Plan Review Details - Permit 07051056
Plan Review Stops For Permit 07051056
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-04 Cont ID  
Sent By amorse Date 2007-07-04 Time 09:13 Rev Time 0.00
Received By amorse Date 2007-07-04 Time 09:13 Sent To PC
Notes
2007-07-04 10:00:44 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS(SEE STRUCTURAL NOTES)
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 639.00 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 7)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 8)CORRECT ADDRESSON PERMIT AND DRAWINGS TO MATCH
 OFFICIAL RECORD FOR THAT PCN WHICH IS 714 - 45 ST
  
 9)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 10)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 11)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR
 MIN BEARING
  
 12)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF
 FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES.
  
 13)DRAWINGS STATE PGT WINDOWS IF YALE OGRON ARE TO BE
 USED REMOVE PGT FROM DRAWINGS, ALSO 3843 SH WINDOWS
 USED IN THE MASTER BEDROOM AND BEDROOM 1 DO NOT MEET
 EGRESS REQUIREMENTS
  
 14)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THATIS RELEVANT PER 9B-72.
 THESE SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
  
 15)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 17)NO PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR
 DOORS, LINTELS, MULLIONS FOR JOINED WINDOWS AND
 CONNECTORS AND STRAPS
  
 18)ENGINEERED TRUSS DRAWINGS ARE MISSING INDIVIDUAL
 TRUSS SHEETS WITH SIGNED AND SEALED COVER SHEET
  
 19)PROVIDE 2 COMPLETE SETS OF ALL DRAWINGS AND
 SUBMITTALS
  
 20)OWNER BUILDER EXEMPTION CANNOT BE CLAIMED FOR
 PROPERTY THAT IS RENTED OR LEASED. THIS OWNER HAS THREE
 PROPERTIES ONE AT 616 - 48TH ST THAT IS CONSIDERED MAIN
 RESIDENCE AND HAS HOMESTEAD EXEMPTION. PLEASE FILL OUT
 A CHANGE OF CONTRACTOR FORM AND HAVE A LICENSED
 CONTRACTOR PERFORM THE WORK.
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By btrobaug Date 2007-06-15 Time 15:09 Rev Time 0.00
Received By btrobaug Date 2007-06-15 Time 13:15 Sent To P
Notes
2007-06-15 13:17:54 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE PANEL SHOWN OVER THE COUNTER IS IN VIOLATION OF
 110.26.
  
 4} INDICATE THE CONDUIT SIZE, WIRE SIZE NUMBER & TYPE,
 BETWEEN THE DISCONNECT AND PANEL ON THE RISER. ALSO SEE
 250.122.
  
 5} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 6} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 7} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 8} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2). SEE MASTER BEDROOM.
  
 9} GFI'S ARE REQUIRED IN THE GARAGE PER 210.8(A)(2).
  
 10} RECEPTACLES ARE REQUIRED AT THE FRONT AND REAR
 OUTSIDE, 210.52(E) AND 210.8(A)(3), GFI.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 09:25 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 09:25 Sent To E
Notes
2007-06-01 09:25:42TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-04 Time   Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 15:57 Sent To  
Notes
2007-05-29 16:00:48TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By tgordon Date 2007-06-01 Time 11:14 Rev Time 0.30
Received By tgordon Date 2007-06-01 Time 11:13 Sent To E
Notes
2007-06-01 11:31:51*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2. AND HAVE ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 3) MECHANICAL PLAN EQUIPMENT SCHEDULE IS CALLING FOR A
 12 SEER A/C SYSTEM, THE MINIMUM SEER THAT MAY BE
 INSTALLED IS 13 SEER, PLEASE CHANGE A/C SYSTEM, SEE
 2004 FBC 13-607.1.ABC.3.2.1.
  
 4) PLEASE SHOW CFM'S OF BATHROOM EXHAUST FAN ON
 MECHANICAL PLAN.
  
 5) PLEASE SHOW THE SIZES OF ALL SUPPLY AIR GRILLS ON
 PLANS.
  
 6) PLEASE SHOW ON MECHANICAL PLAN THE RETURN AIR DUCTS,
 AND HOW AIR IS GETTING BACK TO THE AHU.
  
 7) PLEASE SUBMIT TWO COPY'S OF PLANS AND ALL OTHER
 PAPER WORK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By mperson Date 2007-06-20 Time 13:16 Rev Time 0.45
Received By mperson Date 2007-06-20 Time 13:16 Sent To B
Notes
2007-06-20 14:09:57DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 PLAN REVIEW PER FBC-2004 CHAPTER 1, SECTION 106.1.
  
 2. SHEET A3 PLUMBING RISER: THE SUBMITTED SANITARY
 ISOMETRIC RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. PER FBC-2004 CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELAVENT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. PLEASE REFERENCE THE FOLLOWING RED LINE
 CORRECTIONS ON THIS SHEET FOR THE RESUBMITTAL.
 A} THE UNDERGROUND FITTING FOR THE LAV IS BEING
 INDICATED IN THE WRONG PLACE.
 B} THE WASHING MACHINE BOX AND CLEANOUT ARE BEING
 INDICATED IN THE BEDROOM NOT IN THE LAUNDRY ROOM.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: PLEASE REFERENCE THE THE RED LINE PIPE SIZING FOR
 THE RESUBMITTAL ON SHEET A3 AND THE FOLLOWING THAT IS
 REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE WASHING MACHINE
 STANDPIPE ON THE RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 THREE INCH (3"). PLEASE INDICATE THIS ON THE
 RESUBMITTAL.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
 PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 4. SHEET A3 PLUMBING RISER IS INDICATING THE NEW
 PROPOSED PLUMBING TO "CONNECT TO EXIST. S.S." PLEASE
 CLEARLY INDICATE WHAT "S.S." IS ON THE RESUBMITTAL AND
 THAT PER FBC-2004, PLUMBING, SECTION 909.1, ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. PLEASE CLEARLY INDICATE THIS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By choops Date 2007-05-31 Time 16:23 Rev Time 0.00
Received By choops Date 2007-05-31 Time 16:23 Sent To I
Notes
2007-05-31 16:30:07***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH DIMENSIONS AND SETBACK
 DIMENSIONS FROM PROPERTY LINES.
  
 2)PLEASE SHOW ANY RELOCATED MECHANICAL EQUIPMENT ON
 SURVEYS AND SITE PLANS SHOWING THE SETBACK DIMENSION
 FROM PROPERTY LINES.
  
 3)PLEASE SHOW ELEVATION FROM GRADE TO THE MIDPOINT
 OF THE ROOF'S PITCH.
  
 4)PROVIDE 2 COPIES OF ALL SITE PLANS, ELEVATIONS,
 ETC...
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720