Plan Review Details - Permit 07050991
Plan Review Stops For Permit 07050991
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By jwitmer Date 2007-08-27 Time 07:22 Rev Time 0.22
Received By jwitmer Date 2007-08-27 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By jwitmer Date 2007-07-16 Time 18:44 Rev Time 2.22
Received By jwitmer Date 2007-07-16 Time 16:50 Sent To  
Notes
2007-07-16 19:14:121009 BANYAN WPB WATER TREATMENT PHASE I
 BUILDING PLAN REVIEW
 PERMIT: 07050991
 ADD: 1009 BANYAN BLVD
 CONT: CARDINAL CONTRACTORS, INC.
 TEL: (954)587-6653
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) PLEASE PROVIDE INFORMATIION ON THE NEW FERRIC SULATE
 STORAGE TANK. HOW MUCH OF THIS CHEMICAL WILL BE IN THE
 TANK? WHAT PRECAUTIONS WILL BE TAKEN FOR THIS HEALTH
 HAZARDOUS MATERIAL?
  
 3) FOR THE FERRIC SULFATE TANK AND TRANSFER PUMP HOW
 WILL IT BE HELD IN PLACE TO RESIST THE MOMENT OF OVER
 TURNING? TABLE 1609.2.2, 1609,
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY SEE TABLE 1604.5 IMPORTANCE FACTOR OF 1.15 3)-
 WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)PROVIDE ADDITIONAL INFORMATION ON THE MODIFICATION
 OF HAOH AND FESO4 CHEMICAL SYSTEMS IN THE CHEMICAL
 BUILDING. 106.1.2.
  
 5) PROVIDE ADDITIONAL INFORMATION ON THE SOIUM
 HYDROXIDE, QUANITITIES TO BE STORED. SHEET C2 NOTE 9
 INDICATES THAT NO SECONDARY CONTAINMENTPIPING IS TO
 BE USED?
 PROVIDE PLAN FOR IF A LINE BREAKS HOW WILL THE
 MATERIALS BE RETRIEVED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-05-29 Cont ID  
Sent By dpalmer Date 2008-05-29 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2008-05-29 Time 15:39 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-02 Cont ID  
Sent By dpalmer Date 2008-04-02 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2008-04-02 Time 17:22 Sent To  
Notes
2008-04-02 17:23:10** DENIEDREVISIONS **
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED ARE NOT
 COMPLETE. PLEASE SEE THE THIRD SET IS MISSING SHEETS
 16,6 OF 7, 15-5 OF 7, 14 4 OF 7.
 ** KEEP IN MIND FOR THIS SCOPE OF WORK ONLY TWO SETS
 ARE REQUIRED HOWEVER IF A THIRDSET IS DESIRED TO BE
 REVIEWED AND STAMPED THEN PLEASE SUBMIT THREE SETS.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE NOT COMPLETE
 WITH ALL INFORMATION REQUIRED PER FAC 61G15-23.002.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 PER FS 471.023
 PLEASE SEE MISSING ADDRESS OF FIRM. PLEASE BE SURE TO
 COORDINATE WITH LICENSING INFORMATION.
 PLEASE SEE MISSING PHONE NUMBER ETC AS REQUIRED PER
 SECTION ABOVE.
 THIS IS REQUIRED FOR ALL SHEETS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 19:18 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 18:53 Sent To  
Notes
2007-06-20 19:19:22*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS SHALL HAVE CODES STATED WHICH
 ARE RELEVANT TO PROJECT AND DESIGN. THE FOLLOWING CODES
 ARE TO BE STATED ON BOTH ELECTRICAL AND ARCHITECTURAL
 SHEETS AS ADOPTED BY THE STATE OF FLORIDA AS OF
 DECEMBER 8TH, 2006.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 ** OTHER CODES MAY BE REQUESTED FROM OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION ON
 ELECTRICAL SHEETS AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002
 PLEASE SEE THE ADDRESS AS SHOWN ON OTHER SHEETS DOES
 NOT CORRELATE WITH THE STATE WEBSITE. PLEASE KNOW IF
 THERE IS A MAIN OFFICE FOR FIRM PLEASE LIST ON TITLE
 BLOCKS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 10:51 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 10:20 Sent To  
Notes
2007-08-30 10:51:13*****APPROVED*****
  
  
 C2 SHEET 2 OF 6 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-20 Cont ID  
Sent By mwennerg Date 2007-07-20 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2007-07-20 Time 11:11 Sent To  
Notes
2007-07-20 11:20:50***DENIED***
  
 1) PLEASE PROVIDE MORE INFORMATION REGARDING QUANTITY
 AND TYPE OF CHEMICALS TO BE STORED.
  
