Plan Review Details - Permit 07050990
Plan Review Stops For Permit 07050990
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mjacobs Date 2007-06-11 Time 10:36 Rev Time 0.00
Received By mjacobs Date 2007-06-11 Time 10:36 Sent To PC
Notes
2007-06-11 10:35:36BUILDING PLAN REVIEW
 PERMIT: 07050990
 ADD: 285 CORDOVA RD
 CONT: OWNER (ERIC HANSEN)
 TEL: (561)818-3225
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3)THE FORMULAR FOR THE STAIRS ON SHEET A.1 STATES
 "2R+1T=24-25, HOWEVER, WHEN THE FORMULAR IS USED WITH
 THE NUMBERS STATEDON SHEET S.2, THE TOTAL WILL BE
 MORE THAN 25.ON SHEET A.1 WHAT DOES THE 5" REPRESENTS
 ON THE STAIRS? CLARIFY. SEE R311.5.3
  
 4)THE INFORMATION ON SHEET S.3 SHOWS TWO DIFFERENT
 TYPES OF RAFTER SIZE. CLEARLY INDICATE WHICH TYPE OF
 ROOF RAFTER WILL BE INSTALLED FOR THE PROJECT. SHEET
 A.2 AND SHEET A.3 STATES THE RAFTERS WILL BE INSTALLED
 AT 36" OC, HOWEVER, SHEET S.3 STATES 32" OC. WHICH IS
 IT? FBC 106.1.1. CONSTRUCTION DOCUMENTS SHAL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 5)SHOW ALL DIMENTIONS PERTAINING TO THE ROOF ON THE
 DRAWINGS INCLUDING THE SLOPE OF NEW ROOF.
  
 6)SHEET S.2 DETAIL #3 THE CLOUMN AS HEAVY TIMBER.
 INDICATE THE SIZE OF THE COLUMNS. IF THESE ARE HEAVY
 TIMBER COLUMNS, WHY SHEETS A.2 AND A.3 STATES "CYPRESS
 2X12 VENEER OVER CMU COLUMN?
  
 7)THE FLOOR JOIST SHALL BE OF PRESERVATIVELY TREATED
 LUMBER. SEE R502 FOR MORE INFORMATION. INDICATE THE
 JOIST SPACING ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 09:15 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 09:15 Sent To B
Notes
2007-07-03 09:15:54TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-29 Cont ID  
Sent By mjacobs Date 2007-05-29 Time 11:48 Rev Time 0.00
Received By mjacobs Date 2007-05-29 Time 11:48 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved