Plan Review Details - Permit 07050992
Plan Review Stops For Permit 07050992
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By jwitmer Date 2007-07-16 Time 16:11 Rev Time 0.00
Received By mawillia Date 2007-08-16 Time 22:33 Sent To  
Notes
2007-07-16 16:43:173301 ELECTRONIC WAY
 BUILDING PLAN REVIEW
 PERMIT: 07050992
 ADD: 3301 ELECTRONIC WAY
 CONT: SHAFFER ELECTRICAL
 TEL: (954)868-9411
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)) GENERATOR SLAB & ANCHOR REQUIREMENTPLEASE
 PROVIDE SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS
 WITH THE INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE
 OF FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOADREDUCTION.SECOND, PROVIDE
 INFORMATION ON THE SLAB, THICKNESS, WIDTH AND LENGTH,
 IF WIREMESH, FIBER MESH OR IF STEEL REBAR WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 4) 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION
 RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW
 CONSTRUTION WITH BASE FLOOD ELEVATION, CITY CODE
 REQUIRES AN ADDITIONAL 6".
  
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 16:15 Sent To  
Notes
2007-06-23 16:29:29*** UNSAT ***
  
  
 1) NOTE: PLEASE SUBMIT PLANS WITH A COMPLETE LAYOUT OF
 ALL EXISTING ELECTRICAL SERVICE EQUIPMENT AT THIS
 BUILDING. PLEASE INDICATE ALL MAINS, DISCONNECTS ETC.
 AT THIS TIME AS THE LOCATION OF THESE ITEMS ARE NOT
 CLEAR, NO REVIEW OF LOCATIONS CAN BE DONE.
 FBC 106.1.2, 106.3.5.1.2
 NEC 230.70,230.71,230.72, 225.31-225.39, 702.11 PLEASE
 SEE MISSING DISCONNECTING MEANS AS REQUIRED. THIS IS
 BASED ON NO INFORMATION PROVIDED.
  
 2) NOTE: PLEASE SUBMIT A COMPLETE SURVEY WITH ALL
 SETBACKS ON PLANS FOR EQUIPMENT ETC.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES FOR
 THIS.
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW IF THIS IS INDEED IN A FLOOD ZONE,
 THE ELEVATION OF UNIT WILL NEED TO BE ON PLANS. PLEASE
 KNOW THAT AN ELEVATION CERTIFICATE WILL BE REQUIRED
 BEFORE FINAL.
  
 4) NOTE: PLEASE SEE LOAD CALCULATIONS MENTIONS 2-WORK
 STATIONS AND CONTRACT MENTIONS THREE. THE LOAD ON THE
 GENERATOR IS NOT OF A CONCERN HOWEVER PLEASE CORRELATE
 FOR RECORD SETS OF PLANS.
 FBC 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By mawillia Date 2007-08-16 Time 23:20 Rev Time 0.00
Received By mawillia Date 2007-08-16 Time 22:35 Sent To  
Notes
2007-08-16 22:41:24*****DENIED*****
  
  
 1.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED WITH COMPLIANCE WITH NFPA
 110.
  
 2.EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE
 IN ACCORDANCE WITH NFPA 54.
  
 3.SPECIFY WHAT EQUIPMENT WILL BE POWERED BY THE
 GENERATOR.
  
 4.PROVIDE PROPER SETBACKS TO PROPERTY LINES AND AT
 LEAST 10' DISTANCE TO BUILDING OPENINGS.
  
 5.PROVIDE MANUFACTURE SPEC SHEETS FOR THE EQUIPMENT.
  
 6.DETAIL HOW THE EQUIPMENT WILL BE PROTECTED FROM
 VEHICULAR AND / OR MECHANICAL DAMAGE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By kstevens Date 2007-07-09 Time 10:20 Rev Time 0.00
Received By kstevens Date 2007-07-07 Time 19:01 Sent To  
Notes
2007-07-09 10:24:56DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. WHEN SUBMITTING THE UP TO DATE SITE PLAN, INDICATE
 THE DISTANCE OFF THE STRUCTURE TO THE GENERATOR.
  
 2. SUBMIT MANUF. INSTALLATION INSTRUCTIONS WITH THE
 APPLICATION SHOWING THE MINIMUM REQUIRED CLEARANCES
 REQUIRED FOR MAINTENANCE AND SERVICE OF THE GENERATOR.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-17 Cont ID  
Sent By mawillia Date 2007-08-17 Time 08:23 Rev Time 0.00
Received By mawillia Date 2007-05-29 Time 10:19 Sent To  
Notes
2007-06-14 14:01:34TO "COMM" BD#21
2007-05-29 10:20:01WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By rregueir Date 2007-06-28 Time 11:56 Rev Time 0.00
Received By rregueir Date 2007-06-28 Time 08:06 Sent To  
Notes
2007-06-28 11:01:18------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA
 110-02
  
 1. PLEASE INDICATE IN SITE PLAN THE LOCATION OF NEAREST
 OPENINGS IN THE BUILDING, AND THE DISTANCE TO THE
 GENERATOR, INCLUDING: DOORS, WINDOWS, SIFFIT VENTS, AIR
 INTAKES.
  
 2. PLEASE PROVIDE ACTUA ELEVATIONS SHOWING THE
 ELEVATION OF THE GENERATOR TO BE ABOVE THE BASE FLOOD
 ELEVATION. ALSO, SLAB SHALL RAISE THE GENERATOR MINIMUM
 6" ABOVE GRADE LEVEL PER NFPA 110-7.4.1.1.
  
 3. PLEASE INDICATE ON PLAN THE DISTANCE OF THE
 GENERATOR FROM THE BUILDING AND PROVIDE WALL
 CONSTRUCTION TYPE TO VERIFY PROPER CLEARANCE FROM
 COMBUSTIBLES. ALSO, PLEASE PROVIDE MINIMUM REQUIRED
 CLEARANCE FOR SERVICE, MAINTENANCE AND INSPECTION PER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, WHICH WERE
 NOT INCLUDED WITH THIS APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By jbabcock Date 2007-06-26 Time 08:21 Rev Time 0.00
Received By jbabcock Date 2007-06-28 Time 08:13 Sent To  
Notes
2007-06-26 08:21:46PLANNING AND ZONING ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE A SIGNED AND SEALED SURVEY THAT WAS CREATED
 WITHIN A YEAR.
  
 3. PROVIDE SETBACKS FROM THE GENERATOR TO THE NORTH AND
 WEST PROPERTY LINES.PURSUANT TO SECTION 94-305(4)
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK. WINDOW AIR-CONDITIONING UNITS MAY
 NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED SIDE
 SETBACK.
  
 4. PURSUANT TO SECTION 94-444 (B) ALL GENERATORS AND
 TANKS SHALL BE SCREENED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS. PROVIDE DETAILS/CROSS SECTIONS
 ACCORDINGLY ON PLANS.
  
 FOR ANY ADDITIONAL INFORMATION OR QUESTIONS YOU MAY
 CONTACT:
  
 JULIA BABCOCK
 PLANNER
 (561) 822-1442
 [email protected]