| 2007-08-10 21:13:15 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL NEEDING TO BE ADDRESSED ALONG WITH NEW COMMENTS |
| | DUE TO CHANGES ON PLANS AND NEW INFORMATION ONLY NOW |
| | SUBMITTED FOR REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE A FOUR TIMES THE PERMIT FEE WAS |
| | ASSESSED FOR COMMENCING WORK WITHOUT PERMITS AS |
| | REQUIRED PER FBC 105.1 AND 108.4 |
| | PLEASE KNOW THE BALANCE IS DUE AT THIS TIME. THE |
| | CONTRACTOR WAS CONTACTED AND INFORMATION OF THIS AS OF |
| | THIS REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE SCOPE OF WORK BEING |
| | APPLIED FOR IS APPLIED UNDER OF CERTIFIED RESIDENTIAL |
| | CONTRACTOR (CRC) WHICH DOES NOT PERMIT THIS LICENSE TO |
| | DO WORK IN A COMMERCIAL BUILDING. THIS WAS CONFIRMED |
| | WITH THE PALM BEACH COUNTY LICENSING BOARD AS WELL AS |
| | WITH INFORMATION WITH THE STATE OF FLORIDA LICENSING |
| | BOARD. PLEASE APPLY UNDER A LICENSE WHICH PERMITS THIS |
| | SCOPE OF WORK OR PLEASE KNOW THIS PERMIT WILL BE |
| | REQUIRED TO BE APPLIED FOR UNDER LICENSE CONTRACTOR |
| | WHOM CAN PERFORM THIS WORK. |
| | PLEASE KNOW A MESSAGE WAS LEFT FOR THE CONTRACTOR BY |
| | THE INSPECTION SERVICES MANAGER FOR THE QUALIFIER TO |
| | CONTACT THIS OFFICE. |
| | CHAPTER 67-1876 AS AMENDED BY THE PALM BEACH COUNTY |
| | LICENSING BOARD. |
| | FLORIDA STATUTES 489 |
| | |
| | 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE NOW COMING |
| | IN UNDER A NEW DESIGNER AND THE DESIGNER OF RECORD AS |
| | SHOWN IS PERMITTED TO DESIGN THE SCOPE AS SHOWN HOWEVER |
| | THE PLANS MUST CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS AND DEISGN. |
| | FS 489, 468 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS REVIEW |
| | PLEASE INDICATE THE MAXIMUM TIMES ON OVER RIDES DEVICES |
| | AS REQUIRED PER 13-415.1.ABC.1.1 OF THE FBC. THIS WOULD |
| | BE FOR ALL DEVICES. ONLY TWO SHOWN ON DETAIL, YET PLANS |
| | INDICATE MORE. |
| | PLEASE ALSO SEE MISSING CONTROLS FOR SEPARATE SPACES |
| | PER 13-415.1.ABC.1.1 AND .1.2. THESE ARE SHOWN AS |
| | STANDARD SWITCHES. |
| | PLEASE SEE THE DETAIL AS SUBMITTED DOES NOT PROVIDE |
| | ENOUGH INFORMATION FOR SCOPE OF LIGHTING CONTROL |
| | SYSTEM. PLEASE SEE THAT THE LOCATION OF THE EQUIPMENT |
| | IS NOT SHOWN. |
| | PLEASE PROVIDE THE SCHEDULE OF TIMES AND LISTING OF THE |
| | CIRCUITS ON THE LIGHTING CONTACTOR AS SHOWN. |
| | ** PLEASE COORDINATE ALL OF THESE ITEMS AS SHOWN ON THE |
| | E-SHEET. |
| | PLEASE ALSO SEE THAT NO PERFORMANCE CALCULATIONS WERE |
| | SUBMITTED AND NO FIXTURE LEGEND TO COORDINATE WITH THE |
| | CALCULATIONS AND PLANS. |
| | 13-415.2 |
| | ** PLEASE SEE THE INFORMATION BELOW IN THIS SAME NOTE |
| | IS TAKEN FROM PREVIOUS REVIEW** |
| | |
| | PLEASE SEE FBC 2004 W/2006 REVISIONS AND CHAPTER 13. |
| | THE ADOPTION OF THE 2004 FBC WAS OCT.1ST, 2005 WHICH |
| | REQUIRED LIGHTING CONTROLS. |
| | A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE |
| | WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED |
| | LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF |
| | ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN |
| | BE DONE. |
| | PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE |
| | INDICATE SCHEDULING.(IF A SYSTEM IS INSTALLED) PLEASE |
| | INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER CODE. |
| | PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. ( |
| | TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | B) PLEASE SEE 13-415.2 FOR THE PERFORMANCE CALCULATIONS |
| | WHICH COULD NOT BE LOCATED ON PLANS. |
| | ALL FIXTURES NEED TO BE SPECIFIED AT THIS TIME FOR |
| | MINIMUM DESIGN, THESE MAY BE REVISED AT A LATER DATE, |
| | HOWEVER A REVISION WILL BE REQUIRED TO BE SUBMITTED. |
| | |
| | 4) NOTE: PLEASE SEE NO REVISIONS WERE MADE TO THE |
| | APPLIED SCOPE OF WORK WHEN THE SCOPE OF WORK HAS |
| | INCREASED BASED ON CHANGES ON PLANS. |
| | RESPONSE FROM ENGINEER STATES THIS IS ADDRESS ON |
| | ELECTRICAL SHEETS. THIS IS UNCLEAR HOW THE VALUE FOR |
| | THE SCOPE OF WORK WOULD BE ON PLANS? |
| | |
| | ** PREVIOUS REVIEW NOTE ** PLEASE SEE THE VALUE FOR |
| | COMPLETE SCOPE OF WORK AS APPLIED WILL NEED TO BE |
| | REVISED BASED ON THE COMMENT ABOVE (NOTE #4). |
| | PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO |
| | INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT |
| | ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED. |
| | |
| | 5) NOTE: PLEASE SEE THE INFORMATION ON THE INSTA-HOT |
| | WATER HEATER IS NOW PROVIDED WHICH ACTUALLY CONFLICTS |
| | WITH THE PLANS AS SUBMITTED. |
| | PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS CLEARLY |
| | SHOWS THIS UNIT AS A 240V SINGLE PHASE AND THE SERVICE |
| | IT IS BEING ADDED TO IS A THREE PHASE 120/208V SERVICE. |
| | THIS IS BEING SHOWN AS A LISTED UNTI FOR 240V NOT |
| | 208V. |
| | PLEASE SEE THE LOADS DO NOT CORRELATE ON PANEL |
| | SCHEDULE: FOR EXAMPLE, PLEASE SEE ONLY 28KW IS SHOWN ON |
| | PANEL SCHEDULE WHEN UNIT IS 28.5 KW ON SPECS/CUT |
| | SHEETS. |
| | PLEASE SEE THE LOAD ON THE LOAD CALCULATIONS ALSO DOES |
| | NOT CORRELATE AS THIS IS SHOWN AS 21KW. |
| | PLEASE SEE THE MINIMUM OVER CURRENT PROTECTION ON PANEL |
| | SCHEDULE IS SHOWN AS A 3-POLE 40AMP BREAKER. HOW IS |
| | THIS POSSIBLE WITH THE LOAD AS SHOWN? |
| | PLEASE SEE THE SPECS/CUT SHEETS CALL FOR MULTIPLE |
| | BREAKERS FOR MOST OF THE UNITS AS SHOWN. |
| | PLEASE INDICATE THE LOCATION OF THIS UNIT. |
| | |
| | ** THERE ARE SEVERAL ITEMS ON THIS UNIT WHICH DOES NOT |
| | AND WILL NOT MEET THE MINIMUM REQUIREMENTS OF THE NEC. |
| | 240.4, 310.16, 422.13, 110.3, 90.7, ETC. |
| | |
| | 6) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD |
| | CALCULATIONS DO NOT CORRELATE FOR THE AHU HEAT LOAD. |
| | THIS WAS A COMMENT ON THE PREVIOUS REVIEW AND STILL |
| | REMAINS. |
| | PLEASE SEE THE AHU IS NOW SHOWN AS 5KW, YET THE PANEL |
| | SCHEDULE ALSO SHOWS ONLY 1.0KW FOR EACH PHASE. HOW IS |
| | THIS POSSIBLE? |
| | PLEASE SEE THE LOAD ON THE CU APPEARS TO BE HIGHER |
| | WHICH IS OK, HOWEVER THE HIGHER OF THE TWO LOADS OF AN |
| | A/C SYSTEM IS TO BE FIGURED ON THE LOAD CALCULATIONS. |
| | PLEASE SEE THE PANEL SCHEDULE INDICATES A TOTAL OF 6.6 |
| | KW AND THE LOAD CALCULATIONS INDICATE A LOWER NUMBER |
| | JUST OVER 4KW. |
| | PLEASE CORRELATE AS THE LOAD CALCULATIONS AS SHOWN DO |
| | NOT MEET THE MINIMUM LOADS PER THE NATIONAL ELECTRICAL |
| | CODE. |
| | PLEASE CORRELATE ALL OTHER LOADS ON PANEL SCHEDULE WITH |
| | THAT AS SHOWN IN THE LOAD CALCULATIONS. PLEASE SEE |
| | ANOTHER FOR EXAMPLE: SIGN CIRCUITS PER 600.5, SCHEDULE |
| | SHOWS THE CORRECT 1200VA FOR EACH HOWEVER THE |
| | CALCULATIONS ONLY INCLUDE ONE. |
| | PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN |
| | AND FIGURED AT 125%. |
| | PLEASE SEENEC 220AND COORDINATE AS THERE ARE |
| | SEVERAL SECTIONS OF 220 WHICH APPLY. |
| | 215.3, 230.42 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE RECEPTACLE NEXT TO THE SINK IN |
| | AREA NEXT TO BATHROOM IS NOT GFI AS REQUIRED PER |
| | 210.8B |
| | |
| | 8) NOTE: PLEASE SEE THE OWNER INFORMATION AS STATED ON |
| | PERMIT APPLICATION IS NOT CORRECT AND THIS INFORMATION |
| | NEEDS TO BE UPDATE ON PERMIT APPLICATION. THIS THE SAME |
| | COMMENT AS NO INFORMATION WAS CHANGED. |
| | |
| | 9) NOTE: PLEASE KNOW DUE TO THE EXTENT OF THE COMMENTS, |
| | PERMIT APPLICATION AND SUBMITTED INFORMATION, MOST OF |
| | THESE DOCUMENTS WILL BE RETAINED BY THIS OFFICE. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT THE SAME SHEETS AS ALL TRADES ARE |
| | BEING SHOWN ON THE SAME PAGE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |