Plan Review Details - Permit 07051156
Plan Review Stops For Permit 07051156
Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-09-14 Cont ID  
Sent By dpalmer Date 2007-09-14 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2007-09-14 Time 14:40 Sent To  
Notes
2007-09-14 14:41:13REVIEW PASSED ON 7/17 HAS NOW BEEN CHANGED TO A *N* AS
 THE ELECTRICLA PLANS HAD NOT MATCHED THE SITE FOR
 ZONING.
 ANY SITE ELECTRICAL CONDUITS WILL BE UNDER SEPARATE
 PLANS AND PERMITS.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-07-17 Cont ID  
Sent By dpalmer Date 2007-07-17 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2007-07-17 Time 16:39 Sent To FIRE
Notes
2007-07-17 16:47:48**** PLANS REDLINED ****
  
 SHEET E2.1, IS FOR SITE CONDUIT ONLY.
 SHEET E5.1 IS REFERENCE FOR SITE CONDUIT SIZES ONLY. NO
 OTHER ELECTRICAL ON E5.1 IS REVIEWED OR STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By dpalmer Date 2007-06-22 Time 11:33 Rev Time 0.00
Received By dpalmer Date 2007-06-22 Time 11:33 Sent To FIRE
Notes
2007-06-22 11:34:13** UNSAT ***
  
  
 1) NOTE: PLEASE INDICATE ANY SITE CONDUITS WHICH MAY BE
 INSTALLED AT THIS TIME FOR SITE LIGHTING, SERVICE ETC.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2008-02-20 Cont ID  
Sent By rchokshi Date 2008-02-20 Time 11:15 Rev Time 0.00
Received By rchokshi Date 2008-02-20 Time 11:15 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2007-11-09 Cont ID  
Sent By rchokshi Date 2007-11-09 Time 11:00 Rev Time 0.00
Received By rchokshi Date 2007-11-09 Time 10:57 Sent To  
Notes
2007-11-09 11:00:46***** FAILED *****
  
  
 1.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE
 FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU
 CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION,
 FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION,
 PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO
 SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS
 HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD
 CALCULATION. FIRST FLOOR ELEVATION SHOULD BE HIGHER
 THAN MAX CROWN OF THE ROAD ELEVATION BY 1 FOOT,
 ATLEAST.
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
  
 3. INYOUR WATER QUALITY CALS ON 1ST PAGE, IN
 CALCULATION OF % IMPERVIOUSTHERE IS A MINOR ERROR.%
 OF IMPERVIOUS SHOULD BE = 1.02/1.91=0.53% IMPERVIOUS
 PER SFWMD PROCEDURE.SO,.53X2.5X4.736/12= 0.53 AC-FT
 TO BE TREATED. CHANGES AREMARKED IN YOUR CALS. SO,
 PLEASE REVISE THIS CALCULATIONS.WE USE SFWMD
 CRITERIA.DO YOU KEEP ALL STORM WATER ON SITE??, OR
 GOES INTOANY CANAL? PLEASE EXPLAIN. PLEASE ALSO
 RESUBMIT GEO-TECH REPORT WITH WATER QUALITY CALS.
  
 4. PLEASE SHOW ON THE DRAWING THE SITE AREA, PERVIOUS,
 IMPERVIOUS AREAYOU ARE DEVELOPING FOR THIS PROJECT
 ONLY ? DO YOU HAVE LAKE? PLEASE MAKE SURE THE AREA YOU
 USED IN WATER QUALITY CALS DO MATCH WITH THE AREA YOU
 SHOW ON DRAWINGS.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-09-28 Cont ID  
Sent By rchokshi Date 2007-09-28 Time 10:55 Rev Time 0.00
Received By rchokshi Date 2007-09-28 Time 10:08 Sent To  
Notes
2007-09-28 10:55:18***** FAILED *****
  
