Plan Review Details - Permit 07051013
Plan Review Stops For Permit 07051013
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 11:05 Rev Time 0.00
Received By mawillia Date 2007-07-11 Time 10:26 Sent To  
Notes
2007-07-11 10:47:57*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED.PLAN SHEETS STAMPED, INITIALED, AND DATED;
 READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mawillia Date 2007-06-13 Time 12:15 Rev Time 0.00
Received By mawillia Date 2007-06-13 Time 11:06 Sent To  
Notes
2007-06-13 12:08:31*****DENIED*****
  
  
 1.DUE TO THE TINT OF THE SUBMITTED PLAN SHEETS, THIS
 WRITER WAS UNABLE TO READ WORDING IN SOME OF THE
 DETAILS.
  
 2.AMEND GENERAL NOTE #1 TO REFLECT THAT NFPA 13 (2002
 EDITION) IS REFERENCED.
  
 3.SHOW THE LOCATION AND THE DETAIL OF THE FIRE
 DEPARTMENT CONNECTION.
  
 4.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION PRIOR TO THE FINAL SPRINKLER
 INSPECTION.FOR AN APPLICATION, CONTACT WEST PALM
 BEACH FIRE PREVENTION AT 561-804-4724.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 15:50 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 15:50 Sent To FIRE
Notes
2007-07-03 15:50:56TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By mawillia Date 2007-06-13 Time 11:31 Rev Time 0.00
Received By mawillia Date 2007-05-29 Time 11:10 Sent To  
Notes
2007-05-29 11:10:36TO "F" BOX