | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES, | | | AND THE PRODUCT NOA THAT LISTS THE SYSTEM.ALL CAN BE | | | FOUND ON WWW.FLORIDABUILDING.ORG PROVIDE PRODUCT | | | APPROVALS FOR THE TRUSS CLIPS AND ANY OTHER TIES OR | | | STRAPS TO BE USED. | | | | | | 5)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-23 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-23 |
Time |
06:33 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-01-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-02 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-02 |
Time |
07:33 |
Sent To |
B |
|
| Notes |
| 2008-01-02 08:10:10 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THESE COMMENTS HAVE NOT BEEN ADDRESSED FROM THE | | | PREVIOUS REVIEW: | | | | | | 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15 | | | AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE | | | PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND | | | CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE | | | 680.43 FOR LOCATION AND PROTECTION (GFI). | | | * ALSO THE PANEL INDICATES A 2 POLE 30 AMP BREAKER. | | | CORRELATE AND CORRECT THE LOAD CALCULATIONS TO REFLECT | | | THE NAMEPLATE RATING. | | | | | | 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES | | | NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS.*THE | | | DISCONNECT LOCATION STILL DOES NOT HAVE THE REQUIRED | | | CLEARANCES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-12 |
Time |
10:18 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-06-12 |
Time |
09:34 |
Sent To |
B |
|
| Notes |
| 2007-06-12 10:18:04 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} THE PANEL SCHEDULE NOTE "PROVIDE 200 AMP SERVICE" IS | | | IN CONFLICT WITH THE RISER, WHICH INDICATES AN EXISTING | | | 150 AMP, AND NOTE AT THELOCATION ON THE PLAN ALSO | | | INDICATES 150 AMP. PLEASE CLARIFY. | | | | | | 2} CIRCUIT 14,16 FOR THE DISHWASHER/DISPOSAL INDICATE | | | TWO DIFFERENT AMPERAGES FOR THE OCP. | | | | | | 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15 | | | AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE | | | PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND | | | CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE | | | 680.43 FOR LOCATION AND PROTECTION (GFI). | | | | | | 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES | | | NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. | | | | | | 5} RECEPTACLES MUST BE ADDED IN THE "ENTRY", BEDROOM | | | AND KITCHEN TO COMPLY WITH 221.52(A)(1) & (2). SEE | | | REVIEWED SET OF PLANS FOR APPROXIMATE LOCATIONS. | | | | | | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-12-27 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-12-27 |
Time |
15:36 |
Sent To |
E |
|
| Notes |
| 2007-12-27 15:36:25 | TO BILL TROBAUGHS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-07-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-01 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2007-06-01 15:57:48 | TO "E" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|