  
 1. WE COULD NOT FIND THE DRAWINGIN YOUR SUBMITTAL
 1/A-2 FOR DUMPSTER DETAILS,PER MR. CAMERO'S RESPONE
 LETTER OF MAY 23. 07.
 2.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE
 FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU
 CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION,
 FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION,
 PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO
 SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS
 HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD
 CALCULATION. SFWMD ALSO CHECK FIRST FLOOR ELEVATION
 BEFORE WE APPROVE.
 3. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
 4. INYOUR WATER QUALITY CALS ON 1ST PAGE, IN
 CALCULATION OF % IMPERVIOUSTHERE IS A MINOR ERROR.%
 OF IMPERVIOUS SHOULD BE = 1.02/1.91=0.53% IMPERVIOUS
 PER SFWMD PROCEDURE.SO,.53X2.5X4.736/12= 0.53 AC-FT
 TO BE TREATED. CHANGES ARE MARKED IN YOUR CALS. SO,
 PLEASE REVISE THIS CALCULATIONS.WE USE SFWMD
 CRITERIA. DETAIL OF CONTROL STRUCTURE ETC . DO YOU KEEP
 ALL STORM WATER ON SITE??, OR ANY CANAL? PLEASE
 EXPLAIN. PLEASE ALSO RESUBMIT GEO-TECH REPORT WITH
 WATER QUALITY CALS.
 5. PLEASE SHOW ON THE DRAWING THE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT ONLY ?ALSO, WHAT IS TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT., DO YOU
 HAVE LAKE? PLEASE MAKE SURE THE AREA YOU USED IN WATER
 QUALITY CALS DO MATCH WITH THE AREA YOU SHOW ON
 DRAWINGS.
 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE AT
 CONSTRUCTION SERVICES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-08-02 Cont ID  
Sent By rchokshi Date 2007-08-02 Time 12:59 Rev Time 0.00
Received By rchokshi Date 2007-08-02 Time 12:49 Sent To  
Notes
2007-08-02 12:59:17***** FAILED *****
  
 MOST OF THE FOLLOWING COMMENTS ARE ALSO GIVEN IN YOUR
 PERMIT # 07030559. HOWEVER, THIS PERMIT (07051156) IS
 FOR STORM WATER DRAINAGE/RETENTION POND.SO PLEASE
 PROVIDE THE FOLLOWING INFO:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 THIS IS KIND OF A NEW REQUIREMENTS. YOU MAY HAVE
 ALREADY APPLIED FOR NOI. JUST SEND US A COPY NOITHAT
 YOU APPLY AT FDEP, NPDES STORM WATER SECTION,.
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY STANDARDS
 ETC.,, MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD
 NOTES OF CITY OF WPB IN A C.D. FROM 1000 45TH STREET.
 WE SHOULD HAVE THOSE NOTES ON YOUR DRAWINGS. FOR YOUR
 INFO, MANNY GONZALEZ DOES NOT DO ENG REVIEW, AT
 CONSTRUCTION SERVICES AS MR. CAMERO WROTE IN HIS LETTER
 OF 5/23/07 FOR PER PERMIT # 07030559.
 3.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE
 FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU
 CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION,
 FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION,
 PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO
 SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS
 HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD
 CALCULATION.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
 5. WE COULD NOT FIND A COPY OF WATER QUALITY
 CALCULATION IN THE PACKAGE. IN PREVIOUS REV (LAST TIME)
 WE WROTE THAT PLEASE EXPLAIN IN YOURSTORM WATER
 CALCULATIONS, PAGE 2,IN CALCULATING LENGTH OF
 EXFILTRATION TRNECH, V= 4.736- 2.02,WHY ARE YOU
 DEDUCTING 2.02?, ALSO EXPLAIN ALL OTHER PARAMETERS,
 PLEASE GO THRU ONE MORE TIME, WE USE SFWMD CRITERIA.
 DETAIL OF CONTROL STRUCTURE. DO YOU KEEP ALL STORM
 WATER ON SITE??, OR ANY CANAL? PLEASE EXPLAIN. PLEASE
 ALSO RESUBMIT GEO-TECH REPORT WITH WATER QUALITY CALS.
 6. PLEASE SHOW ON THE DRAWING THE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT ONLY ?ALSO, WHAT IS TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT., DO YOU
 HAVE LAKE? PLEASE MAKE SURE THE AREA YOU USED IN WATER
 QUALITY CALS DO MATCH WITH THE AREA YOU SHOW ON
 DRAWINGS.
 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE AT
 CONSTRUCTION SERVICES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By rchokshi Date 2007-06-21 Time 09:03 Rev Time 0.00
Received By rchokshi Date 2007-06-21 Time 08:32 Sent To  
Notes
2007-06-21 09:03:11***** FAILED *****
  
 WE KNOW THAT THIS IS A PERMIT FOR A SITE PREPARATION.
 HOWEVER, YOU STATED IN THIS APPLICATION THAT THIS
 PERMIT FOR STORM DRAINAGE SYSTM, RETENTION POND TOO.
 BECAUSE SITE PREPARATION MAY INCLUDE POND, STORM WATER
 PIPES ETC.,
 PLEASE NOTE THAT WE REVIEWED YOUR MASTER PERMIT #
 07030559 FOR ENGINEERING ON 04/06/07 & FAILED, HAS NOT
 BEEN PASSEDYET.
 PLEASE PROVIDE FOLLOWING INFO FOR THIS PERMIT:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD NOTES OF
 CITY OF WPB IN A C.D. FROM 1000 45TH STREET. WE SHOULD
 HAVE THOSE NOTES ON YOUR DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE, 5, 10, 25, 100
 YEAR RAIN CRITERIA & FL BLDG CODE TO DETERMINE FIRST
 FLOOR ELEVATION.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & GEO TECH
 REPORT.TO DETERMINE WATER CONDUCTIVITY FOR EXFILTRATION
 TRENCH IF YOU HAVE IT.
 5.PLEASE PROVIDE WATER QUALITY CALCULATIONS,WE USE
 SFWMD CRITERIA. DETAIL OF CONTROL STRUCTURE. DO YOU
 KEEP ALL STORM WATER ON SITE??, OR ANY CANAL? PLEASE
 EXPLAIN.
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ?ALSO, WHAT IS TOTAL PERVIOUS,& IMPERVIOUS
 AREA FOR THIS PROJECT., DO YOU HAVE LAKE?
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS MUST SHOW SILT FENCE ALL AROUND THE SITE,
 YOUR PLANS DO NOT SHOW ALL AROUND AND ALL AROUND CATCH
 BASINS. HEIGHT OF SILT5' OR MORE.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 11. PLEASE APPLY FOR NOTICE OF INTENT(NOI) AT FDEP, AND
 PROVIDE A COPY.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-03 Cont ID  
Sent By mwennerg Date 2008-04-03 Time 15:43 Rev Time 0.00
Received By mwennerg Date 2008-04-03 Time 15:43 Sent To  
Notes
2008-04-03 15:43:52REVISED SHEETS C-1 AND C-7.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2007-11-15 Cont ID  
Sent By mwennerg Date 2007-11-15 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2007-11-15 Time 14:16 Sent To B
Notes
2007-11-15 14:16:50FORWARDED TO BUILDING FOR POSSIBLE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-08-27 Time 16:18 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 15:36 Sent To Z
Notes
2007-08-27 16:15:05*****APPROVED*****
  
  
 PLAN SHEET C-7 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 16:24 Rev Time 0.00
Received By rchokshi Date 2007-06-29 Time 16:21 Sent To FIRE
Notes
2007-06-29 16:22:36*****UNSAT*****
  
  
 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.SEE SHEET CS-1 UNDER PLAN REVIEW DATA
 (APPLICABLE CODES)
  
