Plan Review Details - Permit 07051152
Plan Review Stops For Permit 07051152
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-08 Cont ID  
Sent By amorse Date 2007-07-08 Time 19:18 Rev Time 0.00
Received By amorse Date 2007-07-08 Time 19:18 Sent To PC
Notes
2007-07-08 19:55:15 
  
 DENIED
  
 1)PROVIDE DESIGN PARAMETERS ON DRAWINGS THIS INCLUDES
 THE CODE CYCLE (2004 FBC W/ 2006 AMENDMENTS) AND THE
 TYPE OF CONSTRUCTION
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/
 FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 7)PROVIDE 2 COPIES OF RECENT SURVEY THAT SHOWS ALL
 EXISTING AND PROPOSED WORK, COMPLETE WITH ALL FRONT,
 SIDE AND REAR SETBACKS FROM BUILDINGS AND EQUIPMENT.
  
 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4
  
 9)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1
  
 10)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 11)PROVIDE THEVALUATION ON THE PERMIT APPLICATION.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*. IF VALUE IS FOUND TO BE LOW ADJUSTMENTS
 WILL BE MADE AND FEES DUE.
  
 12)SUBMIT ENERGY CALC'S PER 13-101.2.2 FBC. BE SURE
 THAT THEY ARE SIGNED AND DATED BY PREPARER AND
 OWNER/AGENT PRIOR TO SUBMITTAL
  
 13)FOUNDATION PLAN SHALL CONTAIN NOTES FOR VAPOR
 BARRIER AND TERMITE SOIL TREATMENT PER R506.2.3 & R320
 FBC RES.
  
 14)PROVIDE NOTE AT ALL SHOWER DOORS TO MEET SAFETY
 GLAZING IN HAZARDOUS LOCATIONS PER R308.4 ALSO DOOR
 SCHEDULE ON A/3 SHOWS SHOWER DOORS AS 1 1/2" THICK AND
 THE WALK IN CLOSET AS 3/8" THICK
  
 15)PROVIDE SMOKE ALARMS AT EACH LEVEL PER R313.1 FBC
 RES.
  
 16)STAIR HANDRAIL/GUARDS SHALL NOT ALLOW THE PASSAGE
 OF A 4" SPHERE PER R312.2 FBC RES.
  
 17)SECOND FLOOR LINTEL MARKS ARE NOT ASSIGNED IN
 BUILDINGS 1 & 2 ON SHEET A/10
  
 18)LINTEL SCHEDULE SHOWS ALL SIZES AS 8F24 YET
 SECTIONS SHOW A 8F16 PLEASE CLARIFY
  
 19)SECOND FLOOR FRAMING PLAN ON A/10 DOES NOT
 DESIGNATE A BEAM SIZE
  
 20)PROVIDECOMPLETE CONNECTOR SCHEDULE WITH THE
 FLORIDA STATEWIDE APPROVAL NUMBERS (THIS SAVES PRINTING
 OF ALL PRODUCT APPROVALS FOR EACH CONNECTOR)
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A PERMIT BEING
 ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By btrobaug Date 2007-06-15 Time 16:51 Rev Time 0.00
Received By btrobaug Date 2007-06-15 Time 15:49 Sent To M
Notes
2007-06-15 16:51:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. AND AIC RATING FOR EACH SERVICE.
  
 2} FOR THE PANEL SCHEDULE/LOAD CALCULATION THAT IS
 SUBMITTED WITH THIS SET.
 A) TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER
 210.11(C)(1), 220.52(A).
  
 B) BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3),
  
 C) LAUNDRY CIRCUIT PER 220.52(B), @ 1500 WATTS.
  
 D) DRYER MUST BE CALCULATED PER 220.54 @ 5000 WATTS.
 ALSO SEE THIS IS ON A 40 AMP BREAKER WITH A 900 WATT
 LOAD.
  
 F) 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 3} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 4} WATER HEATERS ARE REQUIRED TO HAVE
 DISCONNECTS.422.16.THERE IS A RECEPTACLE SYMBOL SHOWN.
  
 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. ALL UNITS IN
 SPACING VIOLATION.
  
