Plan Review Details - Permit 07051085
Plan Review Stops For Permit 07051085
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-06-22 Cont ID  
Sent By rmcdouga Date 2007-06-22 Time 14:53 Rev Time 0.00
Received By rmcdouga Date 2007-06-22 Time 14:53 Sent To  
Notes
2007-06-22 14:54:46MILTON GREY BROUGHT IN LETTER STATING THAT EXISTING
 ROOF WAS TILE AND CIRCLED THE FASTENING METHOD ON THE
 NOA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-22 Cont ID  
Sent By rmcdouga Date 2007-06-22 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2007-06-22 Time 13:10 Sent To  
Notes
2007-06-22 13:27:14REVISION TO CHANGE FROM ASPHALT SHINGLES TO CONCRETE
 ROOF TILE IS DENIED.
  
 1) SUBMIT A SIGNED AND SEALED LETTER FROM A FLORIDA
 LICENSED ENGINEER STATING THAT THE EXISTING ROOF
 STRUCTURE IS CAPABLE OF SUPPORTING THE PROPOSED
 CONCRETE ROOF.
  
 2) SPECIFY THE METOD OF ATTACHMENT THAT WILL BE USED TO
 INSTALL THE CONCRETE ROOF TILES. CIRCLE THE FASTENER
 TYPE OR ADHESIVE SYSTEM THAT WILL BE USED ON THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-11 Cont ID  
Sent By rmcdouga Date 2007-06-11 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2007-06-11 Time 15:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-08 Cont ID  
Sent By rmcdouga Date 2007-06-08 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2007-06-08 Time 16:32 Sent To  
Notes
2007-06-08 16:40:52DENIED BY BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE FASTENING OPTION
 SPECIFIED ON PAGE 28 OF THE NOA FOR THE GAF MODIFIED
 ROOFING IS -52.5 PSF IS TOO LOW FOR THE PERIMETER AND
 CORNER AREAS OF THE ROOF. SUBMIT RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER
 7 OF THE NOA. THIS WAS REQUESTED IN ITEM NUMBER 4 OF
 THE FIRST REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By rmcdouga Date 2007-05-30 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2007-05-30 Time 16:10 Sent To  
Notes
2007-05-30 16:50:08DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF
 SYSTEM IS NOT A CLEAR ENOUGH COPY TO BE COPIED FOR
 RECORD KEEPING PURPOSES. SUBMIT TWO CLEAR LEGIBLE
 COPIES. FBC 106.1.3*.
  
 2) THE ASSEMBLY THAT WAS SELECTED IS FOR AN INSULATED
 DECK. IS THIS ROOF DECK GOING TO BE INSULATED?
  
 3) SPECIFY WHICH ONE OF THE FASTENING OPTIONS AND
 DESIGN PRESSURE WILL BE USED. CIRCLE THE CORRECT ONE ON
 THE NOA.
  
 4) THE DESIGN PRESSURE OF -45 PSF ON THE NOA IS TOO LOW
 FOR THE PERIMETER AND CORNER AREAS. SEE GENERAL
 LIMITATION #7 ON PAGE 32, WHICH ALLOWS ENHANCED
 FASTENING. SUBMIT RAS 117 CALCULATIONS AS REQUIRED FOR
 ENHANCED FASTENING.
  
 5) THE WRONG COVERSHEET WAS SUBMITTED FOR THE GAF
 MODIFIED ROOF SYSTEM. THE CORRECT ONE IS FL617-R1.
  
 6) THE COVERSHEET AND NOA FOR THE GAF ROYAL SOVERIGN
 SHINGLES HAVE BEEN REVISED. SUBMIT THE CURRENT ONES
 COVERSHEET FL183-R2 AND NOA 05-1115.11.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-08 Cont ID  
Sent By adarroug Date 2007-06-08 Time 13:12 Rev Time 0.00
Received By adarroug Date 2007-06-08 Time 13:12 Sent To B
Notes
2007-06-08 13:12:51TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-08 Cont ID  
Sent By adarroug Date 2007-05-30 Time 13:12 Rev Time 0.00
Received By adarroug Date 2007-05-30 Time 15:27 Sent To  
Notes
2007-05-30 15:51:13TO "RMCDOUGAL" DESK