| Plan Review Stops For Permit 07050991 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-27 |
Time |
07:22 |
Rev Time |
0.22 |
| Received By |
jwitmer |
Date |
2007-08-27 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-16 |
Time |
18:44 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-07-16 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2007-07-16 19:14:12 | 1009 BANYAN WPB WATER TREATMENT PHASE I | | | BUILDING PLAN REVIEW | | | PERMIT: 07050991 | | | ADD: 1009 BANYAN BLVD | | | CONT: CARDINAL CONTRACTORS, INC. | | | TEL: (954)587-6653 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2) PLEASE PROVIDE INFORMATIION ON THE NEW FERRIC SULATE | | | STORAGE TANK. HOW MUCH OF THIS CHEMICAL WILL BE IN THE | | | TANK? WHAT PRECAUTIONS WILL BE TAKEN FOR THIS HEALTH | | | HAZARDOUS MATERIAL? | | | | | | 3) FOR THE FERRIC SULFATE TANK AND TRANSFER PUMP HOW | | | WILL IT BE HELD IN PLACE TO RESIST THE MOMENT OF OVER | | | TURNING? TABLE 1609.2.2, 1609, | | | 2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY SEE TABLE 1604.5 IMPORTANCE FACTOR OF 1.15 3)- | | | WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | 4)PROVIDE ADDITIONAL INFORMATION ON THE MODIFICATION | | | OF HAOH AND FESO4 CHEMICAL SYSTEMS IN THE CHEMICAL | | | BUILDING. 106.1.2. | | | | | | 5) PROVIDE ADDITIONAL INFORMATION ON THE SOIUM | | | HYDROXIDE, QUANITITIES TO BE STORED. SHEET C2 NOTE 9 | | | INDICATES THAT NO SECONDARY CONTAINMENTPIPING IS TO | | | BE USED? | | | PROVIDE PLAN FOR IF A LINE BREAKS HOW WILL THE | | | MATERIALS BE RETRIEVED. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-29 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-29 |
Time |
15:39 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-04-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-02 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-02 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2008-04-02 17:23:10 | ** DENIEDREVISIONS ** | | | | | | 1) NOTE: PLEASE SEE THE PLANS SUBMITTED ARE NOT | | | COMPLETE. PLEASE SEE THE THIRD SET IS MISSING SHEETS | | | 16,6 OF 7, 15-5 OF 7, 14 4 OF 7. | | | ** KEEP IN MIND FOR THIS SCOPE OF WORK ONLY TWO SETS | | | ARE REQUIRED HOWEVER IF A THIRDSET IS DESIRED TO BE | | | REVIEWED AND STAMPED THEN PLEASE SUBMIT THREE SETS. | | | | | | 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE NOT COMPLETE | | | WITH ALL INFORMATION REQUIRED PER FAC 61G15-23.002. | | | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER | | | PER FS 471.023 | | | PLEASE SEE MISSING ADDRESS OF FIRM. PLEASE BE SURE TO | | | COORDINATE WITH LICENSING INFORMATION. | | | PLEASE SEE MISSING PHONE NUMBER ETC AS REQUIRED PER | | | SECTION ABOVE. | | | THIS IS REQUIRED FOR ALL SHEETS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-06 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-06 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-20 |
Time |
19:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-20 |
Time |
18:53 |
Sent To |
|
|
| Notes |
| 2007-06-20 19:19:22 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE PLANS SHALL HAVE CODES STATED WHICH | | | ARE RELEVANT TO PROJECT AND DESIGN. THE FOLLOWING CODES | | | ARE TO BE STATED ON BOTH ELECTRICAL AND ARCHITECTURAL | | | SHEETS AS ADOPTED BY THE STATE OF FLORIDA AS OF | | | DECEMBER 8TH, 2006. | | | 2004 FBC W/2006 REVISIONS. | | | 2005 NFPA-70 | | | ** OTHER CODES MAY BE REQUESTED FROM OTHER TRADES. | | | | | | 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION ON | | | ELECTRICAL SHEETS AS REQUIRED PER FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.002 | | | PLEASE SEE THE ADDRESS AS SHOWN ON OTHER SHEETS DOES | | | NOT CORRELATE WITH THE STATE WEBSITE. PLEASE KNOW IF | | | THERE IS A MAIN OFFICE FOR FIRM PLEASE LIST ON TITLE | | | BLOCKS. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-30 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2007-08-30 10:51:13 | *****APPROVED***** | | | | | | | | | C2 SHEET 2 OF 6 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-20 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-20 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2007-07-20 11:20:50 | ***DENIED*** | | | | | | 1) PLEASE PROVIDE MORE INFORMATION REGARDING QUANTITY | | | AND TYPE OF CHEMICALS TO BE STORED. | | | | | | 2) FACILITY MSDS SHEETS TO BE UPDATED AS NECESSARY. | | | | | | 3) HOW WILL WORK IMPACT EMERGENCY VEHICLE ACCESS INTO | | | EXISTING PROPERTY. | | | | | | 4) PLEASE PROVIDE APPLICABLE CODES AND EDITIONS FOR THE | | | SCOPE OF THIS WORK. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-16 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-16 |
Time |
14:51 |
Sent To |
E |
|
| Notes |
| 2008-05-16 14:52:20 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-02 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-02 |
Time |
15:16 |
Sent To |
E |
|
| Notes |
| 2008-05-02 15:17:18 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-27 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-27 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2008-03-27 11:09:21 | TO "COMM" BD#25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-30 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-30 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2007-08-01 12:09:39 | TO "COMM" BD#39 | | 2007-07-30 14:12:02 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-20 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-29 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2007-06-15 08:25:14 | TO "COMM" BD#44--CITY PROJECT | | 2007-05-29 13:27:19 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2008-04-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-04-11 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-04-11 |
Time |
14:41 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-18 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-17 |
Time |
17:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-23 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-22 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2007-06-23 09:19:54 | -----------------DENIED------------------- | | | | | | 1. PLEASE SHOW ALL NEW STORAGE TANKS AND EQUIPMENT TO | | | BE SECURED PER THE WIND LOAD REQUIREMENTS OF FBC 1609 | | | WITH A WIND LOAD IMPORTANCE FACTOR OF 1.15 AS | | | DETERMINED BY FBC TABLE 1604.5 IN ACCORDANCE WITH FBC,M | | | 301.13. | | | | | | 2. ADDRESS SHOWN ON TITLE BLOCK FOR ENGINEERING FIRM DO | | | NOT MATCH DBPR RECORDS UNDER THE CERTIFICATE OF | | | AUTHORIZATION. PLEASE UPDATE STATE RECORDS OR CORRECTLY | | | SHOW ENGINEERING FIRM ADDRESS ON PLANS PER FAC RULE | | | 61G15-23.002. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-04-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-12 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-12 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2008-04-12 09:55:36 | REVISIONS OK--SHTS 8 OF 18, 9 OF 18 & 10 OF 18. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-27 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-27 |
Time |
12:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-13 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-07-13 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2007-07-13 09:39:02 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHEETS G1, C1 THRU C6, P1 & M1 THRU M19. THE ADDRESS | | | IN THE TITLE BLOCK DOES NOT REFLECT THE ADDRESS ON THE | | | STATE OF FLORIDA DBPR WEBSITE. PLEASE UPDATE | | | INFORMATION ON THE DBPR WEBSIET OR IN THE TITLE BLOCKS | | | PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1) & | | | FS 481.2055. | | | | | | 2. ALL ELECTRICAL & INSTRUMENT SHEETS. THE FOLLOWING IS | | | REQUIRED IN THE TITLE BLOCK OF EACH SHEET: | | | (1) THE FIRM ADDRESS & TELPHONE NUMBER (SEE COMMENT | | | 1) | | | (2) THE FIRM LICENSE NUMBER | | | FAC 61G1-16.004(1)(2) & FS 481.2055 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|