Plan Review Details - Permit 07051090
| Plan Review Stops For Permit 07051090 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-01 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-01 |
Time |
18:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-06-29 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-29 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2007-06-29 18:18:49 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS FS471.025 (HILLMAN ENGINEERING INC.). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-19 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-19 |
Time |
11:40 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-15 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-15 |
Time |
11:57 |
Sent To |
G |
|
| Notes |
| 2007-06-15 12:05:36 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | | 108.1 FBC. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-07-27 |
Time |
15:06 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-07-27 |
Time |
15:06 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-06-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-06-27 |
Time |
09:48 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-06-27 |
Time |
09:48 |
Sent To |
B |
|
| Notes |
| 2007-06-27 10:07:11 | DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. THE VALUE IS TO LOW FOR THE PROPOSED GENERATOR. | | | PER FBC-2004, CHAPTER 1, SECTION | | | 108.3, BUILDING PERMIT VALUATION: IF IN | | | THE OPINION OF THE BUILDING OFFICIAL, | | | THE CLAIMED VALUATION OF THE BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS | | | TO BE UNDERESTIMATED ON THE APPLICATION, | | | THE PERMIT SHALL BE DENIED. FOR | | | PERMITTING PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, NORMAL SITE WORK (EXCAVATION AND | | | BACKFILL FOR BUILDINGS), ARCHITECTURAL | | | AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND | | | VALUE. VALUATION REFERENCES MAY INCLUDE | | | THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS ECT.) WITH | | | REGIONAL ADJUSTMENTS FOR LOCATION AS | | | PUBLISHED BY INTERNATIONAL CODE | | | CONGRESS. | | | NOTE: PLEASE ADJUST THE VALUE AT THE PERMIT'S CLERK | | | DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO | | | RESUBMITTING. | | | | | | 2.A GAS PERMIT CAN NOT BE ISSUED UNTIL | | | A GEN/RES PERMIT APPLICATION HAS BEEN | | | APPLIED FOR AND APPROVED BY ZONING FOR | | | THE GENERATOR LOCATION. | | | NOTE: THE GAS PLANS MAY NEED TO BE REVISED TO REFLECT | | | THE RELOCATION OF THE GENERATOR DUE TOZONING | | | **FAILURE** COMMENTS. | | | | | | 3. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING | | | LENGTHS INDICATED ON THE ISOMETRIC. THE ONLY INDICATED | | | CUT LENGTHS ARE FOR THE UNDERGROUND PE PIPE. PLEASE | | | INDICATE THE ABOVE GROUND PIPING CORRESPONDING LENGTHS | | | ON THE RESUBMITTAL. | | | | | | 4. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL | | | ON THE RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-16 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-16 |
Time |
08:22 |
Sent To |
Z |
|
| Notes |
| 2007-07-16 08:23:11 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-07 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-07 |
Time |
09:04 |
Sent To |
E |
|
| Notes |
| 2007-06-07 09:04:55 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-29 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-01 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2007-06-01 15:29:05 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-27 |
Time |
16:04 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-07-27 |
Time |
16:04 |
Sent To |
B |
|
| Notes |
| 2007-07-27 16:07:14 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE | | | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS | | | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED | | | CLEARANCES AROUND EQUIPMENT FOR | | | SERVICING,AND PROVIDE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-06-15 |
Time |
08:20 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-06-15 |
Time |
08:20 |
Sent To |
E |
|
| Notes |
| 2007-06-15 08:21:23 | *** DENIED *** | | | 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT. | | | | | | 2) PLEASE BE AWARE. PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED EQUIPMENT POWERED BY | | | INTERNAL COMBUSTION ENGINES SHALL BE INSTALLED IN | | | ACCORDANCE WITH MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION | | | ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS) | | | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS | | | IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING | | | COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED | | | WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE | | | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS | | | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL | | | NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT | | | TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT | | | BE DRAWN INTO THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED | | | BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT | | | TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES | | | TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, BUILDING, WINDOWS, | | | DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND | | | EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD | | | INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-17 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-17 |
Time |
08:11 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-04 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-06-04 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-06-04 |
Time |
13:54 |
Sent To |
I |
|
| Notes |
| 2007-06-04 13:57:15 | ***FAILED*** | | | | | | | | | 1)GENERATOR DOES NOT MEET THE REQUIRED REAR SETBACK. | | | THE EDGE OF THE GENERATOR MUST BE AT LEAST 6' AWAY FROM | | | THE REAR PROPERTY LINE. | | | | | | | | | CHRIS HOOPS | | | ZONING TECHNICIAN | | | 561-805-6720 |
|
|
|