| Plan Review Stops For Permit 07051156 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-14 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-14 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2007-09-14 14:41:13 | REVIEW PASSED ON 7/17 HAS NOW BEEN CHANGED TO A *N* AS | | | THE ELECTRICLA PLANS HAD NOT MATCHED THE SITE FOR | | | ZONING. | | | ANY SITE ELECTRICAL CONDUITS WILL BE UNDER SEPARATE | | | PLANS AND PERMITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-17 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-17 |
Time |
16:39 |
Sent To |
FIRE |
|
| Notes |
| 2007-07-17 16:47:48 | **** PLANS REDLINED **** | | | | | | SHEET E2.1, IS FOR SITE CONDUIT ONLY. | | | SHEET E5.1 IS REFERENCE FOR SITE CONDUIT SIZES ONLY. NO | | | OTHER ELECTRICAL ON E5.1 IS REVIEWED OR STAMPED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-22 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-22 |
Time |
11:33 |
Sent To |
FIRE |
|
| Notes |
| 2007-06-22 11:34:13 | ** UNSAT *** | | | | | | | | | 1) NOTE: PLEASE INDICATE ANY SITE CONDUITS WHICH MAY BE | | | INSTALLED AT THIS TIME FOR SITE LIGHTING, SERVICE ETC. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
P |
Date |
2008-02-20 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-02-20 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-02-20 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-11-09 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-11-09 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2007-11-09 11:00:46 | ***** FAILED ***** | | | | | | | | | 1.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE | | | FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU | | | CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION, | | | FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION, | | | PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO | | | SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS | | | HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD | | | CALCULATION. FIRST FLOOR ELEVATION SHOULD BE HIGHER | | | THAN MAX CROWN OF THE ROAD ELEVATION BY 1 FOOT, | | | ATLEAST. | | | | | | 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, | | | | | | 3. INYOUR WATER QUALITY CALS ON 1ST PAGE, IN | | | CALCULATION OF % IMPERVIOUSTHERE IS A MINOR ERROR.% | | | OF IMPERVIOUS SHOULD BE = 1.02/1.91=0.53% IMPERVIOUS | | | PER SFWMD PROCEDURE.SO,.53X2.5X4.736/12= 0.53 AC-FT | | | TO BE TREATED. CHANGES AREMARKED IN YOUR CALS. SO, | | | PLEASE REVISE THIS CALCULATIONS.WE USE SFWMD | | | CRITERIA.DO YOU KEEP ALL STORM WATER ON SITE??, OR | | | GOES INTOANY CANAL? PLEASE EXPLAIN. PLEASE ALSO | | | RESUBMIT GEO-TECH REPORT WITH WATER QUALITY CALS. | | | | | | 4. PLEASE SHOW ON THE DRAWING THE SITE AREA, PERVIOUS, | | | IMPERVIOUS AREAYOU ARE DEVELOPING FOR THIS PROJECT | | | ONLY ? DO YOU HAVE LAKE? PLEASE MAKE SURE THE AREA YOU | | | USED IN WATER QUALITY CALS DO MATCH WITH THE AREA YOU | | | SHOW ON DRAWINGS. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-09-28 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-09-28 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2007-09-28 10:55:18 | ***** FAILED ***** | | | | | | | | | 1. WE COULD NOT FIND THE DRAWINGIN YOUR SUBMITTAL | | | 1/A-2 FOR DUMPSTER DETAILS,PER MR. CAMERO'S RESPONE | | | LETTER OF MAY 23. 07. | | | 2.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE | | | FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU | | | CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION, | | | FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION, | | | PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO | | | SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS | | | HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD | | | CALCULATION. SFWMD ALSO CHECK FIRST FLOOR ELEVATION | | | BEFORE WE APPROVE. | | | 3. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, | | | 4. INYOUR WATER QUALITY CALS ON 1ST PAGE, IN | | | CALCULATION OF % IMPERVIOUSTHERE IS A MINOR ERROR.% | | | OF IMPERVIOUS SHOULD BE = 1.02/1.91=0.53% IMPERVIOUS | | | PER SFWMD PROCEDURE.SO,.53X2.5X4.736/12= 0.53 AC-FT | | | TO BE TREATED. CHANGES ARE MARKED IN YOUR CALS. SO, | | | PLEASE REVISE THIS CALCULATIONS.WE USE SFWMD | | | CRITERIA. DETAIL OF CONTROL STRUCTURE ETC . DO YOU KEEP | | | ALL STORM WATER ON SITE??, OR ANY CANAL? PLEASE | | | EXPLAIN. PLEASE ALSO RESUBMIT GEO-TECH REPORT WITH | | | WATER QUALITY CALS. | | | 5. PLEASE SHOW ON THE DRAWING THE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT ONLY ?ALSO, WHAT IS TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT., DO YOU | | | HAVE LAKE? PLEASE MAKE SURE THE AREA YOU USED IN WATER | | | QUALITY CALS DO MATCH WITH THE AREA YOU SHOW ON | | | DRAWINGS. | | | 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE AT | | | CONSTRUCTION SERVICES. