Plan Review Details - Permit 07051114
Plan Review Stops For Permit 07051114
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-06 Cont ID  
Sent By mjacobs Date 2007-11-06 Time 06:35 Rev Time 0.00
Received By mjacobs Date 2007-11-06 Time 05:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-10 Cont ID  
Sent By mjacobs Date 2007-10-10 Time 18:30 Rev Time 0.00
Received By mjacobs Date 2007-10-10 Time 17:38 Sent To  
Notes
2007-10-10 18:30:48BUILDING PLAN REVIEW
 PERMIT: 07051114
 ADD: 330 CLEMATIS ST.
 CONT: CASTLE CONST. INC.
 TEL: (561)818-6996
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
 10/10/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT A DETAIL DRAWING SHOWING HOW THE
 RECEPTIONIST COUNTER WILL MEET THE REQUIREMENTS OF FBC.
 11-7. A PORTION OF THE COUNTER SHALL BE A MINIMUM OF 36
 INCHES IN LENGTH AND MAXIMUM HEIGHT OF 36 INCHES.
 **NOTED HOWEVER**
 A PORTION OF THE ?MAIN COUNTER? SHALL BE CUT TO MEET
 THE REQUIREMENT OF 36 INCHES HIGH AND 36 INCHES WIDE.
 SHOW THE FRONT ELEVATION ON THE COUNTER MEETING THE
 REQUIREMENT OF SECTION 11-7 (2) (I)
  
 3) OK
  
 4)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-15 Cont ID  
Sent By mjacobs Date 2007-08-15 Time 17:53 Rev Time 0.00
Received By mjacobs Date 2007-08-15 Time 15:34 Sent To  
Notes
2007-08-15 17:53:47BUILDING PLAN REVIEW
 PERMIT: 07051114
 ADD: 330 CLEMATIS ST.
 CONT: CASTLE CONST. INC.
 TEL: (561)818-6996
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 NO RESPONSE************
 2)SUBMIT A DETAIL DRAWING SHOWING HOW THE
 RECEPTIONIST COUNTER WILL MEET THE REQUIREMENTS OF FBC.
 11-7. A PORTION OF THE COUNTER SHALL BE A MINIMUM OF 36
 INCHES IN LENGTH AND MAXIMUM HEIGHT OF 36 INCHES.
  
 NO RESPONSE*************
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING.
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
  
 NO RESPONSE***************
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By mjacobs Date 2007-06-20 Time 10:44 Rev Time 0.00
Received By mjacobs Date 2007-06-20 Time 06:57 Sent To  
Notes
2007-06-20 10:44:51BUILDING PLAN REVIEW
 PERMIT: 07051114
 ADD: 330 CLEMATIS ST.
 CONT: CASTLE CONST. INC.
 TEL: (561)818-6996
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT A DETAIL DRAWING SHOWING HOW THE
 RECEPTIONIST COUNTER WILL MEET THE REQUIREMENTS OF FBC.
 11-7. A PORTION OF THE COUNTER SHALL BE A MINIMUM OF 36
 INCHES IN LENGTH AND MAXIMUM HEIGHT OF 36 INCHES.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 08:50 Rev Time 0.00
Received By dpalmer Date 2007-10-30 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-01 Cont ID  
Sent By dpalmer Date 2007-10-01 Time 20:02 Rev Time 0.00
Received By dpalmer Date 2007-10-01 Time 19:34 Sent To  
Notes
2007-10-01 20:02:482007-10-01 20:02:48
  
 ** DENIED 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE THERE ARE STILL COMMENTS FROM THE
 TWO PREVIOUS REVIEWS WHICH ARE THE EXACT SAME COMMENTS
 WHICH STILL NEED TO BE ADDRESSED.
 AS THE ELECTRICAL PLANS AS SUBMITTED HAVE NOW ONCE
 AGAIN CHANGED THE DESIGNER OF RECORD, THE FEE AS
 REQUIRED UNDER FLORIDA STATUTES 553.80(2)(B) IS NOT
 ASSESSED.
 THIS STATUTE IS IN PLACE WHEN PLANS ARE DENIED FOR THE
 *SAME CODE COMPLIANT* COMMENT THREE OR MORE TIMES. ONLY
 WHEN THE SAME DESIGNER OF RECORD HAS HAD THE SAME
 COMMENT IS THE FEE THEN ASSESSED.
 THIS IS NOTED AS THESE COMMENTS AND PLANS NEED TO BE
 ADDRESSED AND COORDINATED.
  
 2) NOTE: PLEASE SEE AS CLEARLY STATED ON BOTH PREVIOUS
 REVIEWS: PLEASE SUBMIT A FIXTURE LEGEND/IDENTIFICATION
 AND CORRELATE WITH LIGHTING PERFORMANCE CALCULATIONS AS
 REQUIRED PER FLORIDA BUILDING CODE 13-415.2. PLEASE
 KNOW AS NO LIGHTING FIXTURE IDENTIFICATION AND
 CALCULATIONS WERE SUBMITTED, THE LIGHTING LEVELS CAN
 NOT BE REVIEWED OR CONFIRMED CODE COMPLIANT.
 ** IF THERE IS ANY PART OF THIS COMMENT NOT UNDERSTOOD,
 PLEASE CALL.
  
 3) NOTE: PLEASE SEE AS STATED ON THE PREVIOUS REVIEWS,
 THE INSTANT WATER HEATING UNIT NEEDS TO CORRELATE WITH
 PLANS AND THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED.
 **PLEASE SEE THE SPECS/CUT SHEETS AS SUBMITTED CLEARLY
 SHOW THE NEAREST TANKLESS WATER HEATER UNIT IS 28.5 KW
 AND THIS UNIT IS SHOWN AS 1-PHASE 120/240VOLTS.
 ** THE PLANS INDICATE A 24KW 3-PHASE120/208V UNIT.
 PLEASE SEE AS THE LISTING CONTAINED ON THE SPECS/CUT
 SHEETS DO NOT INDICATE ANY UNIT FOR THIS SIZE AND
 VOLTAGE AS SHOWN ON PLANS/PANEL SCHEDULE AND LOAD
 CALCULATIONS, REVIEW AND CONFORMATION FOR CODE
 COMPLIANCE CAN NOT BE DONE. THESE SIMPLY JUST DO NOT
 MATCH.
 THE SPECS/CUT SHEETS EVEN STATE THREE INDEPENDENT
 BREAKERS??
 PLEASE CORRELATE AND COORDINATE ALL.
 NEC 220, 110.3, 90.7.
  
 4) NOTE: PLEASE CLARIFY HOW THE LOADS FOR THE
 RECEPTACLES WHICH ARE BEING DEDICATED TO HAIR BLOW
 DRYERS AND OTHER DEVICES CAN BE SHOWN WITH A STANDARD
 VA OF 180VA FOR GENERAL USE? (ACTUAL 200VA SHOWN ON
 PANEL)
 PLEASE SEE NEC 220 AND PLEASE CLARIFY LOADS.
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 21:12 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 19:21 Sent To  
Notes
2007-08-10 21:13:15 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL NEEDING TO BE ADDRESSED ALONG WITH NEW COMMENTS
 DUE TO CHANGES ON PLANS AND NEW INFORMATION ONLY NOW
 SUBMITTED FOR REVIEW.
  
  
 1) NOTE: PLEASE SEE A FOUR TIMES THE PERMIT FEE WAS
 ASSESSED FOR COMMENCING WORK WITHOUT PERMITS AS
 REQUIRED PER FBC 105.1 AND 108.4
 PLEASE KNOW THE BALANCE IS DUE AT THIS TIME. THE
 CONTRACTOR WAS CONTACTED AND INFORMATION OF THIS AS OF
 THIS REVIEW.
  
