Plan Review Details - Permit 07051157
Plan Review Stops For Permit 07051157
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-10 Cont ID  
Sent By lmartine Date 2007-12-10 Time 17:23 Rev Time 0.00
Received By lmartine Date 2007-12-10 Time 17:23 Sent To  
Notes
2007-12-10 17:24:44REVSION #6 AND #7 APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By jjohnsto Date 2007-10-22 Time 13:09 Rev Time 2.00
Received By jjohnsto Date 2007-10-22 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By jjohnsto Date 2007-08-27 Time 12:00 Rev Time 1.00
Received By jjohnsto Date 2007-08-27 Time 11:00 Sent To PC
Notes
2007-08-27 12:03:45CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
  
  
 PERMIT NO. 07051157
 PROJECT NAME IRON MOUNTAIN
 ADDRESS 3501 ELECTRONICS WAY
 CONTRACTOR: EDWARDS CONSTRUCTION SERVICES, INC.
  DATE: AUGUST27,2007
 PLANREVIEW2NDREVIEW
  
 JAMES JOHNSTON CBO
 BUILDING PLANS EXAMINER LL
 TEL:561-805-6713FAX:
 561-805-6731
 [email protected]
  
  
  
 (3) SURVEYS(2) REQUIRED NOT SUBMITTED AS STATED ON
 RESPONSE SHEET
  
  
 (7) IMPACT FEES MUST BE PAID, PLANS STAMPED AND RECEIPT
 ATTACHED TO PERMIT APPLICATION.PLEASE CALL
 561-233-5025 FOR FURTHER INFORMATION
  
  
 (10) SUBMIT(2) COPIES OF THE SOIL TEST REPORT SIGNED
 AND SEALED WITH RECCOMENDATIONS FOR SOIL REMOVAL AND
 COMPACTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By jwitmer Date 2007-08-27 Time 12:00 Rev Time 0.00
Received By jjohnsto Date 2007-08-27 Time 11:34 Sent To  
Notes
2007-08-27 11:55:07 
  
2007-06-22 10:47:03 
  
  
  
 IRON MOUNTAIN- FOUNDATION ONLY
  
 BUILDING PLAN REVIEW
 PERMIT: 07051157
 ADD: 3501 ELECTRONIC WAY
 CONT: EDWARDS CONSTRUCTION SERVICES
 TEL: (352)854-6266
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE TAKE NOTE OF SURVEY FROM GT SURVEYING HAS A
 RAISED SEAL BUT A PHOTO-COPIED SIGNATURE. SEE FLORIDA
 ADMINISTRATIVE CODE 61G17 AND FL S S 472.025 ABOUT
 ORIGINAL SIGNATURES.
  
 4) PLEASE TAKE NOTE THAT ARCHITECTURAL ALLIANCE, INC.
 LOST THEIR CERTIFICATE OF AUTHORIZATION 2-28-2001. SEE
 ATTACHMENT FROM THE DPBR WEBSITE.
  
 5) CS-1 PLAN REVIEW DATA INDICATES THE PLAN WAS
 DESIGNED TO THE 2004 FBC PLEASE SEE PLAN AS SUBMITTED
 AFTER DEC.8TH, 2006 ARE TO BE REVIEWED UNDER THE 2006
 FBC.
  