 02. THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).ADD NOTE TO SHEET S1
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 16:27 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 16:27 Sent To FIRE
Notes
2008-03-25 16:27:50TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-08 Cont ID  
Sent By ssherman Date 2007-11-08 Time 08:55 Rev Time 0.00
Received By ssherman Date 2007-11-08 Time 08:55 Sent To Z
Notes
2007-11-08 08:58:04PLANS TAKEN FROM "ENG" SENT TO BOBBY POWELL. .SITE
 PLANWAS MISSING FROM ORIGINAL PACKAGE AND LOCATED IN
 OUR FILES.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 12:39 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 12:39 Sent To Z
Notes
2007-10-18 12:39:40TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-19 Cont ID  
Sent By adarroug Date 2007-09-19 Time 15:44 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 15:44 Sent To ENG
Notes
2007-09-19 15:45:12TO "ENG" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 14:51 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 14:51 Sent To Z
Notes
2007-09-11 14:52:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-17 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-07-17 Time 16:14 Sent To E
Notes
2007-07-17 16:15:33TO "DPALMER" DESK/RESUB---PLANS BROUGHT BACK FROM "Z"
 TO BE ROUTED BACK TO "BOBBY POWELL" WHEN REVIEWS ARE
 DONE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 09:11 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 09:11 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 16:43 Sent To ENG
Notes
2007-06-18 16:43:39TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 16:28 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 16:54 Sent To  
Notes
2007-06-01 16:54:14TO "Z" BOX

Review Stop Z ZONING
Rev No 5 Status P Date 2007-11-08 Cont ID  
Sent By bpowell Date 2007-11-08 Time 09:06 Rev Time 0.00
Received By bpowell Date 2007-11-08 Time 09:06 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-10-29 Cont ID  
Sent By bpowell Date 2007-10-29 Time 08:59 Rev Time 0.00
Received By bpowell Date 2007-10-29 Time 08:59 Sent To ENG
Notes
2007-10-29 09:00:55 
 1. AT LEAST TWO (2) COPIES OF A SIGNED A SEALED SURVEY
 SHALL BE INCLUDED AS A PART OF THE PERMIT APPLICATION.
 2. PLEASE INCLUDE AT LEAST TWO (2) COPIES OF THE SITE
 PLAN ALONG WITH THE PERMIT APPLICATION.
  
 FOR QUESTIONS OR COMMENTS PLEASE CONTACT BOBBY POWELL
 JR., PLANNER, [email protected], (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-19 Cont ID  
Sent By bpowell Date 2007-09-19 Time 09:16 Rev Time 0.00
Received By bpowell Date 2007-09-19 Time 09:16 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-28 Cont ID  
Sent By bpowell Date 2007-08-28 Time 16:28 Rev Time 0.00
Received By bpowell Date   Time   Sent To  
Notes
2007-08-28 16:35:391. THE LOCATION OF THE GATE LOCATED ON THE SOUTH OF THE
 PROPERTY, WITHIN THE LANDSCAPE ISLANDA, SHALL BE
 CONSISTENT WITH THE APPROVED ON THE MINOR AMENDMENT.
  
 2. ALL PLANS SUBMITTED WITHIN THE PACKET SHALL MATCH.
  
 FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR.,
 PLANNER, (561) 822-1435, [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By bpowell Date 2007-06-18 Time 15:51 Rev Time 0.00
Received By bpowell Date 2007-06-18 Time 15:51 Sent To I
Notes
2007-06-18 15:55:001. THE SCOPE OF WORK DOES NOT MATCH WHAT IS INDICATED
 ON THE PLANS, RETENTION PONDS ARE NOT SHOWN ON THE
 PLANS.
  
 2. THE SITE PLAN DOES NOT MATCH WHAT WAS ORIGINALLY
 PERMITTED AND WILL NEED TO UNDERGO A MINOR AMENDMENT
  
 3. THEPLAN SHOWS A NEW GATE LOCATION AND A NEW WALL
 LOCATION.
  
 4. TEN (10) CONSECUTIVE PARKING SPACES ARE ALLOWED
 BETWEEN LANDSCAPE ISLANDS.
  
 FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR.,
 PLANNER, [email protected], (561) 822-1435