 6} SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 914-MM (36-IN.) HORIZONTAL PATH FROM
 A DOOR TO A KITCHEN OR A BATHROOM CONTAINING A SHOWER
 OR TUB. 11.8.3.5(5) NFPA-72, 2002. PER 313.1 WILL BE
 REQUIRED ON THE SECOND FLOOR.
  
 7} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 NOTE: REFERENCING SHEET A1 "WALL LEGEND"PER 2704.1,
 2004 FBC, METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-08 Time   Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:16 Sent To  
Notes
2007-06-04 11:16:41TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By tgordon Date 2007-06-18 Time 15:54 Rev Time 0.35
Received By tgordon Date 2007-06-18 Time 15:54 Sent To P
Notes
2007-06-18 16:09:55PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.1.
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1 .
  
 3) PLEASE SHOW ON MECHANICAL PLANS AN EQUIPMENT LISTING
 WITH ALL PERTINENT INFORMATION.
  
 4) PLEASE SHOW CLOTHES DRYER VENT TERMINATION ON
 MECHANICAL PLANS (ALL UNITS), SEE 2004 FBC/R M1501.
  
 5) SHOW ON MECHANICAL PLANS ALL BATHROOM EXHAUST FANS
 AND THE CFM'S.
  
 6) PLEASE PROVIDE RETURN AIR TO THE FIRST FLOOR OFFICE
 (ALL UNITS),SEE 2004 FBC/R M1602.4.
  
 7) SHOW HOW THE SECOND FLOOR RETURN AIR IS GETTING BACK
 TO THE SECOND FLOOR AIR HANDLER UNIT (IF LOUVERED DOOR
 PLEASE SHOW ON MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By mperson Date 2007-06-22 Time 14:05 Rev Time 0.45
Received By mperson Date 2007-06-22 Time 14:05 Sent To B
Notes
2007-06-22 14:27:06DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 **PLAN REVIEW ONLY NOT FOR PERMIT**
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET M3 PLUMBING RISER: THE SANITARY ISOMETRIC
 RISER DIAGRAM INDICATED ON THIS SHEET DOES NOT REFLECT
 ANY OF THE THREE TOWNHOUSES. PLEASE COMPLY WITH THE
 FOLLOWING. PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELAVENT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM THAT REFLECTS
 THE FLOOR PLAN INDICATING ALL WASTE, VENTS, TRAPS AND
 SIZES WITH CLEANOUT LOCATIONS.
 NOTE: EACH THREE STORY TOWNHOUSE WILL REQUIRE ITS OWN
 SANITARY ISOMETRIC RISER DIAGRAM.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By choops Date 2007-06-04 Time 14:47 Rev Time 0.00
Received By choops Date 2007-06-04 Time 14:47 Sent To E
Notes
2007-06-04 15:04:00***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF AN UPDATED SURVEY
 (WITHIN THE LAST YEAR) , SHOWING THE SCOPE OF WORK,
 DIMENSIONS, AND SETBACK DIMENSIONS TO PROPERTY LINES.
  
 2)LOT AREA MUST BE AT LEAST 9,000 SQUARE FEET FOR 3
 UNITS.
  
 3)REQUIRED SIDE SETBACKS ARE 5 FT. MINIMUM WITH A
 TOTAL OF 15 FT..PROPOSED SIDE SETBACKS ONLY TOTAL 10
 FT.
  
 4)OVERALL BUILDING ELEVATION TO BE MEASURED FROM
 GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.ALL OTHER
 ELEVATIONS TO BE MEASURED FROM GRADE AS WELL.
  
 5)PLEASE PROVIDE OVERHANG DIMENSIONS FROM WALL TO
 ROOF'S OUTERMOST POINT.
  
 6)POOLS REQUIRE A SEPERATE PERMIT, AND MUST BE FULLY
 ENCLOSED BY A FENCE.
  
 7)PLEASE SHOW ANY PROPOSED MECHANICAL AND/OR A/C
 EQUIPMENT ON SURVEYS AND SITE PLANS WITH SETBACK
 DIMENSIONS TO PROPERTY LINES.
  
 8)SHOW DRIVEWAY DIMENSIONS IF TO BE INCLUDED WITH
 THIS PERMIT.IF NOT DRIVEWAYS TO BE UNDER SEPERATE
 PERMIT.
  
 9)PLEASE PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE CITY OF WEST PALM BEACH.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720