 6) CS-1 PLAN REVIEW DATA DECLARES THIS BUILDING AS A
 IIB BUILDING UNPROTECTED (1 STORY) FULLY SPRINKLED,
 NOTE THE COMMENTFOR UNLIMITED AREA FOR TYPE II
 BUILDINGS S OCCUPANCIES FOR FULLY SPRINKLED BUILDINGS
 FBC 507.2REQUIRES A 60'-0"CLEARANCE, WHICH THIS
 BUILDING DOES NOT HAVE. 507.4 DOES PROVIDE FOR REDUCED
 OPEN SPACE REQUIREMENTS BUT THE EXISTING BUILDING IS
 21.29' AWAY FROM THE PROPERTY LINE. PLEASE PROVIDE
 INCREASES FOR SPRINKLERS, ONE STORY AND ANY AREA
 INCREASES THAT CAN BE TAKEN PROVIDE CALCULATIONS FOR
 AREA MODIFICATIONS ON THE PLAN. TOTAL SQ FT UNDER TYPE
 II-B UNPROTECTED (S-1) IS 17,500 SQ FT.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8)THE CONTRACTOR HAS ELECTED TO APPLY FOR A
 FOUNDATION PERMIT, THE DETAIL SHEET S-3 INDICATES THIS
 TO BE A MONOLITHIC SLAB, AS DRAWN THE ELECTRICAL WILL
 NEED TO SEE COMPLIANCE WITH THE GROUNDING ELECTRODE
 SYSTEM REQUIRING AN ELECTRICAL PERMIT.
  
 9) THIS IS A COMPLETELY SEPARATE BUILDING FROM THE
 BUILDING IN FRONT, SO THERE WOULD ALSO NEED TO BE A
 RISER FOR THE FIRE SPRINKLERS PENETRATING THE
 MONOLITHIC SLAB.THE SAME MAY HOLD TRUE FOR PLUMBING
 AND MECHANICAL
  
 10PROVISO: THE SOILS REPORT ALSO INDICATES AREAS OF
 ORGANIC CONTENT. PROVIDE FROM THE SOILS ENGINEERS
 REPORTS FOR THE REMOVAL AND COMPACTION OF THE LIFTS TO
 THE SOILS ENGINEERS RECOMMENDATIONS.
  
 11PROVISO:109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEWCONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIESRESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL
 AS A PERMIT CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE
 WITH THIS PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 12 PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOWCONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 13 BUILDING PROVISO: 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT HIS OR
 HER OWN RISK AND WITH OUT ASSURANCE THAT A PERMIT FOR
 THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 14 BUILDING PROVISO: THIS IS AT MINIMUM TYPE II-B
 BUILDING WHICH NORMALLY WOULD REQUIRE A RESIDENT
 INSPECTOR BY THE CITY?S ADMINISTRATIVE CODE 109.3.7(1),
 AT THIS TIME THE
 INSPECTION SERVICES MANAGER HAROLD PISKURA HAS DEEM IT
 UNNECESSARY. IF PROBLEMS DO OCCUR DURING THE TIME OF
 CONSTRUCTION THE CITY MAY ELECT TO HAVE SUCH INSPECTOR
 ON SITE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 10:32 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 10:22 Sent To  
Notes
2007-10-14 10:32:49RISER FOR GROUNDING OF NEW FOUNDATION, SLAB/FOOTER
 ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-16 Cont ID  
Sent By dpalmer Date 2007-07-16 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2007-07-16 Time 18:36 Sent To I
Notes
2007-07-16 19:09:262007-07-16 19:09:26
 **** UNSAT ****
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS REQUESTED
 TO SUBMIT SLAB/SITE DETAIL INDICATING ANY CONDUITS TO
 BE INSTALLED UNDER THE FOUNDATION/SITE PERMIT. THE
 RESPONSE LETTER MENTIONS TO SEE REV 3 DETAIL ON SHEET
 5.1, HOWEVER NO DETAIL WAS LOCATED.??
  
 **AS A NOTE, THE RISER IS SHOWING AN "EQUIPMENT
 GROUNDING CONDUCTOR" AHEAD OF THE NEW MAIN WHICH IS
 NOT PERMITTED PER 250.6 AND 250.24. AN EQUIPMENT
 GROUNDIGN CONDUCTOR IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-16 18:37:422007-07-16 18:37:42
 PLANS IN ELEC FOR REVIEW. PLANS WILL RETURN TO INCOMING
 WAITING FOR COMM BOARD ONCE REVIEW IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By dpalmer Date 2007-06-22 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2007-06-22 Time 11:25 Sent To FIRE
Notes
2007-06-22 11:27:28*** UNSAT***
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL DETAILS FOR GROUNDING
 ELECTRODE SYSTEM WHICH IS PART OF SLAB/FOOTINGS FOR THE
 MAIN BUILDING. THIS SHOULD BE PART OF THE DESIGN FROM
 THE ELECTRICAL DESIGNER OF RECORD FROM THE BUILDING
 PERMIT APPLICATION.
 250.50, 250.32.
  
