Plan Review Details - Permit 07051000
Plan Review Stops For Permit 07051000
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-31 Cont ID  
Sent By amorse Date 2007-07-31 Time 15:29 Rev Time 0.00
Received By amorse Date 2007-07-31 Time 15:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-01 Cont ID  
Sent By amorse Date 2007-07-01 Time 15:45 Rev Time 0.00
Received By amorse Date 2007-07-01 Time 15:45 Sent To PC
Notes
2007-07-01 15:58:41 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)PROVIDE COMPLETE SCOPE OF WORK ON THE DRAWINGS
  
 3)PROVIDE EXISTING FLOOR PLAN SHOWING PROPOSED DEMO
 OR REMOVAL AND NEW FLOOR PLAN
  
 4)A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303 , 304 AND 305 OF THE FBC EXISTING.
  
 5)PER FLORIDA STATUTE 481.229 EXEMPTION FROM
 ARCHITECTURAL LICENSURE DOES NOT EXEMPT PERSON
 RESPONSIBLE TO SIGN AND DATE SAID PLANS
  
 6)WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS PER
 313.1.1 FBC RES.
  
 7)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A PERMIT BEING
 ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 11:37 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 11:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By btrobaug Date 2007-06-01 Time 11:19 Rev Time 0.33
Received By btrobaug Date 2007-06-01 Time 09:50 Sent To P
Notes
2007-06-01 11:19:20 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI, PLEASE
 LOCATE SAME ON PLANS.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 NOTE:R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS
 REQUIRED IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE
 TEXT.
  
 713.13NOTICE OF COMMENCEMENT.--
  
 (1)(A)EXCEPT FOR AN IMPROVEMENT THAT IS EXEMPT
 PURSUANT TO S. 713.02(5), AN OWNER OR THE OWNER'S
 AUTHORIZED AGENT BEFORE ACTUALLY COMMENCING TO IMPROVE
 ANY REAL PROPERTY, OR RECOMMENCING COMPLETION OF ANY
 IMPROVEMENT AFTER DEFAULT OR ABANDONMENT, WHETHER OR
 NOT A PROJECT HAS A PAYMENT BOND COMPLYING WITH S.
 713.23, SHALL RECORD A NOTICE OF COMMENCEMENT IN THE
 CLERK'S OFFICE AND FORTHWITH POST EITHER A CERTIFIED
 COPY THEREOF OR A NOTARIZED STATEMENT THAT THE NOTICE
 OF COMMENCEMENT HAS BEEN FILED FOR RECORDING ALONG WITH
 A COPY THEREOF. THE NOTICE OF COMMENCEMENT SHALL
 CONTAIN THE FOLLOWING INFORMATION:
  
 THE OWNER/BUILDER DISCLOSURE STATEMENT MUST BE SIGNED
 BY SAME, NOT AN AGENT. SEE FORM. PLEASE COME IN WHEN
 RESUBMITTING AND SIGN SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 16:12 Sent To P
Notes
2007-08-02 16:12:49TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 15:40 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 15:40 Sent To E
Notes
2007-07-13 15:41:19TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-01 Time   Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 09:55 Sent To  
Notes
2007-05-29 09:55:43TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 16:33 Rev Time 0.20
Received By tgordon Date 2007-06-19 Time 16:33 Sent To B
Notes
2007-06-19 16:33:51NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-30 Cont ID  
Sent By mperson Date 2007-07-31 Time 16:37 Rev Time 0.33
Received By mperson Date 2007-07-30 Time 16:37 Sent To B
Notes
2007-07-30 16:59:15****************PROVISO****************
 NOTE: A SEPERATE PLUMBING PERMIT IS REQUIRED. A
 PLUMBING PERMIT WAS NOT APPLIED FOR AT THE TIME OF THE
 ORIGINAL PERMIT APPLICATION DATED 5/25/07. THE PLUMBING
 PERMIT CAN BE ATTAINED BY REFERENCING THE MASTER
 #07051000 ONCE IT IS PERMITTED.
  
  
 NOTE: THE GAS PERMIT APPLICATION #07070372 WAS PULLED
 FROM THIS SUBMITTAL AND WAS REVIEWED SEPERATE FROM THIS
 PERMIT APPLICATION. THE GAS PERMIT WAS NOT APPLIED FOR
 AT THE TIME OF THIS ORIGINAL PERMIT APPLICATION DATED
 5/25/07. THE GAS PIPING ON THIS DRAWING HAS BEEN
 REMOVED AND WILL BE ADDRESSED ON THE GAS PERMIT
 APPLICATION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By mperson Date 2007-06-19 Time 11:14 Rev Time 0.33
Received By mperson Date 2007-06-19 Time 11:14 Sent To M
Notes
2007-06-19 11:24:56DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. MORE INFORMATION IS REQUIRED. PLEASE INDICATE ON
 THE DRAWING THE EXISTING KITCHEN FLOOR PLAN LAYOUT, AND
 ON A SEPERATE DRAWING PLEASE INDICATE THE NEW PROPOSED
 KITCHEN FLOOR PLAN LAYOUT.
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE FOLLOW WHAT IS REQUIRED IN
 COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 4. PLEASE PROVIDE A NOTICE OF COMMENCEMENT RECORDED
 WITH THE CLERK OF COURT AND REFERENCE THE ELECTICAL
 COMMENT ON OWNER/BUILDER DISCLOSER REQUIREMENTS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved