Plan Review Details - Permit 07051094
Plan Review Stops For Permit 07051094
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-17 Cont ID  
Sent By mjacobs Date 2007-07-17 Time 07:26 Rev Time 0.00
Received By mjacobs Date 2007-07-17 Time 06:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-10 Cont ID  
Sent By mjacobs Date 2007-07-10 Time 07:57 Rev Time 0.00
Received By mjacobs Date 2007-07-10 Time 07:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-16 Cont ID  
Sent By mjacobs Date 2007-06-16 Time 12:53 Rev Time 0.00
Received By mjacobs Date 2007-06-15 Time 16:41 Sent To  
Notes
2007-06-16 12:53:26BUILDING PLAN REVIEW
 PERMIT: 07051094
 ADD: 1901 S.FLAGLER DR
 CONT: PRETI CONSTRUCTION, INC
 TEL: (561)840-9949
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
  
 3)INDICATE THE ALTERATION-LEVEL PER 2004 FLORIDA
 EXISTING BUILDING CODE CH.3
  
 4)INDICATE THE SLOPE /LENGTH AND WIDTH OF THE RAMP.
 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR
 WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
  
 5)11-4.5.1 GROUND AND FLOOR SURFACES ALONG ACCESSIBLE
 ROUTES AND IN ACCESSIBLE ROOMS AND SPACES INCLUDING
 FLOORS, WALKS, RAMPS, STAIRS, AND CURB RAMPS, SHALL BE
 STABLE, FIRM, SLIPRESISTANT, AND SHALL COMPLY WITH
 SECTION 11-4.5 .
  
 6)THE HANDRAILS SHALL MEET THE REQUIREMENTS OF FBC.
 11-4.8.5
  
 7)11-4.24.1 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24 . SHOW
 CONPLIANCE.
  
 8)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO COPIES OF THE
 PRODUCT APPROVALS FOR THE 8 INCH LINTEL.
  
 9)ADDITIONAL STRUCTURAL INFORMATION IS REQUIRED FOR
 THE WALL SECTION WHERE THE SINGLE DOOR AND WALL WILL BE
 REMOVED. SHOW THE STRUCTURAL SUPPORT OF THE WALL. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER DATA NECESSARY TO DESCRIBE
 THE CONSTRUCTION OR INSTALLATION AND THE BASIS OF
 CALCULATIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-27 Cont ID  
Sent By dpalmer Date 2007-06-27 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2007-06-27 Time 20:07 Sent To  
Notes
2007-06-27 20:11:00ELECTRICAL SHEETS STAMPED. OK.
 HIGHLIGHTED OS DEVICES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2007-06-10 Time 09:02 Sent To  
Notes
2007-06-10 09:18:47** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE
 CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS
 OF DECEMBER 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON
 ARCHITECTURAL/ELECTRICAL PLANS.
  
 2) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORNS,
 STROBES OR COMBO DEVICES TO MEET ADA 11-4.28.1, 2 AND
 .3(4).
  
 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13. 13-101 AS IF THE SQ FT FOR BUILDING IS 5K
 SQ FT, THEN ONLY THE DEVICES/SWITCHES AS SHOWN ON PLANS
 WILL BE REQUIRED TO MEET AUTOMATED CONTROLS.
 PLEASE STATE THE DEVICE TYPE AND MAXIMUM ALLOWED
 TIMES.
 ( TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
  
  
 4) NOTE11) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS
 AND CORRELATE WITH A SUBMITTED PANEL SCHEDULE. PLEASE
 SEE THERE ARE ROOMS AND AREAS WHERE FIXTURES DO NOT
 INDICATE CIRCUITS, NO CONTROLS FOR LIGHTING (SEE
 NOTE#3)
 PLEASE COMPLETE SW-LEGS FOR LIGHTING CONTROLS.
 PLEASE SEE 408.4.
 LS 101 7.8, 7.9
  
 5) NOTE: PLEASE LABEL NEW ROOM WHICH INDICATES THE
 ELECTRICAL PANEL AND TIME CLOCK. 110.26, 408.7 ETC
 THE DOOR WILL BE REQUIRED TO CONTAIN A SIGN FOR *NO
 STORAGE*ELECTRICAL ROOM* OR WORDS TO THAT AFFECT. THE
 FIRE MARSHAL HAS TYPICAL WORDING USED, PLEASE CALL TO
 OVER IF NEEDED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-17 Cont ID  
Sent By mawillia Date 2007-07-17 Time 19:10 Rev Time 0.00
Received By mawillia Date 2007-07-17 Time 18:59 Sent To B1
Notes
2007-07-17 19:08:30*****REVISIONS APPROVED*****
  
  
 REVISED PLAN SHEET A-1 APPROVED;NO FIRE STAMP NEEDED
 AS PREVIOUSLY (07/09/07) FIRE-STAMPED SHEET A-2 WAS NOT
 AFFECTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-09 Cont ID  
Sent By mawillia Date 2007-07-09 Time 11:15 Rev Time 0.00
Received By mawillia Date 2007-07-09 Time 10:58 Sent To  
Notes
2007-07-09 11:11:39*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET A-2 STAMPED, INITIALED, AND
 DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 00:52 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 23:55 Sent To  
Notes
2007-06-21 00:47:57*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, THE LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.PLEASE INDICATE IF THE BUILDING(S) OR PORTION OF
 THE BUILDING(S) IS/ARE TO BE OCUPIED DURINGTHE SCOPE
 OF WORK.IF SO, THEY SHALL BE PERMITTEDTO BE
 OCCUPIED ONLY WHERE THE REQUIRED MEANS OF EGRESS AND
 REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 CONTINUOUSLY MAINTAINED.
  
 5.INDICATE IF THE BUILDING(S) SPRINKLERED.IF THE
 SCOPE OF WORK CAUSES MODIFICATION TO THE SPRINKLER
 SYSTEM, SEPARATE PLANS AND PERMIT SHALLL BE REQUIRED.
  
 6.SEPARATE PLANS AND PERMIT SHALL BE REQUIRED FOR THE
 FIRE ALARM REMODEL.
  
 7.IN THE ELECTRICAL FIXTURE QUANTITY SCHEDULE ON
 DRAWING A-2, IT LISTS THAT NO NEW SMOKE DETECTORS WILL
 BE ADDED.HOWEVER A NEW SMOKE DETECTOR (NSD) IS SHOWN
 ON THE PROPOSED FIRST FLOOR CEILING PLAN.
  
 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALLS TO BE ERECTED AS CLASS A,CLASS B , OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 14:11 Sent To  
Notes
2007-07-13 14:00:31TO "BOB"#10
2007-07-12 14:11:59WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-26 Cont ID  
Sent By adarroug Date 2007-06-26 Time 16:29 Rev Time 0.00
Received By adarroug Date 2007-06-26 Time 16:29 Sent To  
Notes
2007-06-27 10:51:46TO "BOB"#11
2007-06-26 16:30:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 00:53 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 15:25 Sent To  
Notes
2007-06-05 14:43:49TO "BOB"#17
2007-06-01 15:25:57WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-09 Cont ID  
Sent By jleech Date 2007-07-09 Time 09:28 Rev Time 0.00
Received By jleech Date 2007-07-09 Time 09:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By jleech Date 2007-06-20 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-06-20 Time 07:14 Sent To  
Notes
2007-06-20 07:20:22DENIED;
 1. PLEASE REFORENCE CODES PLANS ARE UNDER .
 2. NOT ENOUGH INFORMATION; IS NEW LAVATORY TO HAVE HOT
 AND COLD WATER? IF SO PLEASE SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695