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-08-02 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-08-02 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2007-08-02 12:59:17 | ***** FAILED ***** | | | | | | MOST OF THE FOLLOWING COMMENTS ARE ALSO GIVEN IN YOUR | | | PERMIT # 07030559. HOWEVER, THIS PERMIT (07051156) IS | | | FOR STORM WATER DRAINAGE/RETENTION POND.SO PLEASE | | | PROVIDE THE FOLLOWING INFO: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | THIS IS KIND OF A NEW REQUIREMENTS. YOU MAY HAVE | | | ALREADY APPLIED FOR NOI. JUST SEND US A COPY NOITHAT | | | YOU APPLY AT FDEP, NPDES STORM WATER SECTION,. | | | 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON | | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | | PARKING, HANDICAP PARKING, PAINTPER CITY STANDARDS | | | ETC.,, MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD | | | NOTES OF CITY OF WPB IN A C.D. FROM 1000 45TH STREET. | | | WE SHOULD HAVE THOSE NOTES ON YOUR DRAWINGS. FOR YOUR | | | INFO, MANNY GONZALEZ DOES NOT DO ENG REVIEW, AT | | | CONSTRUCTION SERVICES AS MR. CAMERO WROTE IN HIS LETTER | | | OF 5/23/07 FOR PER PERMIT # 07030559. | | | 3.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE | | | FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU | | | CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION, | | | FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION, | | | PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO | | | SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS | | | HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD | | | CALCULATION. | | | 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, | | | 5. WE COULD NOT FIND A COPY OF WATER QUALITY | | | CALCULATION IN THE PACKAGE. IN PREVIOUS REV (LAST TIME) | | | WE WROTE THAT PLEASE EXPLAIN IN YOURSTORM WATER | | | CALCULATIONS, PAGE 2,IN CALCULATING LENGTH OF | | | EXFILTRATION TRNECH, V= 4.736- 2.02,WHY ARE YOU | | | DEDUCTING 2.02?, ALSO EXPLAIN ALL OTHER PARAMETERS, | | | PLEASE GO THRU ONE MORE TIME, WE USE SFWMD CRITERIA. | | | DETAIL OF CONTROL STRUCTURE. DO YOU KEEP ALL STORM | | | WATER ON SITE??, OR ANY CANAL? PLEASE EXPLAIN. PLEASE | | | ALSO RESUBMIT GEO-TECH REPORT WITH WATER QUALITY CALS. | | | 6. PLEASE SHOW ON THE DRAWING THE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT ONLY ?ALSO, WHAT IS TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT., DO YOU | | | HAVE LAKE? PLEASE MAKE SURE THE AREA YOU USED IN WATER | | | QUALITY CALS DO MATCH WITH THE AREA YOU SHOW ON | | | DRAWINGS. | | | 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE AT | | | CONSTRUCTION SERVICES. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-06-21 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-06-21 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-06-21 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2007-06-21 09:03:11 | ***** FAILED ***** | | | | | | WE KNOW THAT THIS IS A PERMIT FOR A SITE PREPARATION. | | | HOWEVER, YOU STATED IN THIS APPLICATION THAT THIS | | | PERMIT FOR STORM DRAINAGE SYSTM, RETENTION POND TOO. | | | BECAUSE SITE PREPARATION MAY INCLUDE POND, STORM WATER | | | PIPES ETC., | | | PLEASE NOTE THAT WE REVIEWED YOUR MASTER PERMIT # | | | 07030559 FOR ENGINEERING ON 04/06/07 & FAILED, HAS NOT | | | BEEN PASSEDYET. | | | PLEASE PROVIDE FOLLOWING INFO FOR THIS PERMIT: | | | | | | 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON | | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | | PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,, | | | MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD NOTES OF | | | CITY OF WPB IN A C.D. FROM 1000 45TH STREET. WE SHOULD | | | HAVE THOSE NOTES ON YOUR DRAWINGS. | | | 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE, 5, 10, 25, 100 | | | YEAR RAIN CRITERIA & FL BLDG CODE TO DETERMINE FIRST | | | FLOOR ELEVATION. | | | 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & GEO TECH | | | REPORT.TO DETERMINE WATER CONDUCTIVITY FOR EXFILTRATION | | | TRENCH IF YOU HAVE IT. | | | 5.PLEASE PROVIDE WATER QUALITY CALCULATIONS,WE USE | | | SFWMD CRITERIA. DETAIL OF CONTROL STRUCTURE. DO YOU | | | KEEP ALL STORM WATER ON SITE??, OR ANY CANAL? PLEASE | | | EXPLAIN. | | | 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS | | | PROJECT ONLY ?ALSO, WHAT IS TOTAL PERVIOUS,& IMPERVIOUS | | | AREA FOR THIS PROJECT., DO YOU HAVE LAKE? | | | 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO | | | CONNECT WITH THE STORM WATERFROM ALL OTHER STORM | | | WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL | | | STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ? | | | 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT | | | ETC., PLANS MUST SHOW SILT FENCE ALL AROUND THE SITE, | | | YOUR PLANS DO NOT SHOW ALL AROUND AND ALL AROUND CATCH | | | BASINS. HEIGHT OF SILT5' OR MORE. | | | 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | | 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | 11. PLEASE APPLY FOR NOTICE OF INTENT(NOI) AT FDEP, AND | | | PROVIDE A COPY. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-04-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-04-03 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-04-03 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2008-04-03 15:43:52 | REVISED SHEETS C-1 AND C-7. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