 2) NOTE: PLEASE SUBMIT AN UNDERGROUND CONDUIT
 LAYOUT/SCHEDULE FOR ALL CONDUITS BEING INSTALLED. FBC
 106.3.5.1.2, 106.1.2, NEC 2005
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By rchokshi Date 2007-08-02 Time 09:10 Rev Time 0.00
Received By rchokshi Date 2007-08-02 Time 09:00 Sent To  
Notes
2007-08-02 09:10:16PASSED CONDITIONALLY FOR SLAB AND FOUNDATION WORK
 ONLY.
  
 HOWEVER, YOU MUST PROVIDE THE FOLLOWING INFO IN PERMIT
 # 07051156 FOR SITE DEVELOPMENT PLAN INCLUDING BUILDING
 PAD, STORM DRAINAGE SYSTEM, RETENTION PONDS.
  
 1. IN YOUR RESPONSE LETTER OF 6/26/07, ARCHITECTURE
 ALLIANCE WROTEFOR REV 1 OF 6/21/07"SEE CAMERO'S
 RESPONSE LETTER", WE COULD NOT FIND CAMERO'S LETTER IN
 THE PACKAGE YOU SUBMITTED ON JULY 3, 07.WE ALSO COULD
 NOT FIND CIVIL DRAWING SET YOU SUBMITTED ON JULY 03,
 07. PLEASE RESPOND OUR COMMENTS OF REV 1, 6/21/07. ALSO
 SUBMIT CIVIL DRAWING SET FOR OUR REVIEW.
  
 WE HAVE A NEW FOLLOWING REQUIREMENTS, PLEASE RESPOND
 THAT TOO.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 THIS IS KIND OF A NEW REQUIREMENTS. YOU MAY HAVE
 ALREADY APPLIED FOR NOI. JUST SEND US A COPY NOITHAT
 YOU APPLY AT FDEP, NPDES STORM WATER SECTION,.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-07-27 Cont ID  
Sent By rchokshi Date 2007-07-27 Time 10:46 Rev Time 0.00
Received By rchokshi Date 2007-07-27 Time 10:31 Sent To  
Notes
2007-07-27 10:46:51***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. IN YOUR RESPONSE LETTER OF 6/26/07, ARCHITECTURE
 ALLIANCE WROTEFOR REV 1 OF 6/21/07"SEE CAMERO'S
 RESPONSE LETTER", WE COULD NOT FIND CAMERO'S LETTER IN
 THE PACKAGE YOU SUBMITTED ON JULY 3, 07.WE ALSO COULD
 NOT FIND CIVIL DRAWING SET YOU SUBMITTED ON JULY 03,
 07. PLEASE RESPOND OUR COMMENTS OF REV 1, 6/21/07. ALSO
 SUBMIT CIVIL DRAWING SET FOR OUR REVIEW.
  
 WE HAVE A NEW FOLLOWING REQUIREMENTS, PLEASE RESPOND
 THAT TOO.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 THIS IS KIND OF A NEW REQUIREMENTS. YOU MAY HAVE
 ALREADY APPLIED FOR NOI. JUST SEND US A COPY NOITHAT
 YOU APPLY AT FDEP, NPDES STORM WATER SECTION,.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By rchokshi Date 2007-06-21 Time 09:15 Rev Time 0.00
Received By rchokshi Date 2007-06-21 Time 09:08 Sent To  
Notes
2007-06-21 09:15:37***** FAILED *****
  