 2) NOTE: PLEASE SEE THAT THE SCOPE OF WORK BEING
 APPLIED FOR IS APPLIED UNDER OF CERTIFIED RESIDENTIAL
 CONTRACTOR (CRC) WHICH DOES NOT PERMIT THIS LICENSE TO
 DO WORK IN A COMMERCIAL BUILDING. THIS WAS CONFIRMED
 WITH THE PALM BEACH COUNTY LICENSING BOARD AS WELL AS
 WITH INFORMATION WITH THE STATE OF FLORIDA LICENSING
 BOARD. PLEASE APPLY UNDER A LICENSE WHICH PERMITS THIS
 SCOPE OF WORK OR PLEASE KNOW THIS PERMIT WILL BE
 REQUIRED TO BE APPLIED FOR UNDER LICENSE CONTRACTOR
 WHOM CAN PERFORM THIS WORK.
 PLEASE KNOW A MESSAGE WAS LEFT FOR THE CONTRACTOR BY
 THE INSPECTION SERVICES MANAGER FOR THE QUALIFIER TO
 CONTACT THIS OFFICE.
 CHAPTER 67-1876 AS AMENDED BY THE PALM BEACH COUNTY
 LICENSING BOARD.
 FLORIDA STATUTES 489
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE NOW COMING
 IN UNDER A NEW DESIGNER AND THE DESIGNER OF RECORD AS
 SHOWN IS PERMITTED TO DESIGN THE SCOPE AS SHOWN HOWEVER
 THE PLANS MUST CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS AND DEISGN.
 FS 489, 468
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS REVIEW
 PLEASE INDICATE THE MAXIMUM TIMES ON OVER RIDES DEVICES
 AS REQUIRED PER 13-415.1.ABC.1.1 OF THE FBC. THIS WOULD
 BE FOR ALL DEVICES. ONLY TWO SHOWN ON DETAIL, YET PLANS
 INDICATE MORE.
 PLEASE ALSO SEE MISSING CONTROLS FOR SEPARATE SPACES
 PER 13-415.1.ABC.1.1 AND .1.2. THESE ARE SHOWN AS
 STANDARD SWITCHES.
 PLEASE SEE THE DETAIL AS SUBMITTED DOES NOT PROVIDE
 ENOUGH INFORMATION FOR SCOPE OF LIGHTING CONTROL
 SYSTEM. PLEASE SEE THAT THE LOCATION OF THE EQUIPMENT
 IS NOT SHOWN.
 PLEASE PROVIDE THE SCHEDULE OF TIMES AND LISTING OF THE
 CIRCUITS ON THE LIGHTING CONTACTOR AS SHOWN.
 ** PLEASE COORDINATE ALL OF THESE ITEMS AS SHOWN ON THE
 E-SHEET.
 PLEASE ALSO SEE THAT NO PERFORMANCE CALCULATIONS WERE
 SUBMITTED AND NO FIXTURE LEGEND TO COORDINATE WITH THE
 CALCULATIONS AND PLANS.
 13-415.2
 ** PLEASE SEE THE INFORMATION BELOW IN THIS SAME NOTE
 IS TAKEN FROM PREVIOUS REVIEW**
  
 PLEASE SEE FBC 2004 W/2006 REVISIONS AND CHAPTER 13.
 THE ADOPTION OF THE 2004 FBC WAS OCT.1ST, 2005 WHICH
 REQUIRED LIGHTING CONTROLS.
 A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE
 WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED
 LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF
 ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN
 BE DONE.
 PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE
 INDICATE SCHEDULING.(IF A SYSTEM IS INSTALLED) PLEASE
 INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER CODE.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. (
 TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.2 FOR THE PERFORMANCE CALCULATIONS
 WHICH COULD NOT BE LOCATED ON PLANS.
 ALL FIXTURES NEED TO BE SPECIFIED AT THIS TIME FOR
 MINIMUM DESIGN, THESE MAY BE REVISED AT A LATER DATE,
 HOWEVER A REVISION WILL BE REQUIRED TO BE SUBMITTED.
  
 4) NOTE: PLEASE SEE NO REVISIONS WERE MADE TO THE
 APPLIED SCOPE OF WORK WHEN THE SCOPE OF WORK HAS
 INCREASED BASED ON CHANGES ON PLANS.
 RESPONSE FROM ENGINEER STATES THIS IS ADDRESS ON
 ELECTRICAL SHEETS. THIS IS UNCLEAR HOW THE VALUE FOR
 THE SCOPE OF WORK WOULD BE ON PLANS?
  
 ** PREVIOUS REVIEW NOTE ** PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK AS APPLIED WILL NEED TO BE
 REVISED BASED ON THE COMMENT ABOVE (NOTE #4).
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 5) NOTE: PLEASE SEE THE INFORMATION ON THE INSTA-HOT
 WATER HEATER IS NOW PROVIDED WHICH ACTUALLY CONFLICTS
 WITH THE PLANS AS SUBMITTED.
 PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS CLEARLY
 SHOWS THIS UNIT AS A 240V SINGLE PHASE AND THE SERVICE
 IT IS BEING ADDED TO IS A THREE PHASE 120/208V SERVICE.
 THIS IS BEING SHOWN AS A LISTED UNTI FOR 240V NOT
 208V.
 PLEASE SEE THE LOADS DO NOT CORRELATE ON PANEL
 SCHEDULE: FOR EXAMPLE, PLEASE SEE ONLY 28KW IS SHOWN ON
 PANEL SCHEDULE WHEN UNIT IS 28.5 KW ON SPECS/CUT
 SHEETS.
 PLEASE SEE THE LOAD ON THE LOAD CALCULATIONS ALSO DOES
 NOT CORRELATE AS THIS IS SHOWN AS 21KW.
 PLEASE SEE THE MINIMUM OVER CURRENT PROTECTION ON PANEL
 SCHEDULE IS SHOWN AS A 3-POLE 40AMP BREAKER. HOW IS
 THIS POSSIBLE WITH THE LOAD AS SHOWN?
 PLEASE SEE THE SPECS/CUT SHEETS CALL FOR MULTIPLE
 BREAKERS FOR MOST OF THE UNITS AS SHOWN.
 PLEASE INDICATE THE LOCATION OF THIS UNIT.
  
 ** THERE ARE SEVERAL ITEMS ON THIS UNIT WHICH DOES NOT
 AND WILL NOT MEET THE MINIMUM REQUIREMENTS OF THE NEC.
 240.4, 310.16, 422.13, 110.3, 90.7, ETC.
  
 6) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT CORRELATE FOR THE AHU HEAT LOAD.
 THIS WAS A COMMENT ON THE PREVIOUS REVIEW AND STILL
 REMAINS.
 PLEASE SEE THE AHU IS NOW SHOWN AS 5KW, YET THE PANEL
 SCHEDULE ALSO SHOWS ONLY 1.0KW FOR EACH PHASE. HOW IS
 THIS POSSIBLE?
 PLEASE SEE THE LOAD ON THE CU APPEARS TO BE HIGHER
 WHICH IS OK, HOWEVER THE HIGHER OF THE TWO LOADS OF AN
 A/C SYSTEM IS TO BE FIGURED ON THE LOAD CALCULATIONS.
 PLEASE SEE THE PANEL SCHEDULE INDICATES A TOTAL OF 6.6
 KW AND THE LOAD CALCULATIONS INDICATE A LOWER NUMBER
 JUST OVER 4KW.
 PLEASE CORRELATE AS THE LOAD CALCULATIONS AS SHOWN DO
 NOT MEET THE MINIMUM LOADS PER THE NATIONAL ELECTRICAL
 CODE.
 PLEASE CORRELATE ALL OTHER LOADS ON PANEL SCHEDULE WITH
 THAT AS SHOWN IN THE LOAD CALCULATIONS. PLEASE SEE
 ANOTHER FOR EXAMPLE: SIGN CIRCUITS PER 600.5, SCHEDULE
 SHOWS THE CORRECT 1200VA FOR EACH HOWEVER THE
 CALCULATIONS ONLY INCLUDE ONE.
 PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN
 AND FIGURED AT 125%.
 PLEASE SEENEC 220AND COORDINATE AS THERE ARE
 SEVERAL SECTIONS OF 220 WHICH APPLY.
 215.3, 230.42 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE THE RECEPTACLE NEXT TO THE SINK IN
 AREA NEXT TO BATHROOM IS NOT GFI AS REQUIRED PER
 210.8B
  