 2) FACILITY MSDS SHEETS TO BE UPDATED AS NECESSARY.
  
 3) HOW WILL WORK IMPACT EMERGENCY VEHICLE ACCESS INTO
 EXISTING PROPERTY.
  
 4) PLEASE PROVIDE APPLICABLE CODES AND EDITIONS FOR THE
 SCOPE OF THIS WORK.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 14:51 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 14:51 Sent To E
Notes
2008-05-16 14:52:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 15:16 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 15:16 Sent To E
Notes
2008-05-02 15:17:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 11:04 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 11:04 Sent To  
Notes
2008-03-27 11:09:21TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 14:11 Sent To  
Notes
2007-08-01 12:09:39TO "COMM" BD#39
2007-07-30 14:12:02WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-20 Cont ID  
Sent By mwennerg Date 2007-07-20 Time 11:23 Rev Time 0.00
Received By mwennerg Date 2007-05-29 Time 13:27 Sent To  
Notes
2007-06-15 08:25:14TO "COMM" BD#44--CITY PROJECT
2007-05-29 13:27:19WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2008-04-11 Cont ID  
Sent By rregueir Date 2008-04-11 Time 14:41 Rev Time 0.00
Received By rregueir Date 2008-04-11 Time 14:41 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-18 Cont ID  
Sent By rregueir Date 2007-08-18 Time 09:29 Rev Time 0.00
Received By rregueir Date 2007-08-17 Time 17:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By rregueir Date 2007-06-23 Time 09:20 Rev Time 0.00
Received By rregueir Date 2007-06-22 Time 15:56 Sent To  
Notes
2007-06-23 09:19:54-----------------DENIED-------------------
  
 1. PLEASE SHOW ALL NEW STORAGE TANKS AND EQUIPMENT TO
 BE SECURED PER THE WIND LOAD REQUIREMENTS OF FBC 1609
 WITH A WIND LOAD IMPORTANCE FACTOR OF 1.15 AS
 DETERMINED BY FBC TABLE 1604.5 IN ACCORDANCE WITH FBC,M
 301.13.
  
 2. ADDRESS SHOWN ON TITLE BLOCK FOR ENGINEERING FIRM DO
 NOT MATCH DBPR RECORDS UNDER THE CERTIFICATE OF
 AUTHORIZATION. PLEASE UPDATE STATE RECORDS OR CORRECTLY
 SHOW ENGINEERING FIRM ADDRESS ON PLANS PER FAC RULE
 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 09:54 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 09:54 Sent To  
Notes
2008-04-12 09:55:36REVISIONS OK--SHTS 8 OF 18, 9 OF 18 & 10 OF 18.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By kstevens Date 2007-08-27 Time 12:36 Rev Time 0.00
Received By kstevens Date 2007-08-27 Time 12:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By kstevens Date 2007-07-13 Time 09:11 Rev Time 0.00
Received By kstevens Date 2007-07-13 Time 09:11 Sent To  
Notes
2007-07-13 09:39:02DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHEETS G1, C1 THRU C6, P1 & M1 THRU M19. THE ADDRESS
 IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS ON THE
 STATE OF FLORIDA DBPR WEBSITE. PLEASE UPDATE
 INFORMATION ON THE DBPR WEBSIET OR IN THE TITLE BLOCKS
 PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1) &
 FS 481.2055.
  
 2. ALL ELECTRICAL & INSTRUMENT SHEETS. THE FOLLOWING IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET:
 (1) THE FIRM ADDRESS & TELPHONE NUMBER (SEE COMMENT
 1)
 (2) THE FIRM LICENSE NUMBER
 FAC 61G1-16.004(1)(2) & FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]