 WE KNOW THAT THIS IS A PERMIT FOR A FOUNDATION.
 HOWEVER, FOUNDATION MAY INCLUDE SITE PREPARATION,
 RETENTION POND, EXFILTRETION TRENCH & STORM WATER PIPES
 CROSSING ETC.,
 PLEASE NOTE THAT WE REVIEWED YOUR MASTER PERMIT #
 07030559 FOR ENGINEERING ON 04/06/07 & FAILED, HAS NOT
 BEEN PASSEDYET.
 PLEASE PROVIDE FOLLOWING INFO FOR THIS PERMIT:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD NOTES OF
 CITY OF WPB IN A C.D. FROM 1000 45TH STREET. WE SHOULD
 HAVE THOSE NOTES ON YOUR DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE, 5, 10, 25, 100
 YEAR RAIN CRITERIA & FL BLDG CODE TO DETERMINE FIRST
 FLOOR ELEVATION.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & GEO TECH
 REPORT.TO DETERMINE WATER CONDUCTIVITY FOR EXFILTRATION
 TRENCH IF YOU HAVE IT.
 5.PLEASE PROVIDE WATER QUALITY CALCULATIONS,WE USE
 SFWMD CRITERIA. DETAIL OF CONTROL STRUCTURE. DO YOU
 KEEP ALL STORM WATER ON SITE??, OR ANY CANAL? PLEASE
 EXPLAIN.
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ?ALSO, WHAT IS TOTAL PERVIOUS,& IMPERVIOUS
 AREA FOR THIS PROJECT., DO YOU HAVE LAKE?
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS MUST SHOW SILT FENCE ALL AROUND THE SITE,
 YOUR PLANS DO NOT SHOW ALL AROUND AND ALL AROUND CATCH
 BASINS. HEIGHT OF SILT5' OR MORE.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 11. PLEASE APPLY FOR NOTICE OF INTENT(NOI) AT FDEP, AND
 PROVIDE A COPY.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-30 Cont ID  
Sent By mwennerg Date 2007-10-30 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2007-10-30 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 16:08 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 15:13 Sent To  
Notes
2007-06-29 16:02:15*****UNSAT*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.SEE SHEET CS-1 UNDER PLAN REVIEW DATA
 (APPLICABLE CODES)
  
 02. THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).ADD NOTE TO SHEET S1
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 12:10 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 12:10 Sent To B
Notes
2007-12-04 12:11:20TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 14:45 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 14:45 Sent To  
Notes
2007-10-12 16:46:38TO "COMM" BD#17
2007-09-20 14:46:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 11:34 Sent To  
Notes
2007-07-17 15:54:23TO "COMM" BD#26
2007-07-05 11:34:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 16:45 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 16:45 Sent To ENG
Notes
2007-06-18 16:45:33TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-29 Cont ID  
Sent By bpowell Date 2007-06-08 Time 16:51 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 16:57 Sent To  
Notes
2007-06-01 16:57:33TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-04 Cont ID  
Sent By bpowell Date 2007-10-04 Time 10:39 Rev Time 0.00
Received By bpowell Date 2007-10-04 Time 10:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-26 Cont ID  
Sent By bpowell Date 2007-07-26 Time 19:06 Rev Time 0.00
Received By bpowell Date 2007-07-26 Time 19:06 Sent To  
Notes
2007-07-26 19:06:321. PLEASE INCLUDE A SITE PLAN THE SHOWS THE DIMENSIONS
 FROM EACH PROPERTY LINE TO THE BUILDING.
  
 FOR QUESTIONS OR COMMENTS CONTACT;BOBBY POWELL, JR.,
 PLANNER, (561) 822-1435, [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By bpowell Date 2007-06-18 Time 16:01 Rev Time 0.00
Received By bpowell Date 2007-06-18 Time 16:01 Sent To I
Notes
2007-06-18 16:03:361. A MINOR AMENDMENT WILL BE REQUIRED.
  
 2. THE NEW BUILDING IS NOT THE SAME SIZE AS IT WAS
 ORIGINALLY PERMITTED.
  
 FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR.,
 PLANNER, [email protected], (561) 822-1435