 8) NOTE: PLEASE SEE THE OWNER INFORMATION AS STATED ON
 PERMIT APPLICATION IS NOT CORRECT AND THIS INFORMATION
 NEEDS TO BE UPDATE ON PERMIT APPLICATION. THIS THE SAME
 COMMENT AS NO INFORMATION WAS CHANGED.
  
 9) NOTE: PLEASE KNOW DUE TO THE EXTENT OF THE COMMENTS,
 PERMIT APPLICATION AND SUBMITTED INFORMATION, MOST OF
 THESE DOCUMENTS WILL BE RETAINED BY THIS OFFICE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE SAME SHEETS AS ALL TRADES ARE
 BEING SHOWN ON THE SAME PAGE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2007-06-09 Time 20:23 Sent To  
Notes
2007-06-10 08:55:32** UNSAT **
  
  
 ** PLEASE KNOW AS THERE AREITEMS ON PLANS WHICH WERE
 NOT SUBMITTED IN THE DESIGN FOR REVIEW, A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
 PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE
 RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE
 CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS
 OF DECEMBER 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON
 ARCHITECTURAL/ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE FS 481.229 AS A DRAFTING FIRM MAY
 NOT PRODUCE DOCUMENTS FOR THIS SCOPE OF WORK. THE
 ENGINEER AS STATED ON PLANS IS NOTED AS CIVIL AND
 STRUCTURAL, PLEASE SEE FS 471.025 FOR SCOPE OF WORK
 PERMITTED UNDER SPECIFIC LICENSE AND SCOPE OF
 KNOWLEDGE.
 PLEASE CONTACT THE STATE BOARD OF ENGINEERS FOR FURTHER
 QUESTIONS FOR THE SCOPE OF WORK UNDER ENGINEER. PLEASE
 CONTACT THE STATE BOARD OF ARCHITECTS LEGAL COUNSEL FOR
 ANY FURTHER QUESTIONS.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL RISER AS SHOWN ON
 PLANS DOES NOT CORRELATE WITH THE ACTUAL SERVICE AT
 LOCATION OF JOBSITE. PLEASE SHOW SERVICE AT LOCATION OF
 THIS BUILDING.
 FBC 106.1.2, 106.3.5.1.2
 NEC 215.5
  
 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST,
 2005 WHICH REQUIRED LIGHTING CONTROLS.
 A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE
 WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED
 LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF
 ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN
 BE DONE.
 PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE
 INDICATE SCHEDULING.(IF A SYSTEM IS INSTALLED) PLEASE
 INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER CODE.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. (
 TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.2 FOR THE PERFORMANCE CALCULATIONS
 WHICH COULD NOT BE LOCATED ON PLANS.
 ALL FIXTURES NEED TO BE SPECIFIED AT THIS TIME FOR
 MINIMUM DESIGN, THESE MAY BE REVISED AT A LATER DATE,
 HOWEVER A REVISION WILL BE REQUIRED TO BE SUBMITTED.
  
