| 2007-07-02 18:06:06 | PROJECT: 800 45TH STREET |
| | |
| | PROJECT WORK SCOPE: REMOVE EXISTING SCREEN ENCLOSURE/ |
| | CONSTRUCT BEDROOM & BATH |
| | |
| | PLAN REVIEW: 2004 FLORIDA EXISTING BUILDING CODE AND |
| | FLORIDA BUILDING CODE WITH 2006 REVISIONS. |
| | |
| | STATUS: DENIED |
| | |
| | |
| | PLAN REVIEW COMMENTS: |
| | |
| | 1)105.8 NOTICE OF COMMENCEMENT. |
| | AS PER SECTION 713.135, FLORIDA STATUTES, WHEN ANY |
| | PERSON APPLIES FOR A BUILDING PERMIT, THE AUTHORITY |
| | ISSUING SUCH PERMIT SHALL PRINT ON THE FACE OF EACH |
| | PERMIT CARD IN NO LESS THAN 18-POINT, CAPITALIZED, |
| | BOLDFACED TYPE:?WARNING TO OWNER: YOUR FAILURE TO |
| | RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR |
| | PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU |
| | INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR |
| | AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF |
| | COMMENCEMENT.? |
| | |
| | 2) INITIAL AND SIGN THE OWNER BUILDER INFORMATION |
| | FORM. |
| | |
| | 3) PROVIDE SUPPORTING DOCUMENTATION VERIFYING THE |
| | EXISTING SIZE OF THE MONOLITHIC FOUNDATION AND |
| | REINFORCING STEEL PLACEMENT. INDICATE CONCRETE |
| | SPECIFICATIONS OF NEW FLOOR SLAB OVERLAY. |
| | |
| | 4) PLEASE PROVIDE PRODUCT APPROVALS AND SPECIFICATIONS |
| | FOR ALL MECHANICAL CONNECTORS AND ANCHORS TO BE |
| | UTILIZED. |
| | |
| | 5) PLEASE INDICATE SPECIES AND GRADE OF LUMBER. |
| | |
| | 6) PROVIDE THE FOLLOWING INFORMATION: |
| | |
| | A) WINDOW TYPE AND GLAZING SPECS. |
| | B) DOOR SPECIFICATIONS/ DESIGN PRESSURE. |
| | C) NEW DOOR AT PLAYROOM SHOWS A WINDOW. THE |
| | SUBMITTED PRODUCT APPROVAL DOES NOT REFLECT THE SAME. |
| | D) REQUIRE 2 COPIES OF DOOR AND WINDOW PRODUCT |
| | APPROVALS. |
| | |
| | |
| | 7) THE OBS WINDOW AT THE BATHROOM SHALL BE SAFETY |
| | TEMPERED GLAZING AS PER THE FOLLOWING: |
| | |
| | 2406.3 HAZARDOUS LOCATIONS. |
| | THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| | LOCATIONS REQUIRING SAFETY GLAZING MATERIALS: |
| | |
| | 5. GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, |
| | WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS. |
| | GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING |
| | THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE |
| | GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A |
| | STANDING SURFACE. |
| | |
| | 8) PLEASE SHOW ALL EXTERIOR ELEVATIONS. |
| | |
| | 9) SMOKE ALARMS SHALL BE INSTALLED PER THE FOLLOWING: |
| | |
| | 604.4.3SMOKE ALARMS. |
| | INDIVIDUAL SLEEPING UNITS AND INDIVIDUAL DWELLING UNITS |
| | IN ANY WORK AREA IN GROUP R-1, R-2, R-3, R-4, AND I-1 |
| | OCCUPANCIES SHALL BE PROVIDED WITH SMOKE ALARMS IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| | EXCEPTION: INTERCONNECTION OF SMOKE ALARMS OUTSIDE OF |
| | THE REHABILITATION WORK AREA SHALL NOT BE REQUIRED. |
| | |
| | 10) PLEASE SHOW AN INTERIOR WALL FRAMING SECTION. |
| | |
| | 11) ALL OPENINGS SHALL BE PROTECTED. PLEASE PROVIDE |
| | SHUTTER PRODUCT APPROVALS. |
| | |
| | 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| | ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING DOORS) OR |
| | MIAMI-DADE TAS 201, 202 AND 203 OR AAMA 506 REFERENCED |
| | THEREIN AS FOLLOWS: |
| | 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF |
| | GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| | TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | 3. STORAGE SHEDS THAT ARE NOT DESIGNED FOR HUMAN |
| | HABITATION AND THAT HAVE A FLOOR AREA OF 720 SQUARE |
| | FEET (67 M2) OR LESS ARE NOT REQUIRED TO COMPLY WITH |
| | THE MANDATORY WINDBORNE DEBRIS IMPACT STANDARDS OF THIS |
| | CODE. |
| | 4. OPENINGS IN SUNROOMS, BALCONIES OR ENCLOSED PORCHES |
| | CONSTRUCTED UNDER EXISTING ROOFS OR DECKS ARE NOT |
| | REQUIRED TO BE PROTECTED PROVIDED THE SPACES ARE |
| | SEPARATED FROM THE BUILDING INTERIOR BY A WALL AND ALL |
| | OPENINGS IN THE SEPARATING WALL ARE PROTECTED IN |
| | ACCORDANCE WITH SECTION 1609.1.4 ABOVE. SUCH SPACES |
| | SHALL BE PERMITTED TO BE DESIGNED AS EITHER PARTIALLY |
| | ENCLOSED OR ENCLOSED STRUCTURES. |
| | |
| | 12) THE PROPOSED CONSTRUCTION VALUE APPEARS TO BE LOW |
| | AS PER THE MARSHAL AND SWIFT COST ESTIMATION. |
| | |
| | PLAN REVIEW: KEN CONRAD |
| | |
| | PHONE: 561.805.6666 |
| | E-MAIL: KCONRAD@ WPB.ORG |