N |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-15 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-15 |
Time |
14:16 |
Sent To |
B |
|
| Notes |
| 2007-11-15 14:16:50 | FORWARDED TO BUILDING FOR POSSIBLE REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-27 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-27 |
Time |
15:36 |
Sent To |
Z |
|
| Notes |
| 2007-08-27 16:15:05 | *****APPROVED***** | | | | | | | | | PLAN SHEET C-7 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-29 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-06-29 |
Time |
16:21 |
Sent To |
FIRE |
|
| Notes |
| 2007-06-29 16:22:36 | *****UNSAT***** | | | | | | | | | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.SEE SHEET CS-1 UNDER PLAN REVIEW DATA | | | (APPLICABLE CODES) | | | | | | 02. THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | | THEREOF (INCLUDING FIRE LANES).ADD NOTE TO SHEET S1 | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-25 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-25 |
Time |
16:27 |
Sent To |
FIRE |
|
| Notes |
| 2008-03-25 16:27:50 | TO "F" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
ssherman |
Date |
2007-11-08 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
ssherman |
Date |
2007-11-08 |
Time |
08:55 |
Sent To |
Z |
|
| Notes |
| 2007-11-08 08:58:04 | PLANS TAKEN FROM "ENG" SENT TO BOBBY POWELL. .SITE | | | PLANWAS MISSING FROM ORIGINAL PACKAGE AND LOCATED IN | | | OUR FILES. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-18 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-18 |
Time |
12:39 |
Sent To |
Z |
|
| Notes |
| 2007-10-18 12:39:40 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-19 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-19 |
Time |
15:44 |
Sent To |
ENG |
|
| Notes |
| 2007-09-19 15:45:12 | TO "ENG" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-11 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-11 |
Time |
14:51 |
Sent To |
Z |
|
| Notes |
| 2007-09-11 14:52:12 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-17 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-17 |
Time |
16:14 |
Sent To |
E |
|
| Notes |
| 2007-07-17 16:15:33 | TO "DPALMER" DESK/RESUB---PLANS BROUGHT BACK FROM "Z" | | | TO BE ROUTED BACK TO "BOBBY POWELL" WHEN REVIEWS ARE | | | DONE. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-06 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-06 |
Time |
09:11 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-18 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-18 |
Time |
16:43 |
Sent To |
ENG |
|
| Notes |
| 2007-06-18 16:43:39 | TO "ENG" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-29 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-01 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2007-06-01 16:54:14 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-11-08 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-11-08 |
Time |
09:06 |
Sent To |
ENG |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-10-29 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-10-29 |
Time |
08:59 |
Sent To |
ENG |
|
| Notes |
| 2007-10-29 09:00:55 | | | | 1. AT LEAST TWO (2) COPIES OF A SIGNED A SEALED SURVEY | | | SHALL BE INCLUDED AS A PART OF THE PERMIT APPLICATION. | | | 2. PLEASE INCLUDE AT LEAST TWO (2) COPIES OF THE SITE | | | PLAN ALONG WITH THE PERMIT APPLICATION. | | | | | | FOR QUESTIONS OR COMMENTS PLEASE CONTACT BOBBY POWELL | | | JR., PLANNER, [email protected], (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-09-19 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-09-19 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-09-19 |
Time |
09:16 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-08-28 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2007-08-28 16:35:39 | 1. THE LOCATION OF THE GATE LOCATED ON THE SOUTH OF THE | | | PROPERTY, WITHIN THE LANDSCAPE ISLANDA, SHALL BE | | | CONSISTENT WITH THE APPROVED ON THE MINOR AMENDMENT. | | | | | | 2. ALL PLANS SUBMITTED WITHIN THE PACKET SHALL MATCH. | | | | | | FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR., | | | PLANNER, (561) 822-1435, [email protected]. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-06-18 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-06-18 |
Time |
15:51 |
Sent To |
I |
|
| Notes |
| 2007-06-18 15:55:00 | 1. THE SCOPE OF WORK DOES NOT MATCH WHAT IS INDICATED | | | ON THE PLANS, RETENTION PONDS ARE NOT SHOWN ON THE | | | PLANS. | | | | | | 2. THE SITE PLAN DOES NOT MATCH WHAT WAS ORIGINALLY | | | PERMITTED AND WILL NEED TO UNDERGO A MINOR AMENDMENT | | | | | | 3. THEPLAN SHOWS A NEW GATE LOCATION AND A NEW WALL | | | LOCATION. | | | | | | 4. TEN (10) CONSECUTIVE PARKING SPACES ARE ALLOWED | | | BETWEEN LANDSCAPE ISLANDS. | | | | | | FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR., | | | PLANNER, [email protected], (561) 822-1435 |
|
|