 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS APPLIED WILL NEED TO BE REVISED BASED ON THE
 COMMENT ABOVE (NOTE #4).
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 6) NOTE:PLEASE SEE PANEL SCHEDULE SHOWS A 60AMP
 BREAKER ON #8 CONDUCTORS FOR INSTA-HOT, THESE
 CONDUCTORS ARE NOT RATED PER 110.14, 240.4, 310.16
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT CORRELATE FOR THE AHU HEAT LOAD.
 5KW OR 8KW?
 PLEASE SEE220AND COORDINATE.
 FBC 106.1.2S
  
 8) NOTE: PLEASE SUBMIT REVISED LOAD CALCULATIONS AS THE
 LOADS FOR INSTA-HOT HAVE NOT BEEN FIGURED INTO THE
 CALCULATIONS AS SHOWN.215.5, 215.3, 220, FBC
 106.3.5.1.2
 PLEASE ALSO SEE MISSING LOADS FOR SHOW WINDOWS PER THE
 NEXT COMMENT #9. 220.44/220.14
 PLEASE ALSO SEE COMMENT FOR MISSING SIGN CIRCUIT AND
 LOADS NOT SHOWN.
  
 9) NOTE: PLEASE SEE MISSING SHOW/DISPLAY WINDOW
 RECEPTACLES WHICH WILL BE REQUIRED PER 210.62
  
 10) NOTE: PLEASE SEE MISSING SIGN CIRCUIT EITHER NEW OR
 EXISTING PER 600.5
  
 11) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE THERE ARE FIXTURES AND J-BOXES WITH NO CIRCUITS, NO
 CONTROLS FOR LIGHTING (SEE NOTE#4) AND RECEPTACLES WITH
 NOT CIRCUITS.
 PLEASE COMPLETE SW-LEGS FOR LIGHTING CONTROLS. PLEASE
 SEE 408.4.
 PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO
 ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED. THE
 USE OF *LIGHTING OR RECEPTACLES* IS NOT ACCEPTABLE PER
 CODE.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC 408.4.
  
 *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.*
  
 PLEASE ALSO SEE THE NEC 2005 HANDBOOK WHICH CONTAINS A
 MORE EXTENSIVE COMMENTARY FOR THIS SAME SECTION.
  
 12) NOTE: PLEASE SEE THE OWNER INFORMATION AS STATED ON
 PERMIT APPLICATION IS NOT CORRECT AND THIS INFORMATION
 NEEDS TO BE UPDATE ON PERMIT APPLICATION.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE SAME SHEETS AS ALL TRADES ARE
 BEING SHOWN ON THE SAME PAGE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-10 08:28:162007-06-10 08:28:16
 REVIEW IN PROGRESS
2007-06-09 20:32:152007-06-09 20:32:15
 REVIEW TO CONTINUE ON 6/10
 NOTES TO FOLLOW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2007-11-06 Cont ID  
Sent By mwennerg Date 2007-11-06 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2007-11-06 Time 13:42 Sent To  
Notes
2007-11-06 13:45:26PLANS APPROVED ON 8/27/07 AND NEW SHEET STAMPED ON THIS
 DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-08-27 Time 12:43 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 12:30 Sent To  
Notes
2007-08-27 12:40:55*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND
 DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 15:16 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 15:05 Sent To  
Notes
2007-06-20 15:13:31*****UNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL OF AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF ( INCLUDING STREETS, ROADS, ALLEYS,
 FIRE LANES).
  
 3.SHOW THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) FOR THIS TENANT
 SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 16:10 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 16:10 Sent To  
Notes
2007-10-30 14:41:11TO "BOB"#4
2007-10-23 16:12:36WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-21 Cont ID  
Sent By adarroug Date 2007-09-21 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-09-21 Time 14:44 Sent To  
Notes
2007-10-01 14:32:58TO "BOB"#5
2007-09-21 14:44:58WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 18:02 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 18:02 Sent To  
Notes
2007-08-08 19:42:48TO BOB BOARD #17
2007-07-28 18:02:45WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 15:05 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 14:58 Sent To  
Notes
2007-06-05 14:44:11TO "BOB"#12
2007-06-01 15:02:31WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-11-07 Cont ID  
Sent By jleech Date 2007-11-07 Time 07:35 Rev Time 0.00
Received By jleech Date 2007-11-07 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-20 Cont ID  
Sent By jleech Date 2007-10-20 Time 11:29 Rev Time 0.00
Received By jleech Date 2007-10-20 Time 11:29 Sent To  
Notes
2007-10-20 12:14:49DENIED;
 FROM PAST REVIEW;
 1. NO YES NOTE SHOWING VACUUM BREAKER CODES HELPS BUT
 DOES NOT SHOW WERE REQUIRED. ALSO 608.15.4.1 REFURS TO
 MANUFACTURE'S INSTRUCTIONS. (NOT SHOWN ON CUT SHEETS
 PROVIDED) ADD NOT TO WATER RISER DIAGRAM "VACUUM
 BREAKERS REQUIRED HERE" WITH AN ARROW.
 2. OK
 3.NO THE ADA DETAILS SHOWN DO NOT REFLECT THE FLOOR
 PLAN. SHOW ONLY THE ADA DRINKING FOUNTAIN. THE BATHROOM
 DETAIL SHOWN DOES NOT REFLECT THE FLOOR PLAN.
 FROM LAST REVIEW;
 4.(F)ONE DRINKING FOUNTAIN IS PERMITED WITH A CUP
 DISPENSOR INSTALLED. ( SHOW DISPENSOR ON PLANS)
 5. NO SINK NOT SHOWN ON RISER DIAGRAMS SANITARY AND
 WATER. ALSO THE FLOOR PLAN SHOWS A 36" PLUMBERS WALL
 FOR SHAMPOO SINKS BUT SANITARY RISER DIAGRAM SHOWS
 SINKS ARE VENTED INTO THE CEILING. PLEASE CORRECT.
 6. OK
 NEW COMMENTS;
 7.IS SINK, BEING MOVED, A BREAK SINK OR A WORK SINK? IF
 A BREAK SINK IT MUST MEET ADA REQUIREMENTS ( SINCE IT
 IS BEING RELOCATED) FBC BUILDING SECTIONS 11-4.24.1
 THRU 11-4.24.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-21 Cont ID  
Sent By mperson Date 2007-08-21 Time 08:14 Rev Time 0.00
Received By mperson Date 2007-08-21 Time 08:14 Sent To  
Notes
2007-08-21 10:16:52DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO/OK** WATER RISER REQUIRED. FBC-2004
 ADMINISTRATION CODE SECTION 106.3.5.1(3).
 NOTE: THE RESUBMITTED WATER RISER DIAGRAM NEED TO
 INDICATE THE REQUIRED ATMOSPHERIC VACUUM BREAKERS PER
 FBC-2004 PLUMBING SECTION 608.13.6 FOR THE PROPOSED
 PORTABLE SHAMPOO CHAIRS W/SINK. THEY NEED TO BE LOCATED
 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE SHAMPOO SINKS
 AND NOTED AS SUCH ON THE WATER RISER.
  
 2. **OK**
  
 3. **NO** SHOW ON THE PLAN COMPLIANCE WITH THE
 ACCESSIBILITY CODEBUILDING CHAPTER 11 SECTION
 11-4.1.6(2) 20% RULE.
 NOTE: PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE
 RESUBMITTED PLANS PER FBC-2004 CHAPTER 11.
  
 **WATER CLOSETS
 A} 11-4.16 WATER CLOSETS, ELEVATION DETAIL REQUIRED.
  
 B} 11-4.16.2 CLEAR FLOOR SPACE.(ALSO INDICATE ON FLOOR
 PLAN SHEET A-1)
  
 C} 11-4.16.3 HEIGHT.
  
 D} 11.4.16.4 GRAB BARS.
  
 E} 11-4.16.5 FLUSH CONTROLS.
  
 F} 11-4.16.6 DISPENSERS.
  
 **LAVATORIES AND MIRRORS
 A} 11-4.19 LAVATORIES, ELEVATION DETAIL REQUIRED.
  
 B} 11-4.19.2 HEIGHT AND CLEARANCES.
  
 C} 11-4.19.3 CLEAR FLOOR SPACE.(ALSO INDICATE ON FLOOR
 PLAN SHEET A-1)
  
 D} 11-4.19.4 EXPOSED PIPES AND SURFACES.
  
 E} 11-4.19.5 FAUCETS.
  
 F} 11-4.19.6 MIRRORS.
  
 **THE FOLLOWING ARE NEW ITEMS:
  
 4. PER FBC-2004 PLUMBING, TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED AND MUST BE ADA COLMPLIANT PER
 FBC-2004 CHAPTER 11.
  
 A} 11-4.15 DRINKING FOUNTAIN, ELEVATION DETAIL
 REQUIRED.
  
 B} 11-4.15.2 SPOUT HEIGHT.
  
 C} 11-4.15.3 SPOUT LOCATION.
  
 D} 11-4.15.4 CONTROLS.
  
 E} 11-4.15.5 CLEARANCES.(ALSO INDICATE CLEAR FLOOR
 SPACE ON FLOOR PLAN SHEET A-1)
  
 F} 11-4.1.3(10)(A)WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 5. SHEET A-1 SANITARY RISER DIAGRAM: THE RESUBMITTED
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE
 BATHROOM. PER 106.1.1 RISER DIAGRAM SHALL REFLECT THE
 FLOOR PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS
 INDICATING THIS AND CORRECT FOR THE RESUBMITTAL.
  
 6. SHEET A-1 SANITARY RISER DIAGRAM: THE WATER CLOSET
 DOES NOT NEED A TRAP IT HAS AN INTEGRAL TRAP. PER
 FBC-2004 PLUMBING SECTION 1002.1 A FIXTURE SHALL NOT BE
 DOUBLE TRAPPED.
  
 7. SHEET A-1 SANITARY RISER DIAGRAM: A VENT IS
 REQUIRED FOR THE PROPOSED PORTABLE SHAMPOO CHAIRS
 W/SINKS PER FBC-2004 PLUMBING SECTION 901.2.1.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED, PLEASE
 INCLUDE A TRANSMITTAL LETTER INDICATING HOW EACH ITEM
 WAS ADDRESSED AND PROVIDE ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By jleech Date 2007-06-19 Time 07:39 Rev Time 0.00
Received By jleech Date 2007-06-19 Time 07:39 Sent To  
Notes
2007-06-19 07:55:46DENIED;
 1. WATER RISER REQUIRED. FBC-2004 ADMINISTRATION CODE
 SECTION 106.3.5.1.3(3).
 2. SUBMIT MANUFACTURE CUT SHEETS FOR ELECTRIC WATER
 HEATER AND PORTABLE SHAMPOO CHAIRS/ WITH SINK.
 3. SHOW ON PLAN COMPLIANCE WITH THE ACCESSIBILITY CODE
 BUILDING CHAPTER 10 SECTION 11-4.1.6(2) 20% RULE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-05 Cont ID  
Sent By astelly Date 2007-11-05 Time 11:45 Rev Time 0.00
Received By astelly Date 2007-11-05 Time 11:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-15 Cont ID  
Sent By astelly Date 2007-10-15 Time 19:11 Rev Time 0.00
Received By astelly Date 2007-10-15 Time 19:11 Sent To  
Notes
2007-10-15 19:08:31AMY STELLY
 URBAN DESIGN
 822-1440
  
 A SURVEY WAS NOT INCLUDED FOR REVIEW. PLEASE INCLUDE IN
 YOUR NEXT SUBMISSION. THERE ARE CONCERNS REGARDING THE
 DOOR SWINGING INTO THE RIGHT-OF-WAY.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-06-14 Cont ID  
Sent By astelly Date 2007-06-14 Time 09:45 Rev Time 0.00
Received By astelly Date 2007-06-14 Time 09:45 Sent To  
Notes
***NONE***