Plan Review Details - Permit 07050924
Plan Review Stops For Permit 07050924
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-08-20 Cont ID  
Sent By mperson Date 2007-08-20 Time 08:51 Rev Time 0.33
Received By mperson Date 2007-08-20 Time 08:51 Sent To PC
Notes
2007-08-20 08:52:56REVISION: REPLACE EXISTING DAMAGED 3/4" GALV. GAS LINE.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-27 Cont ID  
Sent By pschmitz Date 2007-06-27 Time 08:11 Rev Time 0.00
Received By pschmitz Date 2007-06-27 Time 08:11 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By mperson Date 2007-06-19 Time 08:26 Rev Time 0.33
Received By mperson Date 2007-06-19 Time 08:26 Sent To PC
Notes
2007-06-19 08:37:04DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
 NOTE: MORE INFORMATION IS REQUIRED FOR PLAN REVIEW.
 RECORDS INDICATE THAT RESIDENCE HAS EXISTING GAS.
 PLEASE REFERENCE THE ATTACHED PERMIT INFORMATION TO THE
 GAS PLAN REVIEW COMMENTS INDICAING THIS. PLEASE PROVIDE
 THE FOLLOWING INFORMATION TO MEET CODE COMPLIANCE.
 PLEASE REFERENCE THE ENCLOSED CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS FOR FUTURE PERMIT
 APPLICATIONS.
  
 1. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING SYSTEM.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING SYSTEM.
  
 3. PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL OF
 THE PROPOSED POOL HEATER.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 15:48 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 15:48 Sent To G
Notes
2007-08-16 15:51:11TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 13:57 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 13:57 Sent To G
Notes
2007-06-24 13:58:13TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-19 Cont ID  
Sent By mperson Date 2007-06-19 Time 08:39 Rev Time 0.00
Received By mperson Date 2007-05-23 Time 15:09 Sent To  
Notes
2007-06-12 15:09:16TO "G" BOX